51

DIAGNOSTIC CODES

SENSOR TEMPERATURE VS. RESISTANCE 

TABLE

REPLACEMENT PARTS

Contact your local distributor for a complete parts list.

CHARGE INFORMATION

Refer to the appropriate charge chart on the unit, or in this booklet.

TROUBLESHOOTING

Refer to the troubleshooting chart included in this manual.

WIRING DIAGRAMS

Refer to the appropriate wiring diagram included in this manual.

LED 1 

LED 2 

Control Board Status

OFF 

OFF 

No Power

ON 

ON 

Coil Sensor Failure

OFF 

ON 

Ambient Sensor Failure

FLASH FLASH  Normal

OFF 

FLASH 

Low Pressure Lockout (short test pins to reset)

FLASH 

OFF 

High Pressure Lockout (short test pins to reset)

ON  

FLASH 

Low Pressure Control Open

FLASH 

ON 

High Pressure Control Open

          Alternate Flashing 

5 Minute Time Delay

 

Degrees C 

Degrees F 

Ohms

 -20 

-4 

96,974

 -10 

14 

55,298

 0 

32 

32,650

 10 

50 

19,903

 20 

68 

12,493

 25 

77 

10,000

 

30 

86 

 8,056

 

40 

104 

 5,324

Summary of Contents for RHPD Series

Page 1: ...ON OF THIS UNIT READ THESE INSTRUCTIONS THOROUGHLY BEFORE ATTEMPTING INSTALLATION OR OPERATION FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION ADJUSTMENT SERVICE OR MAINTENANC...

Page 2: ...9 VII Ductwork 40 VIII Filters 40 IX Conversion Procedure 40 X Condensate Drain 40 XI Condensate Drain Outdoor Coil 41 XII Electrical Wiring 41 A Power Wiring 41 RXJJ Series Heater Kit Installation In...

Page 3: ...ONAL INJURY OR DEATH WARNING THE UNIT MUST BE PERMANENTLY GROUNDED A GROUNDING LUG IS PROVIDED IN THE ELECTRIC HEAT ACCESS AREA FOR A GROUND WIRE FAILURE TO GROUND THIS UNIT CAN RESULT IN FIRE OR ELEC...

Page 4: ...nting outside of the building The information on the rating plate is in compliance with the FTC and DOE rating for single phase units The following infor mation is for three phase units which are not...

Page 5: ...ostatic Expansion Valve TXV The Bi Flow TXV is specifically designed to operate with R 410A heat pumps Replacement of the TXV should only be made with the factory specified bi flow R 410A valve Do not...

Page 6: ...090 THRU 102 MODELS 50 1270 mm RETURN COVER SUPPLY COVER DRAIN PAN SERVICE DISCONNECT KNOCKOUT FIGURE 2 UNIT DIMENSIONS ST A1273 01_D 00 SERVICE PORT DOOR POWER ENTRY RECEPTACLE 29 1 4 743 mm 32 3 4...

Page 7: ...7 mm FIGURE 4 REAR VIEW 55 3 8 1407 mm 59 1 2 1511 mm 14 356 mm 26 3 4 679 mm 59 1 8 1507 mm 6 1 2 165 mm 6 5 8 321 mm 5 1 2 140 mm 28 1 2 724 mm 6 3 8 162 mm 36 3 8 924 mm 86 3 4 2203 mm 90 1 8 2289...

Page 8: ...No Type 1 Scroll 1 Scroll 1 Scroll 1 Scroll Outdoor Sound Rating dB 5 88 88 88 88 Outdoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Type MicroChannel MicroChannel MicroChannel MicroChann...

Page 9: ...No Type 1 Scroll 1 Scroll 1 Scroll 1 Scroll Outdoor Sound Rating dB 5 88 88 88 88 Outdoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Type MicroChannel MicroChannel MicroChannel MicroChann...

Page 10: ...r No Type 1 Scroll 1 Scroll 1 Scroll 1 Scroll Outdoor Sound Rating dB 5 88 88 88 88 Outdoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Type MicroChannel MicroChannel MicroChannel MicroChan...

Page 11: ...r No Type 1 Scroll 1 Scroll 1 Scroll 1 Scroll Outdoor Sound Rating dB 5 88 88 88 88 Outdoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Type MicroChannel MicroChannel MicroChannel MicroChan...

Page 12: ...sor No Type 1 Scroll 1 Scroll 1 Scroll 1 Scroll Outdoor Sound Rating dB 5 88 88 88 88 Outdoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Type MicroChannel MicroChannel MicroChannel MicroCh...

Page 13: ...essor No Type 1 Scroll 1 Scroll 1 Scroll 1 Scroll Outdoor Sound Rating dB 5 88 88 88 88 Outdoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Type MicroChannel MicroChannel MicroChannel Micro...

Page 14: ...essor No Type 1 Scroll 1 Scroll 1 Scroll 1 Scroll Outdoor Sound Rating dB 5 88 88 88 88 Outdoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Type MicroChannel MicroChannel MicroChannel Micro...

Page 15: ...essor No Type 1 Scroll 1 Scroll 1 Scroll 1 Scroll Outdoor Sound Rating dB 5 88 88 88 88 Outdoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Type MicroChannel MicroChannel MicroChannel Micro...

Page 16: ...essor No Type 1 Scroll 1 Scroll 1 Scroll 1 Scroll Outdoor Sound Rating dB 5 88 88 88 88 Outdoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Type MicroChannel MicroChannel MicroChannel Micro...

Page 17: ...essor No Type 1 Scroll 1 Scroll 1 Scroll 1 Scroll Outdoor Sound Rating dB 5 88 88 88 88 Outdoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Type MicroChannel MicroChannel MicroChannel Micro...

Page 18: ...essor No Type 1 Scroll 1 Scroll 1 Scroll 1 Scroll Outdoor Sound Rating dB 5 88 88 88 88 Outdoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Type MicroChannel MicroChannel MicroChannel Micro...

Page 19: ...ssor No Type 1 Scroll 1 Scroll 1 Scroll 1 Scroll Outdoor Sound Rating dB 5 88 88 88 88 Outdoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Type MicroChannel MicroChannel MicroChannel MicroC...

Page 20: ...essor No Type 1 Scroll 1 Scroll 1 Scroll 1 Scroll Outdoor Sound Rating dB 5 88 88 88 88 Outdoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Type MicroChannel MicroChannel MicroChannel Micro...

Page 21: ...High Temp Btuh kW Rating 112 000 32 82 112 000 32 82 System Power KW COP 9 03 3 3 9 03 3 3 Low Temp Btuh kW Rating 68 000 19 92 68 000 19 92 System Power KW COP 8 3 2 26 8 3 2 26 Compressor No Type 1...

Page 22: ...essor No Type 1 Scroll 1 Scroll 1 Scroll 1 Scroll Outdoor Sound Rating dB 5 88 88 88 88 Outdoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Type MicroChannel MicroChannel MicroChannel Micro...

Page 23: ...essor No Type 1 Scroll 1 Scroll 1 Scroll 1 Scroll Outdoor Sound Rating dB 5 88 88 88 88 Outdoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Type MicroChannel MicroChannel MicroChannel Micro...

Page 24: ...mpressor No Type 1 Scroll 1 Scroll 1 Scroll 1 Scroll Outdoor Sound Rating dB 5 88 88 88 88 Outdoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Type MicroChannel MicroChannel MicroChannel Mi...

Page 25: ...ompressor No Type 1 Scroll 1 Scroll 1 Scroll 1 Scroll Outdoor Sound Rating dB 5 88 88 88 88 Outdoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Type MicroChannel MicroChannel MicroChannel M...

Page 26: ...ompressor No Type 1 Scroll 1 Scroll 1 Scroll 1 Scroll Outdoor Sound Rating dB 5 88 88 88 88 Outdoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Type MicroChannel MicroChannel MicroChannel M...

Page 27: ...ompressor No Type 1 Scroll 1 Scroll 1 Scroll 1 Scroll Outdoor Sound Rating dB 5 88 88 88 88 Outdoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Type MicroChannel MicroChannel MicroChannel M...

Page 28: ...8 000 19 92 68 000 19 92 68 000 19 92 System Power KW COP 8 3 2 26 8 3 2 26 8 3 2 26 Compressor No Type 1 Scroll 1 Scroll 1 Scroll Outdoor Sound Rating dB 5 88 88 88 Outdoor Coil Fin Type Louvered Lou...

Page 29: ...0 230 460 460 460 Phase 3 3 3 3 3 3 3 3 3 RPM 3450 3450 3450 3450 3450 3450 3450 3450 3450 HP Compressor 1 7 7 7 7 7 7 7 7 7 Amps RLA Comp 1 25 3 25 3 25 3 25 3 25 3 25 3 9 6 9 6 9 6 Amps LRA Comp 1 1...

Page 30: ...460 575 575 575 575 575 575 Phase 3 3 3 3 3 3 3 3 3 RPM 3450 3450 3450 3450 3450 3450 3450 3450 3450 HP Compressor 1 7 7 7 7 7 7 7 7 7 Amps RLA Comp 1 9 6 9 6 9 6 7 1 7 1 7 1 7 1 7 1 7 1 Amps LRA Comp...

Page 31: ...Phase 3 3 3 3 3 3 3 3 3 RPM 3450 3450 3450 3450 3450 3450 3450 3450 3450 HP Compressor 1 7 1 2 7 1 2 7 1 2 7 1 2 7 1 2 7 1 2 7 1 2 7 1 2 7 1 2 Amps RLA Comp 1 28 8 28 8 28 8 28 8 28 8 28 8 12 5 12 5...

Page 32: ...575 575 Phase 3 3 3 3 3 3 3 3 3 RPM 3450 3450 3450 3450 3450 3450 3450 3450 3450 HP Compressor 1 7 1 2 7 1 2 7 1 2 7 1 2 7 1 2 7 1 2 7 1 2 7 1 2 7 1 2 Amps RLA Comp 1 12 5 12 5 12 5 9 7 9 7 9 7 9 7 9...

Page 33: ...460 460 460 Phase 3 3 3 3 3 3 3 3 3 RPM 3450 3450 3450 3450 3450 3450 3450 3450 3450 HP Compressor 1 10 10 10 10 10 10 10 10 10 Amps RLA Comp 1 32 6 32 6 32 6 32 6 32 6 32 6 14 8 14 8 14 8 Amps LRA Co...

Page 34: ...575 575 575 Phase 3 3 3 3 3 3 3 3 3 RPM 3450 3450 3450 3450 3450 3450 3450 3450 3450 HP Compressor 1 10 10 10 10 10 10 10 10 10 Amps RLA Comp 1 14 8 14 8 14 8 11 1 11 1 11 1 11 1 11 1 11 1 Amps LRA C...

Page 35: ...60 460 460 575 575 575 Phase 3 3 3 3 3 3 3 3 3 RPM 3450 3450 3450 3450 3450 3450 3450 3450 3450 HP Compressor 1 7 7 7 7 7 7 7 7 7 Amps RLA Comp 1 25 3 25 3 25 3 9 6 9 6 9 6 7 1 7 1 7 1 Amps LRA Comp 1...

Page 36: ...575 Phase 3 3 3 3 3 3 3 3 3 RPM 3450 3450 3450 3450 3450 3450 3450 3450 3450 HP Compressor 1 7 1 2 7 1 2 7 1 2 7 1 2 7 1 2 7 1 2 7 1 2 7 1 2 7 1 2 Amps RLA Comp 1 28 8 28 8 28 8 12 5 12 5 12 5 9 7 9...

Page 37: ...575 575 575 Phase 3 3 3 3 3 3 3 3 3 RPM 3450 3450 3450 3450 3450 3450 3450 3450 3450 HP Compressor 1 10 10 10 10 10 10 10 10 10 Amps RLA Comp 1 32 6 32 6 32 6 14 8 14 8 14 8 11 1 11 1 11 1 Amps LRA Co...

Page 38: ...will not disturb owner or neighbors 5 Locate unit so roof runoff water does not pour directly on the unit Provide gutter or other shielding at roof level Do not locate unit in an area where excessive...

Page 39: ...must be pro vided 5 The unit should be placed on a solid and level roofcurb or platform of adequate strength See Figure 8 6 The location of the unit on the roof should be such as to provide proper acc...

Page 40: ...ors and clearance to combustible mate rial of 0 for the first 3 feet 0 91 m of discharge duct Clearance to unit top and side is 0 VIII FILTERS This unit is provided with 4 2 20 20 51 mm 508 mm 508 mm...

Page 41: ...The outdoor coil during heating operation will sweat or run water off The outdoor coil will also run water off during the defrost cycle See Section VI Installation Page 48 for mounting precau tions X...

Page 42: ...42 Zy...

Page 43: ...43...

Page 44: ...44...

Page 45: ...45 FIGURE 12 FIGURE 13...

Page 46: ...46 FIGURE 14 FIGURE 15 FIGURE 16...

Page 47: ...520 0 1 5 8 7 03 7 5 520 21 7 50267 7 21 8 7 520 32 5 6833 6 3 5 57 675 7 21 8 7 77 1 6 3 5 57 21 8 7 520 21 7 50267 7 675 7 21 8 7 77 1 32 5 175 87 2 6 3 5 57 21752 92 7 87 2 3 5 57 21 8 7 187 FIGUR...

Page 48: ...FLOW DATA Belt drive blower models have motor sheaves set for proper CFM at a typical external static See Airflow Data Tables to determine if adjustments are necessary TABLE 1 COPPER WIRE SIZE AWG 1...

Page 49: ...n the cool mode fan auto and the room tem perature higher than the thermostat setting A Indoor blower contactor is energized through thermostat contact G B Compressor contactor is energized through th...

Page 50: ...ing mode TROUBLESHOOTING DEMAND DEFROST During the test mode the coil temperature should be moni tored If the system exits defrost at approximately the termina tion temperature the control is operatin...

Page 51: ...appropriate wiring diagram included in this manual LED 1 LED 2 Control Board Status OFF OFF No Power ON ON Coil Sensor Failure OFF ON Ambient Sensor Failure FLASH FLASH Normal OFF FLASH Low Pressure...

Page 52: ...RZHU 6KHDYH 0RWRU 6KHDYH 9 93 93 HOW 7XUQV 2SHQ 530 127 6 DFWRU VKHDYH VHWWLQJV DUH VKRZQ LQ EROG W SH 6HQVLEOH 0 3RZHU N 7RWDO 0 5HVLVWDQFH QFKHV RI DWHU N3D R QRW VHW PRWRU VKHDYH EHORZ PLQLPXP RU P...

Page 53: ...DYH 9 93 93 HOW 7XUQV 2SHQ 530 127 6 DFWRU VKHDYH VHWWLQJV DUH VKRZQ LQ EROG W SH LUIORZ 5 2 255 7 21 7256 7RWDO 0 6HQVLEOH 0 3RZHU N 5 2 3 5 250 1 5 3 20321 17 5 2 5 6 67 1 HW RLO RUL RQWDO FRQRPL HU...

Page 54: ...IXVHU 5 51 RQFHQWULF GDSWHU 5 0 OXVK RQFHQWULF LIIXVHU 5 51 RQFHQWULF GDSWHU 5 0 URS 6HQVLEOH 0 3RZHU N 7RWDO 0 5HVLVWDQFH QFKHV RI DWHU N3D R QRW VHW PRWRU VKHDYH EHORZ PLQLPXP RU PD LPXP WXUQV RSHQ...

Page 55: ...VHU 5 51 RQFHQWULF GDSWHU 5 0 OXVK RQFHQWULF LIIXVHU 5 51 RQFHQWULF GDSWHU 5 0 URS 6HQVLEOH 0 3RZHU N 5HVLVWDQFH QFKHV RI DWHU N3D 7RWDO 0 R QRW VHW PRWRU VKHDYH EHORZ PLQLPXP RU PD LPXP WXUQV RSHQ VK...

Page 56: ...HU 5 DPSHU 2SHQ RQFHQWULF LIIXVHU 5 51 LIIXVHU 5 0 OXVK RQFHQWULF LIIXVHU 5 51 LIIXVHU 5 0 URS 5HVLVWDQFH QFKHV RI DWHU N3D 7RWDO 0 R QRW VHW PRWRU VKHDYH EHORZ PLQLPXP RU PD LPXP WXUQV RSHQ VKRZQ 5H...

Page 57: ...WRU 3 ORZHU 6KHDYH 0RWRU 6KHDYH 9 93 93 HOW 7XUQV 2SHQ 530 127 6 DFWRU VKHDYH VHWWLQJV DUH VKRZQ LQ EROG W SH 5 2 3 5 250 1 5 3 5 2 255 7 21 7256 LUIORZ HW RLO RUL RQWDO FRQRPL HU 5 DPSHU 2SHQ RQFHQWU...

Page 58: ...9 25 25 33 77 20 6 23 8 72 76 80 90 80 90 26 30 30 30 46 46 60 70 60 70 DD15CP 1 10 8 14 4 36 84 49 13 30 0 34 6 84 89 90 100 100 100 38 44 40 45 46 46 60 70 60 70 DD20CP 2 14 9 19 8 50 83 67 55 41 3...

Page 59: ...36 84 49 13 30 0 34 6 86 91 90 100 100 110 38 44 40 45 48 48 60 70 60 70 DD20CP 2 14 9 19 8 50 83 67 55 41 3 47 6 100 108 110 110 110 110 52 60 60 60 48 48 60 70 60 70 DD30CP 2 21 6 28 8 73 69 98 25...

Page 60: ...8 14 4 36 84 49 13 30 0 34 6 94 100 100 110 110 110 38 44 40 45 57 57 70 80 70 80 DD20CP 2 14 9 19 8 50 83 67 55 41 3 47 6 108 116 125 125 125 125 52 60 60 60 57 57 70 80 70 80 DD30CP 2 21 6 28 8 73 6...

Page 61: ...84 49 13 30 0 34 6 91 96 100 110 100 110 38 44 40 45 53 53 60 80 60 80 DD20CP 2 14 9 19 8 50 83 67 55 41 3 47 6 105 113 110 110 125 125 52 60 60 60 53 53 60 80 60 80 DD30CP 2 21 6 28 8 73 69 98 25 60...

Page 62: ...8 8 98 25 34 6 63 70 70 44 45 20 25 25 DD40DNV 2 39 6 135 10 47 6 80 90 90 60 60 20 25 25 RHPDZS090ADC No Heat 20 25 25 20 25 25 DD10DNV 1 9 9 33 77 11 9 35 40 40 15 15 20 25 25 DD15DNV 1 14 4 49 13 1...

Page 63: ...DNV 1 9 9 33 77 11 9 37 40 45 15 15 23 30 30 DD15DNV 1 14 4 49 13 17 3 44 50 50 22 25 23 30 30 DD20DNV 2 19 8 67 55 23 8 52 60 60 30 30 23 30 30 DD30DNV 2 28 8 98 25 34 6 66 70 70 44 45 23 30 30 DD40D...

Page 64: ...DNV 1 9 9 33 77 11 9 42 45 50 15 15 27 35 40 DD15DNV 1 14 4 49 13 17 3 49 60 60 22 25 27 35 40 DD20DNV 2 19 8 67 55 23 8 57 60 60 30 30 27 35 40 DD30DNV 2 28 8 98 25 34 6 70 80 80 44 45 27 35 40 DD40D...

Page 65: ...DNV 1 9 9 33 77 11 9 40 45 45 15 15 25 30 35 DD15DNV 1 14 4 49 13 17 3 47 50 50 22 25 25 30 35 DD20DNV 2 19 8 67 55 23 8 55 60 60 30 30 25 30 35 DD30DNV 2 28 8 98 25 34 6 68 80 80 44 45 25 30 35 DD40D...

Page 66: ...14 20 20 RHPDZS090AYB No Heat 15 20 20 15 20 20 RHPDZS090AYC No Heat 15 20 20 15 20 20 RHPDZS090AYF No Heat 14 20 20 14 20 20 RHPDZS090AYG No Heat 15 20 20 15 20 20 RHPDZS090AYH No Heat 15 20 20 15 20...

Page 67: ...Incorrect voltage At compressor terminals voltage must be 10 of nameplate marking when unit is operating Defective overload protector Replace check for correct voltage Refrigerant undercharge Add ref...

Page 68: ...TO INSTALL LOW AMBIENT ACCESSORY CRANKCASE HEATER ATTACHED TO CC1 L2 AND CC1 AUX 52 COMPRESSOR MOTOR THERMALLY PROTECTED ALL 3 PHASE MODELS ARE PROTECTED UNDER PRIMARY SINGLE PHASE CONDITIONS TRANSFOR...

Page 69: ...SURE SWITCH OUTSIDE AIR SENSOR OUTDOOR COIL TEMPERATURE SENSOR OUTDOOR FAN MOTOR PLUG POWER TRANSFORMER RETURN AIR SENSOR RUN CAPACITOR ROOFTOP UNIT CONTROL REVERSING VALVE SPARK ELECTRODE TERMINAL BL...

Page 70: ...70 T2 T3 T1 COMP AUX 4 5 6 2 1 3 W FIGURE 22...

Page 71: ...DISCONNECT SWITCH DEFROST RELAY FLAME SENSOR FAN PROVING FREEZE SENSOR FREEZE STAT GROUND FAULT CONVENIENCE OUTLET GROUND LUG GROUND HIGH PRESSURE CONTROL INDOOR BLOWER MOTOR INDUCED DRAFT MOTOR INTEG...

Page 72: ...STALL LOW AMBIENT ACCESSORY CRANKCASE HEATER ATTACHED TO CC1 L2 AND CC1 AUX 52 COMPRESSOR MOTOR THERMALLY PROTECTED ALL 3 PHASE MODELS ARE PROTECTED UNDER PRIMARY SINGLE PHASE CONDITIONS TRANSFORMER F...

Page 73: ...POWER SUPPLY L3 L2 L1 DISC OPTIONAL LAC OPT AR OPT 1 2 DR CCH AUX SW GND 1 3 L1 L2 L3 T1 T2 T3 IBM BC 10k ohms OAT 10k ohms OCT DR AR RV DR 6 4 BC 24 VAC US ALARM CODES CODE Description FAULT LEVEL 0...

Page 74: ...EMOVE J3 AT DR 2 TO INSTALL LOW AMBIENT ACCESSORY CRANKCASE HEATER ATTACHED TO CC1 L2 AND CC1 AUX 52 COMPRESSOR MOTOR THERMALLY PROTECTED ALL 3 PHASE MODELS ARE PROTECTED UNDER PRIMARY SINGLE PHASE CO...

Page 75: ...RC2 OFM1 OFM2 L1 L2 L3 T1 T2 T3 CC COMP POWER SUPPLY L3 L2 L1 DISC OPTIONAL VFD S LAC OPT AR OPT 1 2 DR CCH AUX SW GND 1 3 US 10k ohms OAT 10k ohms OCT DR AR RV DR 6 4 24 VAC ALARM CODES CODE Descrip...

Page 76: ...76 PR T2 T3 T1 COMP AUX 4 5 6 2 1 3 FIGURE 28...

Page 77: ...ENSOR DISCONNECT SWITCH DEFROST RELAY FLAME SENSOR FAN PROVING FREEZE SENSOR FREEZE STAT GROUND FAULT CONVENIENCE OUTLET GROUND LUG GROUND HIGH PRESSURE CONTROL INDOOR BLOWER MOTOR INDUCED DRAFT MOTOR...

Page 78: ...78 PR T2 T3 T1 COMP VFD AUX 4 5 6 2 1 3 FIGURE 30...

Page 79: ...CT SWITCH DEFROST RELAY FLAME SENSOR FAN PROVING FREEZE SENSOR FREEZE STAT GROUND FAULT CONVENIENCE OUTLET GROUND LUG GROUND HIGH PRESSURE CONTROL INDOOR BLOWER MOTOR INDUCED DRAFT MOTOR INTEGRATED FU...

Page 80: ...325 350 425 475 525 450 200 40 0 60 0 80 0 20 0 100 0 140 0 160 0 180 0 200 0 220 0 120 0 80 70 60 SYSTEM CHARGE CHART HEATING 92 106139 04 00 CAUTION 1 RETURN AIR TEMPERATURE MUST BE WITHIN COMFORT C...

Page 81: ...81 FIGURE 33...

Page 82: ...0 200 0 210 0 220 0 CAUTION 1 RETURN AIR TEMPERATURE MUST BE WITHIN COMFORT CONDITIONSBEFORE FINAL REFRIGERANT CHECK INSTRUCTIONS 2 MEASURE PRESSURE AT COMPRESSOR SUCTIONAND L IOUID 3 MEASURE OUTDOOR...

Page 83: ...83...

Page 84: ...ct improvement Rheem reserves the right to make changes without notice Rheem Heating Cooling Water Heating P O Box 17010 Fort Smith Arkansas 72917 www rheem com Rheem Canada Ltd Lt e 125 Edgeware Road...

Reviews: