9
INSTALLATION
Installation Codes
Installations must follow these codes:
• Local, state, provincial, and national codes, laws,
regulations and ordinances
• National Fuel Gas Code, ANSI Z223.1/NFPA 54 –
latest edition (NFGC)
• National Electrical Code, ANSI/NFPA 70 - latest
edition (NEC)
• Standard for Controls and Safety Devices for Auto-
matically Fired Boilers, ANSI/ASME CSD-1, when
required (CSD-1)
• For Canada only: CAN/CGA B149 Installation
Code (B149) and CSA C22.1 C.E.C. Part 1 (C22.1)
The temperature of the water in the heater can be reg-
ulated by using the temperature controller. To comply
with safety regulations, the temperature controller is
set at the lowest setting when shipped from the factory.
To adjust the water temperature, insert a small straight
screwdriver into the adjustment screw on the front of
temperature controller and turn the wheel to the de-
sired setting (See Fig. 4.).
A
CAUTION:
Hotter water increases the risk of
scalding! There is a hot water scald potential if
the thermostat is set too high.
Fig. 4: Temperature Control
Equipment Base
The heater should be mounted on a level, structurally
sound surface. The heater is approved for installation
on a combustible surface but must NEVER be installed
on carpeting. Gas-fueled equipment installed in en-
closed parking garages must be located at least 18 in.
above the floor.
Stacking
Delta Limited units can be stacked two units high with
an optional stacking rack. A stacking kit is available
from Raypak for this type of installation.
A
CAUTION:
The heaters should be located in
an area where water leakage will not result in
damage to the area adjacent to the appliances or
to the structure. When such locations cannot be
avoided, it is recommended that a suitable catch
pan, adequately drained, be installed under the
appliance. The pan must not restrict air flow.
REQUIRES OPTIONAL VENT TEE.
REQUIRES OPTIONAL VENT TEE IF VENTED OUT BACK
OF HEATER.
Fig. 5: Typical Stacked Installation
Summary of Contents for Raypak Delta Limited 399B
Page 39: ...39 Wiring Diagram Models 399B 1259B...
Page 40: ...40 Wiring Diagram Models 1529B 2339B...
Page 51: ...51 DIAGNOSTIC DETAIL 12 J 7 J 6 J 5 J 3 0 2 0 16 S 1 F 2 F 3 F 4 F BLOWER DETAIL...
Page 53: ...53 13 J 8 J 10 J 11 J 4 J 2 J 3 J 6 C 14 J 9 J 1 J CONTROL BOX DETAILS...
Page 57: ...57 ILLUSTRATED PARTS LIST MODELS 989B 2339B 10 J 3 O 5 O...
Page 58: ...58 12 H 6 H 7 H 8 H 2 H 9 H 3 H 5 H 1 H 4 H 1 P HEAT EXCHANGER DETAILS BURNER ASSEMBLY DETAILS...
Page 59: ...59 CONTROL BOX DETAILS 9 J 8 J 23 S 13 J 10 J 3 O 10 J 3 O 5 O FRONT SWITCH DETAILS...
Page 66: ...66...
Page 67: ...67 Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 Litho in U S A NOTES...