![Rheem RGLE series Installation Instructions Manual Download Page 5](http://html1.mh-extra.com/html/rheem/rgle-series/rgle-series_installation-instructions-manual_1451427005.webp)
Before beginning any troubleshooting procedure, complete the following installation checklist. A furnace malfunction is some-
times caused by an improper installation. By completing this checklist, the problem may be found and corrected. Make copies
of the checklist and complete one for every Low Profile Furnace service call for your records.
INSTALLATION CHECKLIST
(Refer to this manual for specifics.)
GAS SUPPLY
Adequate pipe size
No gas leaks
Proper supply and manifold gas pressure (check with an accurate U-tube manometer with the furnace and all other
gas appliances operating.)
ELECTRICAL
Correct thermostat and subbase
Thermostat model
Subbase model
Correct thermostat mode and setting
Correct line supply voltage
Correct power supply polarity is required with electronic ignition
Correct furnace ground to electrical panel
DC microamp (
∝
A) flame signal (hot surface ignition units)
Correct control voltage
Measure and set heat anticipator amperage
Air conditioning low voltage wires connected to terminals “Y” “C” - not with wire nuts
VENTING
Correct vent pipe diameter and length (according to CSA tables)
Vent connection size
Correct venting material (according to CSA tables)
Correct lining for masonry chimneys
Adequate clearance from combustibles
Proper negative pressure reading in the vent
Vent pipe secured to induced draft blower housing
COMBUSTION AIR
Proper source of combustion air
Optional attic combustion air pull
Correct combustion air opening size
Non-attic combustion air pull
FURNACE INSTALLATION
Adequate clearance from combustibles
Adequate clearance for service
Proper air temperature rise (See furnace rating plate)
External static pressure
inches w.c.
Correct filter(s)
Correct cooling coil or accessories (if equipped)
Adequate supply and return air ducting
Return Air Duct Size
Supply Air Duct Size
Air ducts sealed to prevent leakage
5
Summary of Contents for RGLE series
Page 58: ...TABLE 17 NORMAL OPERATION CODES 58...
Page 66: ...TABLE 20 FURNACE FAULT CODES EXPANDED W DESCRIPTIONS AND SOLUTIONS CONTINUED 66...
Page 67: ...TABLE 20 FURNACE FAULT CODES EXPANDED W DESCRIPTIONS AND SOLUTIONS CONTINUED 67...
Page 68: ...TABLE 20 FURNACE FAULT CODES EXPANDED W DESCRIPTIONS AND SOLUTIONS CONTINUED 68...
Page 69: ...69 TABLE 20 FURNACE FAULT CODES EXPANDED W DESCRIPTIONS AND SOLUTIONS CONTINUED...
Page 70: ...TABLE 20 FURNACE FAULT CODES EXPANDED W DESCRIPTIONS AND SOLUTIONS CONTINUED 70...
Page 71: ...TABLE 20 FURNACE FAULT CODES EXPANDED W DESCRIPTIONS AND SOLUTIONS CONTINUED 71...
Page 72: ...TABLE 20 FURNACE FAULT CODES EXPANDED W DESCRIPTIONS AND SOLUTIONS CONTINUED 72...
Page 75: ...TABLE 20 FURNACE FAULT CODES EXPANDED W DESCRIPTIONS AND SOLUTIONS CONTINUED 75...
Page 76: ...TABLE 20 FURNACE FAULT CODES EXPANDED W DESCRIPTIONS AND SOLUTIONS CONTINUED 76...
Page 77: ...TABLE 20 FURNACE FAULT CODES EXPANDED W DESCRIPTIONS AND SOLUTIONS CONTINUED 77...
Page 79: ...FIGURE 46 WIRE DIAGRAM 79...
Page 95: ...95...
Page 96: ...96 CM 0810...