A new pressure relief valve, complying
with the Standard for Relief Valves and
Automatic Gas Shut-Off Devices for Hot
Water Supply Systems, ANSI Z21.22,
must be installed at the hot water outlet
connection of the water heater at the
time of installation. Local codes shall
govern the installation of relief valves.

For safe operation of the water heater, be
sure that:

The pressure rating of the relief valve
must not exceed 150 psi, the maximum
working pressure of the water heater as
marked on the rating plate.

The BTUH rating of the relief valve
must equal or exceed the BTUH input
of the water heater as marked on its
rating plate.

No valve of any type should be
installed between the relief valve and
the water heater

Discharge from the relief valve should
be piped to a suitable drain to eliminate
potential water damage. Piping used
should be of a type approved for the
distribution of hot water.

Hot and cold water lines should be
insulated up to the water heater. Refer

The discharge line must be NO

SMALLER than the outlet of the valve
and must pitch downward to allow
complete drainage (by gravity) of the

relief valve and discharge line.

The end of the discharge line should not

be threaded or concealed and should be
protected from freezing. No valve of
any type, restriction or reducer coupling
should be installed in the discharge line.

: Local codes govern the

installation of relief valves. If local codes
require that a temperature and pressure
relief valve should be installed the
manufacturer recommends a type 40XL
Watts T&P relief valve or an equivalent
model be used.

: Manual operation of relief valves

should be performed at least once a year.
Turn off the electrical power and gas
shutoff valve. Lift and release lever on the
relief valve and check the manual
operation of the relief valve. You should
take precaution to avoid contact with the
hot water coming out of the relief valve
and to prevent water damage.

: If the relief valve on the system

discharges periodically, a problem exists
and service to the water system is
required.

Notice

Notice

Notice

Relief Valve

Notice

: The above illustrates a

pressure only relief valve. If local
codes require a combination
temperature and pressure relief
valve be installed, an extension
piece may be needed.

Install a Check Valve between the water
heater and the water shutoff valve. (See
illustration the top left).

The following should be addressed in
regards to the HOT WATER OUTLET:

Connections between the water heater

and point(s) of use should be as short
and direct as possible.

DO NOT use lead or plastic pipe.

To conserve energy and minimize heat
loss, insulation of hot water piping is
recommended.

: The flow rate of hot water may

vary when more than two faucets
(appliances, fixtures, etc.) are being used
simultaneously.

: The pipes MUST be completely

drainable. If the hot water faucets are
located at a point higher than the water
heater, place a drain valve at the lowest
point (see diagram to the left).

Notice

Notice

10

Install a shutoff valve near the inlet of the
water heater for service and draining
purposes.

DO NOT use pipes with smaller diameters
than the water supply connection of the
water heater.

Before connecting the water supply pipe
to the water heater, open the shutoff valve
and clean out sand, debris, air, caulking
material, etc. inside the pipe. Connect to
the water inlet, then check water flow.

Close the shutoff valve and clean the
water filter.

Be sure to connect the water inlet and the
hot water outlet as shown on the water
heater. If reversed, the water heater will
not function.

Installation of unions or flexible copper
connections are recommended on the
HOT and COLD water lines, so that the
water heater may disconnect easily for
servicing if necessary.

Water Supply Connections Continued.

Installing the water heater.

Pressure
Relief
Valve

Discharge

line

(To Suitable Drain)

6

Air Gap

Cold Water
Supply Line
Shut-off
Valve

Hot Water
Supply
Outlet

F

ON/OFF

UP

DOWN

Output Temp

Set Temp

Error Code

Error Code

Summary of Contents for Residential Indoor Gas Tankless Water Heater

Page 1: ...ion Instructions for the Installer 136 000 BTU Max Input Recognize this symbol as an indication of Important SafetyInformation California Proposition 65 Warning This product contains chemicals known to the State of California to cause cancer birthdefects or other reproductive harm WARNING If the in formation in these instructions is not followed exactly a fire or explosion may result causing prope...

Page 2: ...he appliance Proof of the original purchase date is needed to obtain service under the warranty Staple sales slip or cancelled check here READ THIS MANUAL Inside you will find many helpful hints on how to use and maintain your water heater properly A little preventive care on your part can save you time and money over the life of your water heater You ll find many answers to common problems in the...

Page 3: ...ire explosion or asphyxiation from carbon monoxide never operate this water heater unless it is installed properly and has an adequate air supply for proper operation Be sure to inspect the flue terminal for proper installation at initial start up and at least annually thereafter Refer to the Care and Cleaning section of this manual for more information regarding flue terminal inspection DANGER IN...

Page 4: ...l panel was set at 110 F before it was shipped from the factory o The illustration to the bottom left illustrates the control panel and how to adjust the water temperature Notice When this water heater is supplying general purpose hot water requirements for use by individuals a thermostatically controlled mixing valve for reducing point of use water temperature is recommended to reduce the risk of...

Page 5: ...r LP gas must be used with great caution It is heavier than air and will collect first in lower areas making it hard to detect at nose level Before attempting to light the water heater make sure to look and smell for gas leaks Use a soapy solution to check all gas fittings and connections Bubbling at a connection indicates a leak that must be corrected When smelling to detect a gas leak be sure to...

Page 6: ...o prevent property damage personal injury or loss of life California Law requires that residential water heaters must be braced anchored or strapped to resist falling or horizontal displacement due to earthquake motions For residential water heaters up to 52 gallon capacity a brochure with generic earthquake bracing instructions can be obtained from Office of the State Architect 400 P Street Sacra...

Page 7: ... fire which may result in severe burns death or property damage The water heater must be located so it is not subject to physical damage for example by moving vehicles area flooding etc If the water heater is installed in a garage it should be installed so that the direct ignition system and main burner are no less than 18 inches above the garage floor Raising the gas fired water heater will reduc...

Page 8: ...r combustion and ventilation air must be made A confined space is one having a volume of less than 50 cubic feet per 1000 Btuh of the aggregate input of all appliances within that space The air must be supplied through two permanent openings of equal area One is to be located within 12 above the floor and the other is to be located within 12 below the ceiling The minimum net free area of each open...

Page 9: ...oors additional water pressure 0 44 psi ft must be ensured The measurement should be calculated by the distance between the water inlet of the water heater ground level to the hot water faucet upper floor level Well water systems should be set at a range of 50 60 psi When the water is supplied from a water supply tank the height of the tank and the diameter of the pipes and their relation to water...

Page 10: ...lief valve and to prevent water damage If the relief valve on the system discharges periodically a problem exists and service to the water system is required Notice Notice Notice Relief Valve Notice The above illustrates a pressure only relief valve If local codes require a combination temperature and pressure relief valve be installed an extension piece may be needed Install a Check Valve between...

Page 11: ...sion could result in hazardous operating conditions 11 Gas Supply The supplied Manual Gas Appliance Shutoff Valve must be installed at the gas connection of the water heater at the time of installation see diagram to the left The branch gas supply line to the water heater should be clean 3 4 black steel pipe or other approved gas piping material A ground joint union or ANSI design certified semi r...

Page 12: ...on monoxide NEVER operate the water heater unless it is properly vented and has adequate air supply for proper operation as outlined in the Venting section of this manual WARNING Use UL approved Category III Stainless Steel vent material only No other vent material is permitted WARNING Refer to page 7 for clearances to combustible material MAXIMUM VENT LENGTH The system will not operate if there i...

Page 13: ...the adapter over the water heater collar before proceeding Adjust clamp as needed With an alcohol wipe clean inside surface A of adapter and outside surface of B of heater collar Apply 1 4 wide bead of high temperature silicone 500 F around outside of heater collar B Slide adapter end A down over heater collar B as far as it will go o Vent Adapter Tighten the clamp around the collar Inspect the in...

Page 14: ... water heater Additional Considerations 14 Horizontal Vent Terminal Location Do Not install vent terminal under any patio or deck To help prevent moisture from freezing on walls and under eaves do not locate vent terminal on the side of a building with prevailing winter winds Do Not terminate vent pipe directly on brick or masonry surfaces Use a rust resistant sheet metal backing plate 2 x 2 feet ...

Reviews: