39
ELECTRICAL DATA—RKNB- SERIES
Unit Operating
Voltage Range
Model No.
RKNB-
Minimum Circuit
Ampacity
Minimum Overcurrent
Protection Device Size
Maximum Overcurrent
Protection Device Size
No.
Volts
Phase
HP
Amps
(FLA)
Amps
(LRA)
Unit Information
Evaporator Fan
A180CL25E
187-253
72/72
80/80
90/90
1
208/230
3
3
11.5
74.5
A180CL35E
187-253
72/72
80/80
90/90
1
208/230
3
3
11.5
74.5
A180CM25E
187-253
75/75
80/80
90/90
1
208/230
3
5
14.7
82.6
A180CM35E
187-253
75/75
80/80
90/90
1
208/230
3
5
14.7
82.6
A180DL25E
414-506
42
45
50
1
460
3
3
7
38.1
A180DL35E
414-506
42
45
50
1
460
3
3
7
38.1
A180DM25E
414-506
45
45
50
1
460
3
5
10
41.3
A180DM35E
414-506
45
45
50
1
460
3
5
10
41.3
A180YL25E
518-632
35
35
45
1
575
3
3
8
20
A180YL35E
518-632
35
35
45
1
575
3
3
8
20
A180YM25E
518-632
35
35
45
1
575
3
5
8
33
A180YM35E
518-632
35
35
45
1
575
3
5
8
33
Summary of Contents for RKKB SERIES
Page 60: ...60 WIRING SCHEMATICS RKKB RKMB SERIES...
Page 61: ...61 WIRING SCHEMATICS RKKB RKMB SERIES...
Page 62: ...62 WIRING SCHEMATICS RKKB RKMB SERIES...
Page 63: ...63 WIRING SCHEMATICS RKNB SERIES...
Page 64: ...64 WIRING SCHEMATICS RKNB SERIES...
Page 65: ...65 WIRING SCHEMATICS RKNB SERIES...
Page 66: ...66 NOTES...
Page 67: ...67 NOTES...