MECHANICAL SPECIFICATIONS—RKKB/RKMB/RKNB- SERIES

General

Units shall be convertible airflow. Operating
range for units with electromechanical
controls shall be between 125°F (51.7°C)
and 50°F (4.4°C). Cooling performance
shall be rated in accordance with DOE
and/or ARI testing procedures. All units
shall be factory assembled, internally 
wired, fully charged with R-22, and 100
percent run-tested before leaving the
factory. Wiring internal to the unit shall 
be colored and numbered for simplified
identification. Units shall be UL listed 
and labeled, classified in accordance to
ANSI-Z21.47 for gas fired central furnaces
and UL 1995/CAN/CSA No. 236-M90 for
central cooling air conditioners. Canadian
units shall be CUL certified.

Casing

Unit casing shall be constructed of zinc
coated, heavy gauge, galvanized steel.
Exterior surfaces shall be cleaned, phos-
phatized, and finished with a weather-
resistant baked enamel finish. Unit’s sur-
face shall be tested 1000 hours in a salt
spray test in compliance with ASTM B117.
Cabinet construction shall allow for all
maintenance on one side of the unit. All
exposed vertical panels and top covers in
the indoor air section shall be insulated
with a cleanable foil faced, fire retardant
permanent, odorless glass fiber material
and secured with adhesive and mechani-
cal fasteners. The base of the unit shall be
insulated with foil-faced material. All insula-
tion edges shall be either captured or
sealed. The unit’s base pan shall have no
penetrations within the perimeter of the
curb other than the raised 1-1/8

[28.58

mm] high downflow supply return openings
to provide an added water integrity precau-
tion. The base rails of the unit shall have
provisions for forklift and crane lifting, with
forklift capabilities on three sides of 
the unit.

Unit Top

The indoor top cover shall be one-piece
construction, it shall not be double-
hemmed and gasket-sealed.

Filters

Two inch [50.8 mm], throwaway filters shall
be standard on all units.

Compressors

Units shall have direct-drive, hermetic,
scroll type compressors with centrifugal
type oil pumps. Motor shall be suction gas-
cooled and shall have a voltage utilization
range of plus or minus 10 percent of unit
nameplate voltage. Internal overloads shall
be provided with the scroll compressors.
The compressor shall have external isola-
tion to minimize noise. 

Refrigerant Circuits

Each refrigerant circuit shall have capillary
tubes expansion device. Service pressure
ports, shall be factory-installed as standard.

Evaporator And Condenser Coils

Internally finned, 3/8

[9.53 mm] copper

tubes mechanically bonded to a configured
aluminum plate fin shall be standard. Coils
shall be leak tested at the factory to ensure
pressure integrity. The evaporator coil and
condenser coil shall be leak tested to 200
psig and pressure tested to 450 psig. A
sloped condensate drain pan shall be
standard.

Gas Heating Section

The heating section shall have a tubular
heat exchanger design using Rheem exclu-
sive burners and corrosion resistant steel
throughout. An induced draft combustion
blower shall be used to pull the combustion
products through the firing tubes. The
heater shall use a direct spark ignition
(DSI) system and Remote Flame Sense.
On initial call for heat, the combustion
blower shall purge the heat exchanger for
30 seconds before ignition after two unsuc-
cessful ignition attempts on low fire and two
unsuccessful attempts on high fire, the
entire heating system shall be locked out
for one hour or until manually reset at the
thermostat/zone sensor. Units shall be
suitable for use with natural gas or propane
(field-installed kit).

Outdoor Fans

The outdoor fans shall be direct-drive 
statically and dynamically balanced, draw-
through in the vertical discharge position.
The fan motor shall be permanently 
lubricated and shall have built-in thermal
overload protection.

Indoor Fans

All 3-phase units offer belt drive, FC cen-
trifugal fans with adjustable motor sheaves.
All motors shall be thermally protected. All
indoor fan motors meet the U.S. Energy
Policy Act of 1992 (EPACT).

Controls

Unit shall be completely factory wired with
necessary controls and contactor pressure
lugs or terminal block for power wiring.
Units shall provide an external location 
for mounting a fused disconnect device. 

24-volt electromechanical control circuit
shall include control transformer and 
contactor pressure lugs for power wiring.
Unit shall have single point power entry 
as standard.

Accessories/Option

Roof Curb—

The roof curb shall be

designed to mate with the unit’s downflow
supply and return openings and provide
support and a watertight installation when
installed properly. The roof curb design
shall allow field-fabricated rectangular
supply/return ductwork to be connected
directly to the curb. Curb design shall 
comply with NRCA requirements. Curbs
shall be shipped knocked down for toolless
field assembly and shall include wood
nailer strips.

Economizer—

This accessory shall be

either field or factory-installed and is avail-
able with barometric relief standard. The
assembly includes direct drive gear driver,
fully modulating 0-100 percent motor and
dampers, minimum position setting, mixed
air sensor, wiring harness with plug, and
single enthalpy control. Optional differential
enthalpy control shall be field-installed.
The factory-installed economizer arrives
ready for operation.

Remote Potentiometer—

Field installed,

the minimum position setting of economizer
shall be adjusted with this accessory.

Motorized Outside Air Dampers—

Field-installed manually set outdoor air
dampers shall provide up to 50 percent
outside air. Once set, outdoor air dampers
shall open to set position when indoor fan
starts. The damper shall close to the full
closed position when indoor fan shuts
down.

Manual Outside Air Damper—

Factory or

field-installed rain hood and screen shall
provide up to 50 percent outside air.

Oversized Motors—

Factory installed belt

drive oversized motors shall be available for
high static applications.

Summary of Contents for RKKB SERIES

Page 1: ...NAL SIZES 15 25 TONS 52 8 87 9 kW ASHRAE 90 1 1989 COMPLIANT MODELS RKMB HIGH EFFICIENCY SERIES NOMINAL SIZES 15 20 TONS 52 8 70 3 kW ASHRAE 90 1 1999 COMPLIANT MODELS RKNB SUPER HIGH EFFICIENCY SERIE...

Page 2: ...Series 25 27 General Data Notes 28 Performance Data RKKB Series 29 30 RKMB Series 31 RKNB Series 32 Airflow Performance RKKB Series 33 34 RKMB Series 33 34 RKNB Series 33 Electrical Data RKKB Series...

Page 3: ...e growth of harmful bacteria All insulation is secured with both adhesive and mechanical fasten ers and all edges are hidden During development each unit was tested to U L 1995 ANSI 21 47 ARI 340 370...

Page 4: ...connection and low pressure connection With the gauge ports mounted externally an accurate diagnostic of system operation can be performed quickly and easily The blower compartment is to the right of...

Page 5: ...nsulation behind sheet metal to improve indoor air quality The furnace compartment contains the latest furnace technology on the market The draft inducers draw the flame from the Rheem exclusive in sh...

Page 6: ...al applications for job config uration flexibility The return air compartment can also contain an economizer Two models exits one for downflow applications and one for horizontal applications Each uni...

Page 7: ...700 x 995 231 540 BTUH 67 86 kW Sensible Capacity 172 500 x 987 170 260 BTUH 49 90 kW Power Input 21 600 x 999 21 578 Watts These are Gross Capacities not corrected for blower motor heat or power 4 D...

Page 8: ...on C 208 230 V 3 PH 60 Hz D 460 V 3 PH 60 Hz Y 575 V 3 PH 60 Hz Cooling Capacity BTUH kW 180 180 000 52 75 240 240 000 70 34 300 300 000 87 92 Future Technical Variations Design Series B B Series Cabi...

Page 9: ...o factory installed economizer RKKB A240CL40ECLA Example Options same as above with factory installed economizer RKKB A240CL40ECLB No Economizer Single Enthalpy Economizer With Barometric Relief A x B...

Page 10: ...Capacity Btu kW 46 000 13 5 46 000 13 5 46 000 13 5 46 000 13 5 Indoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Type Rifled Rifled Rifled Rifled Tube Size in mm 0 375 9 5 0 375 9 5 0 375...

Page 11: ...1 22 9 1 22 9 Net Latent Capacity Btu kW 46 000 13 5 46 000 13 5 46 000 13 5 46 000 13 5 Indoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Type Rifled Rifled Rifled Rifled Tube Size in mm...

Page 12: ...9 1 22 9 1 22 9 Net Latent Capacity Btu kW 46 000 13 5 46 000 13 5 46 000 13 5 46 000 13 5 Indoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Type Rifled Rifled Rifled Rifled Tube Size in...

Page 13: ...22 9 1 22 9 1 22 9 Net Latent Capacity Btu kW 64 000 18 8 64 000 18 8 64 000 18 8 64 000 18 8 Indoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Type Rifled Rifled Rifled Rifled Tube Size...

Page 14: ...22 9 1 22 9 1 22 9 Net Latent Capacity Btu kW 64 000 18 8 64 000 18 8 64 000 18 8 64 000 18 8 Indoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Type Rifled Rifled Rifled Rifled Tube Size...

Page 15: ...22 9 1 22 9 1 22 9 Net Latent Capacity Btu kW 64 000 18 8 64 000 18 8 64 000 18 8 64 000 18 8 Indoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Type Rifled Rifled Rifled Rifled Tube Size...

Page 16: ...9 2 22 9 Net Latent Capacity Btu kW 88 000 25 8 88 000 25 8 88 000 25 8 88 000 25 8 Indoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Type Rifled Rifled Rifled Rifled Tube Size in mm 0 37...

Page 17: ...9 2 22 9 Net Latent Capacity Btu kW 88 000 25 8 88 000 25 8 88 000 25 8 88 000 25 8 Indoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Type Rifled Rifled Rifled Rifled Tube Size in mm 0 37...

Page 18: ...2 22 9 2 22 9 Net Latent Capacity Btu kW 88 000 25 8 88 000 25 8 88 000 25 8 88 000 25 8 Indoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Type Rifled Rifled Rifled Rifled Tube Size in mm...

Page 19: ...Face Area sq ft sq m 36 3 34 36 3 34 36 3 34 36 3 34 Rows FPI FPcm 1 22 9 1 22 9 1 22 9 1 22 9 Net Latent Capacity Btu kW 46 000 13 5 46 000 13 5 46 000 13 5 46 000 13 5 Indoor Coil Fin Type Louvered...

Page 20: ...t sq m 36 3 34 36 3 34 36 3 34 36 3 34 Rows FPI FPcm 1 22 9 1 22 9 1 22 9 1 22 9 Net Latent Capacity Btu kW 46 000 13 5 46 000 13 5 46 000 13 5 46 000 13 5 Indoor Coil Fin Type Louvered Louvered Louve...

Page 21: ...1 22 9 1 22 9 1 22 9 1 22 9 Net Latent Capacity Btu kW 46 000 13 5 46 000 13 5 46 000 13 5 46 000 13 5 Indoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Type Rifled Rifled Rifled Rifled T...

Page 22: ...3 34 36 3 34 36 3 34 Rows FPI FPcm 2 22 9 2 22 9 2 22 9 2 22 9 Net Latent Capacity Btu kW 64 000 18 8 64 000 18 8 64 000 18 8 64 000 18 8 Indoor Coil Fin Type Louvered Louvered Louvered Louvered Tube...

Page 23: ...34 36 3 34 36 3 34 Rows FPI FPcm 2 22 9 2 22 9 2 22 9 2 22 9 Net Latent Capacity Btu kW 64 000 18 8 64 000 18 8 64 000 18 8 64 000 18 8 Indoor Coil Fin Type Louvered Louvered Louvered Louvered Tube T...

Page 24: ...36 3 34 36 3 34 36 3 34 Rows FPI FPcm 2 22 9 2 22 9 2 22 9 2 22 9 Net Latent Capacity Btu kW 64 000 18 8 64 000 18 8 64 000 18 8 64 000 18 8 Indoor Coil Fin Type Louvered Louvered Louvered Louvered T...

Page 25: ...e in mm OD 0 375 9 5 0 375 9 5 0 375 9 5 0 375 9 5 Face Area sq ft sq m 36 3 34 36 3 34 36 3 34 36 3 34 Rows FPI FPcm 2 22 9 2 22 9 2 22 9 2 22 9 Net Latent Capacity Btu kW 47 000 13 8 47 000 13 8 47...

Page 26: ...Face Area sq ft sq m 36 3 34 36 3 34 36 3 34 36 3 34 Rows FPI FPcm 2 22 9 2 22 9 2 22 9 2 22 9 Net Latent Capacity Btu kW 47 000 13 8 47 000 13 8 47 000 13 8 47 000 13 8 Indoor Coil Fin Type Louvered...

Page 27: ...e in mm OD 0 375 9 5 0 375 9 5 0 375 9 5 0 375 9 5 Face Area sq ft sq m 36 3 34 36 3 34 36 3 34 36 3 34 Rows FPI FPcm 2 22 9 2 22 9 2 22 9 2 22 9 Net Latent Capacity Btu kW 47 000 13 8 47 000 13 8 47...

Page 28: ...and in accordance with DOE test procedures 3 Integrated Part Load Value is rated in accordance with ARI Standard 210 240 or 360 Units are rated at 80 F ambient 80 F entering dry bulb and 67 F entering...

Page 29: ...wbE Entering air wet bulb Total Total capacity x 1000 BTUH Sens Sensible capacity x 1000 BTUH Power KW input NOTES When the entering air dry bulb is other than 80 F 27 C adjust the sensible capacity f...

Page 30: ...50 97 26 9 298 0 87 34 154 2 45 19 26 5 306 9 89 94 225 1 65 97 26 9 299 3 87 72 211 3 61 93 26 6 288 4 84 52 191 6 56 15 26 2 296 3 86 84 264 1 77 40 26 4 288 7 84 61 250 3 73 36 26 1 277 8 81 42 230...

Page 31: ...1 7 C 67 F 19 4 C 63 F 17 2 C CFM L s 8880 4191 7400 3492 5920 2794 8880 4191 7400 3492 5920 2794 8880 4191 7400 3492 5920 2794 DR 15 12 08 15 12 08 15 12 08 O U T D O O R D R Y B U L B T E M P E R A...

Page 32: ...34 08 15 2 189 4 55 51 105 5 30 92 14 9 195 6 57 32 156 0 45 72 15 3 188 7 55 30 142 7 41 82 15 1 181 9 53 31 129 4 37 92 14 8 187 7 55 01 183 5 53 78 15 3 181 2 53 10 167 9 49 21 15 0 174 6 51 17 15...

Page 33: ...W RPM W 924 2307 937 2486 950 2665 933 2612 946 2791 959 2970 942 2917 955 3097 968 3276 951 3223 964 3402 977 3581 960 3528 973 3707 986 3886 969 3833 982 4012 995 4192 978 4139 991 4318 1004 4497 Ca...

Page 34: ...Air Flow CFM L s 1098 7424 RPM W RPM W 1035 5287 1048 5466 1044 5592 1057 5771 1053 5897 1066 6076 1062 6203 1075 6382 1071 6508 1084 6687 1080 6813 1093 6992 1089 7119 1102 7298 0 1 02 0 2 05 0 3 07...

Page 35: ...208 230 3 5 14 7 82 6 A240CM30E 187 253 109 109 125 125 125 125 1 208 230 3 7 5 22 3 136 A240CM40E 187 253 109 109 125 125 125 125 1 208 230 3 7 5 22 3 136 A240DL30E 414 506 58 60 60 1 460 3 5 10 41 3...

Page 36: ...M40E 4 200 230 3 4 3 4 3450 17 8 17 8 124 124 4 208 230 1 1 3 2 4 4 7 A240DL30E 4 460 3 4 3 4 3450 9 3 59 6 4 460 1 1 3 2 2 4 A240DL40E 4 460 3 4 3 4 3450 9 3 59 6 4 460 1 1 3 2 2 4 A240DM30E 4 460 3...

Page 37: ...35E 414 506 46 50 50 1 460 3 5 10 41 3 A180YL25E 518 633 34 35 35 1 575 3 3 8 20 A180YL35E 518 633 34 35 35 1 575 3 3 8 20 A180YM25E 518 633 34 35 35 1 575 3 5 8 33 A180YM35E 518 633 34 35 35 1 575 3...

Page 38: ...4 575 1 1 3 1 1 5 A180YM25E 4 575 3 3 1 2 3450 5 34 4 575 1 1 3 1 1 5 A180YM35E 4 575 3 3 1 2 3450 5 34 4 575 1 1 3 1 1 5 A240CL30E 4 200 240 3 4 3 4 3450 17 5 17 5 123 123 4 208 230 1 1 3 2 4 4 7 A24...

Page 39: ...35E 187 253 72 72 80 80 90 90 1 208 230 3 3 11 5 74 5 A180CM25E 187 253 75 75 80 80 90 90 1 208 230 3 5 14 7 82 6 A180CM35E 187 253 75 75 80 80 90 90 1 208 230 3 5 14 7 82 6 A180DL25E 414 506 42 45 50...

Page 40: ...6 3 4 3450 22 4 22 4 164 164 4 208 230 1 1 3 2 4 4 7 A180DL25E 2 460 3 6 3 4 3450 11 8 100 4 460 1 1 3 2 2 4 A180DL35E 2 460 3 6 3 4 3450 11 8 100 4 460 1 1 3 2 2 4 A180DM25E 2 460 3 6 3 4 3450 11 8...

Page 41: ...41 UNIT DIMENSIONS RKKB RKMB RKNB SERIES BOTTOM VIEW Illustration ST A0886 02 GAS HEAT ELECTRIC COOLING PACKAGE Illustration ST A0886 06 Designates Metric Conversions...

Page 42: ...40 1016 mm 23 584 2 mm 43 16 106 4 mm 54 1371 6 mm THRU THE BASE GAS THRU THE BASE ELECTRIC 3 76 2 mm TYP SUPPLY AIR R E T U R N A I R 1415 16 3589 3 mm 23 8 60 3 mm TYP ST A0886 07 01 SUPPLY AND RETU...

Page 43: ...er Weights by Percentage WEIGHTS Accessory Shipping lbs kg Economizer Downflow 155 70 31 Fresh Air Damper Manual 51 23 13 40 18 14 146 66 22 Operating lbs kg Fresh Air Damper Motorized 46 20 87 Roof C...

Page 44: ...are recommended for proper unit performance and serviceability Illustration ST A0886 09 Illustration ST A0886 08 Recommended Clearance In mm Location 48 1219 A Front 18 457 B Condenser Coil 18 457 C...

Page 45: ...x 36 RXRN AD80 213 96 6 115 52 2 No Concentric Diffuser Flush 24 x 48 RXRN AD85 270 122 4 175 79 4 No Downflow Transition Rect to Rect 18 x 36 RXMC CG07 81 36 7 65 29 5 No Compressor Time Delay Relay...

Page 46: ...s Slip In Design for Easy Installation Plug In Polarized 12 pin Electrical Connections Pre Configured No Field Adjustments Necessary Standard Barometric Relief Damper Single Enthalpy with Dual Enthalp...

Page 47: ...lip In Design for Easy Installation Plug In Polarized 12 pin Electrical Connections Pre Configured No Field Adjustments Necessary Standard Barometric Relief Damper Single Enthalpy with Dual Enthalpy U...

Page 48: ...olts Phase HP ea Low Speed RXRX BFF02C 2 208 230 1 0 33 2200 1038 1518 2500 1179 High Speed 1670 1 48 FLA ea 3 6 LRA ea RXRX BFF02D 2 460 1 0 33 2200 1038 1518 2500 1179 1670 0 75 1 8 RXRX BFF02Y 2 57...

Page 49: ...ration ST 7951 17 Designates Metric Conversions RXRF HEA1 Manual RXRX ATO1 Motorized damper kit for manual fresh air damper Illustration ST A0889 02 FRESH AIR DAMPER MOTORIZED DAMPER KIT RXRX ATO1 Mot...

Page 50: ...orners for simple and fast assembly 1 25 4 mm x 4 102 mm Nailer provided Insulating panels not required because of insulated outdoor base pan Sealing gasket 28 711 mm provided with Roofcurb Packaged f...

Page 51: ...EW MODEL KKB KMB KNB 15 20 25 TON 52 8 70 3 87 9 kW OLD MODELS OLD CURB MODEL ROOFCURB ADAPTER COMMERCIAL CABINET 12 5 15 20 TON 44 52 8 70 3 kW RCF RGF REF RXRK E56 RXRX CHCE56 Illustration ADS 7952...

Page 52: ...ER APPLICATION Illustration ST A0840 02 DOWNFLOWTRANSITION DRAWINGS RXMC CG07 15 Ton 52 8 kW Used with RXRN AD80 and RXRN AD81 Concentric Diffusers Illustration ADS 7951 10 Designates Metric Conversio...

Page 53: ...DOWNFLOWTRANSITION DRAWINGS Cont RXMC CH08 20 25 Ton 70 3 87 9 kW Used with RXRN AD85 and RXRN AD86 Concentric Diffusers Illustration ADS 7951 11 Designates Metric Conversions 53 ACCESSORIES...

Page 54: ...ing supports Diffuser box constructed of sheetmetal insulated with 1 25 4 mm 1 5 lbs 7 kg duct liner PART NUMBER CFM L s STATIC PRESSURE THROW FEET 5800 2737 0 39 29 38 6000 2832 0 42 40 50 RXRN AD80...

Page 55: ...tructed of sheetmetal insulated with 1 25 4 mm 1 5 lbs 7 kg duct liner Double deflection diffuser with the blades secured by spring steel PART NUMBER CFM L s STATIC PRESSURE THROW FEET 1022 954 920 NE...

Page 56: ...heetmetal insulated with 1 25 4 mm 1 5 lbs 7 kg duct liner PART NUMBER CFM L s STATIC PRESSURE THROW FEET 1051 1024 996 NECK VELOCITY 2209 2151 2093 JET VELOCITY 7800 3681 0 47 40 50 1079 2276 8000 37...

Page 57: ...1 25 4 mm 1 5 lbs 7 kg duct liner Double deflection diffuser with the blades secured by spring steel PART NUMBER CFM L s STATIC PRESSURE THROW FEET 873 850 827 NECK VELOCITY 873 850 827 JET VELOCITY...

Page 58: ...ng section shall have a tubular heat exchanger design using Rheem exclu sive burners and corrosion resistant steel throughout An induced draft combustion blower shall be used to pull the combustion pr...

Page 59: ...connect or circuit breaker This option can only be ordered with the Disconnect Switch Through the Base Gas Piping The unit shall include a standard through the base gas provision Freeze Clogged Filter...

Page 60: ...60 WIRING SCHEMATICS RKKB RKMB SERIES...

Page 61: ...61 WIRING SCHEMATICS RKKB RKMB SERIES...

Page 62: ...62 WIRING SCHEMATICS RKKB RKMB SERIES...

Page 63: ...63 WIRING SCHEMATICS RKNB SERIES...

Page 64: ...64 WIRING SCHEMATICS RKNB SERIES...

Page 65: ...65 WIRING SCHEMATICS RKNB SERIES...

Page 66: ...66 NOTES...

Page 67: ...67 NOTES...

Page 68: ...Factory Option Stainless Steel Heat Exchanger Three Phase models installed in a commercial application Twenty 20 Years Single Phase models installed in a residential application Limited Lifetime For...

Reviews: