Rheem RBHP-17A00NH1 Installation Instructions Manual Download Page 19

19

4.0 DUCTWORK

Field  ductwork  must  comply  with  the  National  Fire  Protection Association  NFPA  90A,
NFPA 90B and any applicable local  ordinance.

Sheet metal ductwork run in unconditioned spaces must be insulated and covered with a
vapor barrier. Fibrous ductwork may be used if constructed and installed in accordance
with  SMACNA  Construction  Standard  on  Fibrous  Glass  Ducts.  Ductwork  must  comply
with  National  Fire  Protection Association  as  tested  by  U/L  Standard  181  for  Class  I Air
Ducts. Check local codes for requirements on ductwork and insulation.

• Duct system must be designed within the range of external static pressure the unit is

designed to operate against. It is important that the system airflow be adequate. Make
sure supply and return ductwork, grills, special filters, accessories, etc. are accounted
for in total resistance. See airflow performance tables in this manual.

• Design the duct system in accordance with “ACCA” Manual “D” Design for Residential

Winter  and  Summer Air  Conditioning  and  Equipment  Selection.  Latest  editions  are
available  from:  “ACCA” Air  Conditioning  Contractors  of America,  1513  16th  Street,
N.W., Washington, D.C. 20036. If duct system incorporates flexible air duct, be sure
pressure  drop information  (straight  length  plus  all  turns)  shown  in  “ACCA”  Manual
“D” is accounted for in system.

• Supply  plenum  is  attached  to  the  3/4”  duct  flanges  supplied  on  the  unit  around  the

blower outlet. Flanges are flat for shipping purposes and must be bent up along perfo-
rated edge around blower opening. Be sure to bend flanges completely up so they do
not interfere with air being discharged from blower.

IMPORTANT:  Flanges  around  blower  opening  for  attaching  supply  duct  must  be
bent  up  out  of  blower  discharge  even  if  not  used  so  they  do  not  restrict  airflow
from blower.

• Supply  plenum  should  be  the  same  size  as  the  flanges  provided  around  the  blower

outlet.  Ideally,  it  should  extend  3  feet  from  the  unit  before  turning  or  branching  off
plenum  into  duct  runs.  The  plenum  forms  an  extension  of  the  blower  housing  and
minimizes air expansion losses from the blower. Changing the size, shape or length
will  degrade  blower  performance.  If  supply  discharges  directly  into  a  larger  duct  or
plenum as much as .1” W.C., static pressure will be lost. If 3 feet is not possible, even
6, 12 or 18 inches will help.

IMPORTANT: If an elbow is included in the plenum close to the unit, it must not be
smaller than the dimensions of the supply duct flange on the unit.

• Some units with electric heaters require 1 in. clearance to supply plenum and branch

ducts to combustible material for the first 3 feet from the unit. See CLEARANCES.

• A 3/4” return duct flange is supplied on all sides of the air inlet opening of the unit coil

casing. If the unit is to be installed without a coil casing (no indoor coil), a 3/4” flange
is  supplied  on  the  back  and  sides  of  the  air  inlet  opening  of  the  blower  casing.  No
flange  is  provided  on  the  front  of  the  opening  to  the  blower  casing.  If  return  duct  is
attached to the inlet of the blower casing, the front flange of the duct should be run up
into the opening or 90° brake made on the front flange to tape to the front of the blow-
er casing.

• IMPORTANT: The front flange on the return duct if connected to the blower cas-

ing must not be screwed into the area where the power wiring is located. Drills
or sharp screw points can damage insulation on wires located inside unit.

• Return duct flanges on blower or coil casing are flat for shipping purposes and must

be bent out along perforated edge around opening.

• Secure the supply and return ductwork to the unit flanges, using proper fasteners for

the type of duct used and tape the duct-to-unit joint as required to prevent air leaks.

!

WARNING

UNITS ARE FOR DUCTED APPLICATIONS ONLY. A MINIMUM OF 36 INCHES OF
SUPPLY AIR PLENUM AND DUCTWORK IS REQUIRED. NO SUPPLY AIR OPEN-
INGS,  REGISTERS  OR  FLEXIBLE  AIR  DUCTS  MAY  BE  LOCATED WITHIN THE
FIRST  36  INCHES  OF  SUPPLY  PLENUM  AND  DUCTWORK  ON  UNITS WITH
ELECTRIC  HEATERS.  FAILURE TO  OBSERVE  SUPPLY  PLENUM/DUCT WARN-
INGS  CAN  CAUSE  A  FIRE  RESULTING  IN  PROPERTY  DAMAGE,  PERSONAL
INJURY OR DEATH.

(SEE SPECIFIC AIRFLOW POSITION FOR ADDITIONAL

WARNINGS)

Summary of Contents for RBHP-17A00NH1

Page 1: ...ions thoroughly before attempting installation or operation Failure to follow these instructions may result in improper installation adjustment service or maintenance possibly resulting in fire electrical shock property damage personal injury or death ISO 9001 2008 AIR HANDLERS BHP MODELS FEATURING R 22 REFRIGERANT MODELS FEATURING EARTH FRIENDLY R 410A REFRIGERANT MODELS FEATURING ELECTRIC HEAT W...

Page 2: ...TER 22 8 0 AIRFLOW PERFORMANCE 22 8 1 Airflow Operatng Limits 23 8 2 Airflow Performance Data 23 9 0 SEQUENCE OF OPERATION 25 9 1 Cooling cooling only or heat pump 25 9 2 Heating electric heat only 25 9 3 Heating heat pump 25 9 4 Watt Restrictor 25 9 5 Defrost Sequence 25 9 6 Emergency Heat Heating of Heat Pump 26 9 7 Room Thermostat Anticipator Setting 26 10 0 CALCULATIONS 26 10 1 Calculating Tem...

Page 3: ...iary drain pan under the entire unit to avoid dam age to ceiling is recommended WARNING THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED LICENSED SERVICE PERSONNEL FOR PROPER INSTALLATION SET UP AND OPERA TION OF THIS UNIT READ THESE INSTRUCTIONS THOROUGHLY BEFORE ATTEMPTING INSTALLATION OR OPERATION FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION SET UP SERVICE OR M...

Page 4: ... TO THE COMBUSTIBLE FLOOR BASE IF NOT IT MUST BE CONNECTED TO THE UNIT SUPPLY DUCT FLANGES SUCH THAT COMBUSTIBLE FLOOR OR OTHER COMBUSTIBLE MATERIAL IS NOT EXPOSED TO THE SUPPLY AIR OPENING FROM THE DOWNFLOW UNIT EXPOSING COMBUSTIBLE NON METAL MATERIAL TO THE SUPPLY OPENING OF A DOWNFLOW UNIT CAN CAUSE A FIRE RESULT ING IN PROPERTY DAMAGE PERSONAL INJURY OR DEATH EXCEPTIONS TO DOWNFLOW WARNINGS IN...

Page 5: ... ALL DISCONNECT SWITCHES SUPPLYING POWER TO THE AIRHANDLER MUST BE DE ENER GIZED AND LOCKED IF NOT IN SIGHT OF UNIT SO THE FIELD POWER WIRES CAN BE SAFELY REMOVED FROM THE BLOWER ASSEMBLY FAILURE TO DO SO CAN CAUSE ELECTRICAL SHOCK RESULTING IN PERSONAL INJURY OR DEATH WARNING UNITS ARE FOR DUCTED APPLICATIONS ONLY A MINIMUM OF 36 INCHES OF SUPPLY AIR PLENUM AND DUCTWORK IS REQUIRED NO SUPPLY AIR ...

Page 6: ...ower wires control wires refrigerant tubing and condensate line where they enter the cabinet Seal the power wires on the inside where they exit conduit opening Caulking is required to prevent air leakage into and condensate from forming inside the unit control box and on electrical controls Install the unit in such a way as to allow free access to the coil filter com partment and blower control co...

Page 7: ...or installation not made in accordance with the Underwriters Laboratory UL certification or these instructions can result in unsatisfactory operation and or dangerous conditions and are not cov ered by the unit warranty Duct leaks can create an unbalanced system and draw pollutants such as dirt dust fumes and odors into the home causing property damage Fumes and odors from toxic volatile or flamma...

Page 8: ...stems NFPA90B Installation of warm air heating and air conditioning systems The equipment has been evaluated in accordance with the Code of Federal Regulations Chapter XX Part 3280 2 3 CLEARANCES All units are designed for 0 inches clearance to combustible material on all cabinet surfaces Some units require supply duct clearances and combustible floor bases depending on the heating kW The followin...

Page 9: ...LASSIFICATION B BLOWER UNIT TRADEBRAND CABINET SIZE 17 17 5 21 21 0 24 24 5 25 24 5 APPLICATION H HEAT PUMP AIR HANDLER 2 4 UNIT MODEL EXPLANATION AVAILABLE MODELS FEATURING R 410A REFRIGERANT BHP 17A00NH1 BHP 17J06SH1 BHP 17J07SH1 BHP 17J11SH1 BHP 21A00NH2 BHP 21J06SH2 BHP 21J07SH2 BHP 21J11SH2 BHP 24A00NH4 BHP 24J06SH4 BHP 24J07SH4 BHP 24J11SH4 BHP 24J18SH4 BHP 25A00NH7 BHP 25J11SH7 BHP 25J18SH7...

Page 10: ...ZE UNIT WIDTH W IN SUPPLY DUCT A IN UNIT WITH COIL MAX kw UNIT WEIGHT SHIPPING WEIGHT LBS UNIT WITHOUT COIL MAX kw 17 171 2 79 16 92 99 323 6 348 2 66 75 232 1 263 8 21 21 97 16 109 117 383 3 411 5 79 87 277 8 306 24 241 2 113 4 125 134 439 6 471 3 88 97 309 5 341 1 25 241 2 113 4 125 134 439 6 471 3 88 97 309 5 341 1 2 5 DIMENSIONS AND WEIGHTS ...

Page 11: ...nd gasketing when unit is installed in attic applications If installed in an unconditioned space apply caulking around the power wires control wires refrigerant tubing and condensate line where they enter the cabinet Seal the power wires on the inside where they exit conduit opening Caulking is required to prevent air leakage into and condensate from forming inside the unit control box and on elec...

Page 12: ...ir is to be ducted install duct flush with floor Use fireproof resilient gasket 1 8 to 1 4 in thick between duct unit and floor Set unit on floor over opening 2 8 VERTICAL DOWNFLOW Conversion to Vertical Downflow A vertical upflow unit may be converted to vertical downflow See Figure 3 Remove the indoor coil Install coil rails in the top of the coil box supplied Rotate unit into the downflow posit...

Page 13: ...reaker lug Replace breaker by inserting breaker mounting tab opposite white pull tab in opening hook mounting tab over edge in opening With screwdriver or pencil pull white tab with hole away from breaker while setting that side of breaker into opening When breaker is in place release tab locking circuit break er into location in opening Repeat above operation for remaining breaker s if more than ...

Page 14: ... AIR SUPPLY HORIZONTAL DRAIN PAN MUST BE LOCATED UNDER INDOOR COIL FAILURE TO USE THE DRAIN PAN CAN RESULT IN PROPERTY DAMAGE FIGURE 6 INDOOR COIL AND DRAIN PAN SET UP HORIZONTAL LEFT HAND AIR SUPPLY FIGURE 7 INDOOR COIL AND DRAIN PAN SET UP HORIZONTAL RIGHT HAND AIR SUPPLY I156 I156 WARNING THE FIRST 36 INCHES OF SUPPLY AIR PLENUM AND DUCTWORK MUST BE CONSTRUCTED OF SHEET METAL AS REQUIRED BY NFP...

Page 15: ... circuit disconnect of adequate size located within sight of and readily accessible to the unit Units with factory installed circuit breaker s meet UL and CSA requirements as a ser vice disconnect and should make above requirement for a field installed branch circuit disconnect unnecessary IMPORTANT Units may be equipped with one two or three 60 amp circuit breakers These breaker s protect the int...

Page 16: ...han 100 ft 16 AWG wire should be used Control wiring should be routed through 1 2 dia knockout near power wiring entrance on either left or right side of unit After opening selected knockout install bushing supplied in parts bag in openings If control wiring is routed through right side upflow it must be routed through extrud ed holes in lower front of blower housing behind power raceway to the le...

Page 17: ... 29 7 33 4 38 42 40 45 BHP 24J11SH 7 5 10 0 1 60 3 3 3 Single Circuit 40 3 45 9 51 58 60 60 13 2 17 5 5 3 5 Single Circuit 67 7 77 1 85 97 90 100 BHP 24J18SH 5 3 7 0 1 60 2 3 5 Multiple Ckt 1 29 7 33 4 38 42 40 45 7 9 10 5 3 3 5 Multiple Ckt 2 39 0 43 8 48 55 50 60 BHP 25J11SH 7 5 10 0 1 60 3 3 3 Single Circuit 91 8 47 4 53 60 60 60 13 2 17 5 5 3 5 Single Circuit 69 2 78 6 87 99 90 100 BHP 25J18SH...

Page 18: ... TYPICALTHERMOSTAT WIRING STRAIGHT COOLING WITH ELECTRIC HEAT B W2 G Y W1 B C R Air Handler Control Board Y G W2 E Heat PumpThermostat Heat Pump Outdoor Unit C R Y B C R D Y G BK BR W BL W BK BL BR R Y BL R P FIGURE 9 HEAT PUMP WITH ELECTRIC HEAT Purple Recommitted to jump W1 and W2 together for maximum temperature rise ...

Page 19: ...lenum forms an extension of the blower housing and minimizes air expansion losses from the blower Changing the size shape or length will degrade blower performance If supply discharges directly into a larger duct or plenum as much as 1 W C static pressure will be lost If 3 feet is not possible even 6 12 or 18 inches will help IMPORTANT If an elbow is included in the plenum close to the unit it mus...

Page 20: ...brazing When making braze connections close to outside of cabinet use a brazing shield to protect cabinet paint from being damaged from torch flame If the installation is in a tight location it might be convenient to make some external tubing connections before setting unit in place IMPORTANT Install refrigerant tubing so it does not block service access to front of unit 24 in clearance is require...

Page 21: ...astic web covering secondary connection must be broken out if used Secondary connection is lowered by 3 8 Do not get primary and secondary con nections interchanged Removal of door knockouts required for drain connections can be made much easier with the door removed from the cabinet Install drain lines so they do not block service access to front of unit 24 in clearance is required for filter coi...

Page 22: ...ould be installed in the return air system If a remote filter is installed it should be sized for a maximum of 300 feet min air velocity for the CFM required IMPORTANT Do not operate system without a filter A filter is required to protect the coil blower and internal parts from excessive dirt and dust See unit position figures for location of filter in unit cabinet and service panel giving access ...

Page 23: ...8 334 223 672 317 226 3 max 4 208 240 834 393 146 809 831 150 789 372 159 754 355 164 3 max 5 208 240 946 446 179 922 435 189 902 426 193 876 413 203 843 398 206 804 380 216 773 365 221 748 353 231 696 328 240 660 311 243 none 4 115 846 399 143 821 387 148 801 378 157 766 361 162 none 5 115 964 455 167 945 446 178 914 431 181 888 419 191 861 406 196 821 387 205 787 372 210 761 359 218 726 342 220 ...

Page 24: ...1 582 1889 891 599 1846 871 617 1805 851 626 1783 841 638 5 max 2 208 240 1831 854 393 1795 847 413 1756 828 427 1720 811 439 5 max 3 208 240 2043 964 517 2004 945 531 1985 936 553 1951 920 573 1912 901 583 1878 886 602 1857 876 619 1814 856 637 1773 836 646 1751 826 658 none 2 115 1872 883 373 1837 866 393 1798 848 407 1763 832 419 none 3 115 2075 979 497 2036 960 511 2017 951 533 1984 936 553 19...

Page 25: ...heater circuit or may be in the control circuit controlling heater sequencer HR2 indirectly controlling two or three heater elements HE see unit wiring diagram The watt restrictor WR will restrict the amount of supplemental electric heat that can be energized dependent on the heat output of the heat pump temperature of the air leaving the indoor heat pump coil Since the heat output of the heat pum...

Page 26: ... air circulation from the other rooms being con trolled by the thermostat It is essential that there be free air circulation at the location of the same average temperature as other rooms being controlled Movement of air should not be obstructed by furniture doors draperies etc The thermostat should not be mounted where it will be affected by drafts hot or cold water pipes or air ducts in walls ra...

Page 27: ...turned up Is ductwork correctly sized run taped and insulat ed have all cabinet openings and wiring been sealed with caulking Is the indoor coil flowcheck piston and valve size correct Is the filter clean in place and of adequate size Is the wiring tight correct and to the wiring diagram Is the unit properly grounded and protected fuse Is the thermostat heat anticipator been set properly Is the un...

Page 28: ...n line from the unit away from the pan and coil to clear the drain line IMPORTANT Do not use caustic household drain cleaners in the condensate pan or near the indoor coil Drain cleaners will quickly damage the indoor coil 12 3 BLOWER MOTOR AND WHEEL Inspect the blower motor and wheel for cleanliness With the system air filter in place it should be several years before it would become necessary to...

Page 29: ...m the blower housing without disturbing the motor or blower wheel Remove both wires from the heater to be removed and remove three screws from outside of blower wrap holding heater brackets to blower wrap One screw is located under the control mounting plate and is a little difficult to get at A 1 4 box end or open end wrench should be used to remove and replace this screw With three screws remove...

Page 30: ...and the outside of the blower wheel Re assemble the motor wiring high and low voltage plugs into the motor IMPORTANT DO NOT FORCE POWER PLUG INTO THE MOTOR CONNECTOR BACKWARDS The A C power plug to the motor has locking tabs It has been proven that by applying excessive force to the A C cable half of the connector it is possible to force the connector in backwards It will not seat and click proper...

Page 31: ...hree phase multiple two circuit units to a single supply circuit If a factory supplied jumper bar for single supply circuit is removed from unit to make multiple supply circuits the line side of the circuit breakers must be covered with fin ger safe covers Each circuit breaker pole must be covered with a finger safe cover Finger Safe Circuit Breaker Cover Part number 45 23203 01 One is required fo...

Page 32: ...32 CM 0316 FIGURE 13 WIRING DIAGRAM ...

Reviews: