Place the unit as close to the conditioned space as possible allowing clearances as indi-
cated. Run ducts as directly as possible to supply and return outlets. Use of non-flam-
mable weatherproof flexible connectors on both supply and return connections at unit to
reduce noise transmission is recommended.
On ductwork exposed to outside temperature and humidity, use a minimum of 2” of
insulation and a vapor barrier. Distribution system in attic, furred space or crawl space
should be insulated with at least 2” of insulation. Half-inch to 1” thick insulation is usually
sufficient for ductwork inside the air conditioned space.
Provide balancing dampers for each branch duct in the supply system. Properly support
ductwork from the structure.
IMPORTANT:
In the event that the return air ducts must be run through an “unconfined”
space containing other fuel burning equipment, it is imperative that the user/homeowner
must be informed against future changes in construction which might change this to a
“confined space.” Also, caution the user/homeowner against any future installation of
additional equipment (such as power ventilators, clothes dryers, etc.), within the existing
unconfined and/or confined space which might create a negative pressure within the
vicinity of other solid, liquid, or gas fueled appliances.
J. RETURN AIR
!
WARNING
NEVER ALLOW PRODUCTS OF COMBUSTION OR THE FLUE PRODUCTS TO
ENTER THE RETURN AIR DUCTWORK, OR THE CIRCULATING AIR SUPPLY.
ALL RETURN DUCTWORK MUST BE ADEQUATELY SEALED AND SECURED
TO THE FURNACE WITH SHEET METAL SCREWS, AND JOINTS TAPED. ALL
OTHER DUCT JOINTS MUST BE SECURED WITH APPROVED CONNECTIONS
AND SEALED AIRTIGHT.
FAILURE TO PREVENT PRODUCTS OF COMBUSTION FROM BEING CIRCU-
LATED INTO THE LIVING SPACE CAN CREATE POTENTIALLY HAZARDOUS
CONDITIONS, INCLUDING CARBON MONOXIDE POISONING THAT COULD
RESULT IN PERSONAL INJURY OR DEATH.
FIGURE 10A
FLAT ROOFTOP INSTALLATION, ATTIC OR DROP CEILING DISTRIBUTING
SYSTEM. MOUNTED ON ROOFCURB. CURB MUST BE LEVEL.
ST-A1111-03
FIGURE 10B
FLAT ROOFTOP INSTALLATION, ATTIC OR DROP CEILING DISTRIBUTING
SYSTEM. MOUNTED ON ROOFCURB. CURB MUST BE LEVEL.
ST-A1111-03
Summary of Contents for RKKL Series
Page 9: ...9 Illustration ST A0801 17 I FIGURE 6 ROOFCURB INSTALLATION FIGURE 5 ST A1154 02 00...
Page 41: ...41 TABLE 9 AIR FLOW PERFORMANCE 12 5 TON 43 9 kW RKKL B120 MODELS...
Page 45: ...45 FIGURE 21...
Page 46: ...46 FIGURE 22...
Page 47: ...47 FIGURE 23...
Page 48: ...48 FIGURE 24...
Page 49: ...49 FIGURE 25...
Page 50: ...50 FIGURE 26...
Page 51: ...51 FIGURE 27 RKKL SYSTEM CHARGE CHART...
Page 54: ...54...
Page 55: ...55...
Page 56: ...56 CM 1110...