16
Rheem Manufacturing Company
Electrical and Physical Data: RAPL- JEZ
Model
No.
RAPL-
ELECTRICAL
PHYSICAL
Phase
Hertz
Volts
Compr.
RLA
Compr.
LRA
Fan
Motor
FLA
Min. Circuit
Ampacity
Amps
Fuse or HACR
Circuit Breaker
Outdoor Coil
Refrig.
Per Circuit
Oz. [g]
Weight
Min. Amps
Face Area
Sq. Ft. [m
2
]
No.
Rows
CFM [L/s]
Net
Lbs. [kg]
Shipping
Lbs. [kg]
Max. Amps
018JEZ 1-60-208/230
9/9
48
0.8
12/12
15/15
20/20
11.00 [1.02]
1
1900 [897]
79 [2240] 140 [63.5] 150 [68.0]
030JEZ 1-60-208/230 12.8/12.8
64
1.2
17/17
25/25
30/30
20.00 [1.86]
1
3200 [1510] 135 [3827] 200 [90.7] 210 [95.3]
036JEZ 1-60-208/230 16.7/16.7
79
1.2
22/22
30/30
35/35
23.01 [2.14]
1
3200 [1510] 141 [3997] 230 [104.3] 240 [108.9]
042JEZ 1-60-208/230 17.9/17.9
112
1.2
24/24
30/30
40/40
23.01 [2.14]
1
3200 [1510] 152 [4309] 230 [104.3] 240 [108.9]
048JEZ 1-60-208/230 21.8/21.8
117
1.2
29/29
35/35
50/50
23.01 [2.14]
1
3300 [1557] 152 [4309] 230 [104.3] 240 [108.9]
060JEZ 1-60-208/230 26.4/26.4
134
1.2
35/35
45/45
60/60
44.00 [4.09]
2
3100 [1463] 286 [8108] 280 [127.0] 290 [131.5]
024JEZ 1-60-208/230 13.5/13.5
58.3
0.8
18/18
25/25
30/30
11.00 [1.02]
1
2300 [1085] 105 [2977] 140 [63.5] 150 [68.0]
Electrical and Physical Data: RANL- JEZ
Model
No.
RANL-
ELECTRICAL
PHYSICAL
Phase
Hertz
Volts
Compr.
RLA
Compr.
LRA
Fan
Motor
FLA
Min. Circuit
Ampacity
Amps
Fuse or HACR
Circuit Breaker
Outdoor Coil
R-410A
Oz. [g]
Weight
Min. Amps
Face Area
Sq. Ft. [m
2
]
No.
Rows
CFM [L/s]
Net
Lbs. [kg]
Shipping
Lbs. [kg]
Max. Amps
024JEZ 1-60-208-230 12.8/12.8
58.3
0.6
17/17
20/20
25/25
11.00 [1.02]
1
1920 [906]
72 [2041] 140 [63.5] 150 [68.0]
030JEZ 1-60-208-230 14.1/14.1
73
0.8
19/19
25/25
30/30
12.94 [1.20]
1
2470 [1166]
94 [2665] 160 [72.6] 170 [77.1]
036JEZ 1-60-208-230 17.9/17.9
112
0.8
24/24
30/30
40/40
17.26 [1.60]
1
2570 [1213] 113 [3204] 205 [93.0] 215 [97.5]
042JEZ 1-60-208-230 17.9/17.9
112
1.2
24/24
30/30
40/40
17.26 [1.60]
1
3290 [1553] 130 [3686] 205 [93.0] 215 [97.5]
048JEZ 1-60-208-230 21.8/21.8
117
1.2
29/29
35/35
50/50
23.01 [2.14]
1
3500 [1652] 145 [4111] 230 [104.3] 240 [108.9]
060JEZ 1-60-208-230 26.3/26.3
134
1.2
35/35
45/45
60/60
23.01 [2.14]
1
3500 [1652] 180 [5103] 250 [113.4] 260 [117.9]
[
] Designates Metric Conversions
AIR DISCHARGE
ALLOW 60
⬙
[1524 mm] CLEARANCE
AIR INLETS
(LOUVERS)
ALLOW 6
⬙
[152 mm]
MIN. CLEARANCE
3 SIDES
ALLOW 24
⬙
[610 mm]
ACCESS CLEARANCE
ACCESS
PANEL
W
L
H
A-0
000
1
SERVICE
FITTINGS
LOW VOLTAGE
7
/
8
⬙
[22 mm]
HIGH VOLTAGE
1
11
/
32
⬙
[34 mm]
LIQUID LINE
CONNECTION
SERVICE ACCESS
TO ELECTRICAL &
VALVES ALLOW
24
⬙
[610 mm]
CLEARANCE
ONE SIDE
2
7
/
8
⬙
[73 mm] DIA.
ACCESSORY
KNOCKOUTS
VAPOR LINE
CONNECTION
HIGH PRESSURE
CONTROL
MANUAL RESET
(FIELD INSTALLED
ACCESSORY)
A-00003
Unit Dimensions
Model Number
RAPL-
Height “H”
(Inches) [mm]
Length “L”
(Inches) [mm]
Width “W”
(Inches) [mm]
018JEZ/024JEZ
19 [483]
40
1
/
2
[1029]
27
5
/
8
[702]
030JEZ
29 [737]
44
3
/
8
[1127]
31
1
/
2
[800]
036JEZ/042JEZ/
048JEZ/060JEZ
33 [838]
44
3
/
8
[1127]
31
1
/
2
[800]
Model Number
RANL-
Height “H”
(Inches) [mm]
Length “L”
(Inches) [mm]
Width “W”
(Inches) [mm]
024JEZ
19 [483]
40
1
/
2
[1029]
27
5
/
8
[702]
048JEZ/060JEZ
33 [838]
44
3
/
8
[1127]
31
1
/
2
[800]
036JEZ/042JEZ
25 [635]
44
3
/
8
[1127]
31
1
/
2
[800]
030JEZ
19 [483]
44
3
/
8
[1127]
31
1
/
2
[800]