background image

#

Remedy

13

Verify last defrost cycle duration under 

Status →Defrost→Last Defr. Time

, and/or force a defrost manually and time it to verify 

duration.  Low Profile and Center Mount evaporators should not defrost for longer than 30‐35 minutes.  Adjust Defrost 
Termination Temperature (

Def. Term. Temp

) down as needed, and also adjust the Maximum Defrost Time (

Def. Max Run 

Time

) down from the 60 minute default setting if needed.

14

The Drain Temp sensor may be used on Low Profile Freezers as an additional early warning that ice is building up on the drain 
pan.  To enable this function set 

Drain Sensor?

 to YES on 

Settings →Equipment

, and make sure that a Drain Temp Sensor (part 

no. 08219623) is connected to the controller (DRAIN) and secured to the drain pan (carefully securing the sensor wire from 
touching the heaters).  When a defrost cycle ends, if the Drain Temp does not reach Termination Temp, the controller will 
generate the 

"Drain Temp < Defrost Termination Temp." 

alarm.  Verify that the drain pan heater is connected and working 

properly, and/or that the sensor is properly placed flat on the drain pan secured with the same nut that is holding the heater 
bracket.  Verify that drain line is free of obstruction and heat tape is working properly to keep the line warm.

15

If no Drain Temp sensor is installed, make sure Drain Temp sensor is configured to NO under 

Settings →Equipment→Drain 

Temp?

.  If a Drain Temp sensor is meant to be installed, make sure the sensor is reconnected or replaced (part no. 08219623)

16

Go to 

Settings →Equipment→Aux Temp?

 and make sure it is configured to NO.  The Aux Temp sensor input is not used in the 

current software version.

Air Defrost units (set to 

Cooler

) typically end defrost on maximum time, so in this scenario this notification would be nomal.  If a 

shorter or longer defrost cycle is desired, the Max Defrost Time can be adjusted under 

Settings →Equipment→Def. Max Run 

Time

 (default is 60 minutes).

Electric Defrost units (set to 

Freezer

) typically end defrost when the Evap Temp reading reaches Defrost Termination 

Temperature.  If an Electric Defrost evaporator is ending defrost on maximum time instead, verify under  

Settings→Equipment→Def. Max Run Time

 is set to no less than 30 minutes (or is already at the default 60 minutes).  If it is still 

terminating on max time, verify the Evap Temp sensor and electric heaters by referring to items 10 and 11 in this guide.

Verify that each controller that is intended to work in the group is addressed properly.  On each controller display, go to 

Settings →Equipment→Group‐Member Cfg.

 to set the address.  Group 1 Leader will be G1‐L, Group 1 Follower #2 will be G1‐2, 

Group 1 Follower #3 will be G1‐3, etc.  Same for Groups 2, 3 and 4.  Each group will support a maximum of 6 evaporators (1 
 5 Followers).  Make sure that there are no conflicting addresses set between two or more controllers.

Verify that the communication wire used is at least 

22 gauge, shielded

.  Verify each of the 3 conductors are terminated at each 

board on E1, E2 and RT terminals and that polarity is maintained from board terminal to board terminal (a wire landed at E1 on 
the first board has to go to E1 on every other board on the daisy chain; same for E2 and RT).  Verify that the shielding strands 
are connected at every splice and terminated at a ground point on one end of the daisy chain only.

Verify on each controller in the group that 

System Enable

 is set to YES.  Go to 

Settings →System Enable 

and verify that all the 

controllers in the group are set to YES.

Verify software version at each controller on the display by navigating to 

Service →So ware Version

.  Every controller in one 

Group must be running the same software version for the group function to operate properly.  If you are having group sync 
issues and have one or more boards where the software version does not match the others, please call Customer Support.

Go to 

Settings →Date and Time

 on each controller board display to set the controller time clock.  If you have a Command 

Center Display wired to one or more controller boards, the time clock can be set there and it will be simultaneously broadcast to 
every controller connected.

If the controller board remains powered off for more than a couple of days, the time clock will have to be reset.  Go to 

Settings →Date and Time

 on each controller board display to set the controller time clock.  If you have a Command Center 

Display wired to one or more controller boards, the time clock can be set there and it will be simultaneously broadcast to every 
controller connected.

If installing Command Center within 150 feet of the nearest EcoNet controller, make sure that the wires from the R and C 
terminals at the Command Center mounting bracket are securely connected to the 0V and 16V terminals at the controller.  
Make sure the controller is powered on.  If Command Center is installed more than 150 feet away from nearest controller, make 
sure it is connected to a separate 24VAC or 24VDC power supply.  Please refer to the Command Center wiring diagram on Page 
13 of the EcoNet Installation Manual.

Inspect the Command Center Display for signs of damage (cracked screen, burn marks on the circuit board/mounting bracket, 
broken components).  If damaged, replace the Command Center Display.  Make sure that the Command Center is installed 
indoors, outside of the walk‐in cooler/freezer, and that it does not get wet or dropped.

Time clock on controller may not have been set.

Time clock on controller may have been set at 
install, but a prolonged power loss may have reset 
it.

Time stamp on the Alarm History is not 
accurate.

EcoNet controller may not be addressed properly 
to work as part of the group.

EcoNet controller may not be wired properly to 
the rest of the group.

One or more controllers in the group may be 
manually disabled.

One controller may have a different software 
version from the other controllers in the group.

I have multiple evaporators in the same 
box working as a group, but one or more 
of them are not cooling/operating in sync.

Make sure that Command Center Display is 
connected to a power supply.

Command Center Display could be damaged.

Command Center Display screen is blank.

EcoNet Controller generates alarm 

"A002 

Drain Temp < Defrost Termination 
Temp." 

(Low Profile FREEZER only).

There may be ice on the drain pan after a defrost 
cycle ended; drain line could be blocked.

Evaporator Coil is steaming excessively 
during a defrost; water droplets 
accumulating on the ceiling (Low Profile 
and Center Mount FREEZER units).

Defrost cycle is running too long.

EcoNet Controller generates notification 

"T001 Defrost Failure: Max Time Expired"

Problem

Possible Cause

17

Evaporator works on Air Defrost

Evaporator works on Electric Defrost

EcoNet Controller generates alarm "

A104 

Drain Temp Thermistor Failure

"

Drain Temp Sensor configured to YES under 
Settings and sensor is not connected.

EcoNet Controller generates alarm "

A105 

Aux Temp Thermistor Failure

"

Aux Temp Sensor is configured to YES under 
Settings and sensor is not connected.

18

19

20

Page 3 of 4

Summary of Contents for HTPG EcoNet Series

Page 1: ...Unit Coolers Troubleshooting Guide 3885 Crestwood Pkwy Ste 500 Duluth Georgia 30096 www htpg com Phone 800 288 9488 256 259 7400 Fax 256 259 7478 A member of the Rheem family of brands HTPG EN TG0821...

Page 2: ...via display under Status Outputs Aux Relay 1 Aux Relay 2 Relay operation for fan speed control is as follows Aux Relay 1 ON Full Speed Aux Relays 1 2 ON Half Speed Aux Relays 1 2 OFF Fans off If dama...

Page 3: ...g properly proceed to verify defrost cycle duration on the controller display go to Status Defrost Last Defr Time Also force a defrost and wait for it to finish to take note of the duration Low Profil...

Page 4: ...Settings System Enable and verify that all the controllers in the group are set to YES Verify software version at each controller on the display by navigating to Service So ware Version Every control...

Page 5: ...ment Network Instance Make sure that communication wires from E1 and E2 terminals at the Command Center mounting bracket are securely connected at the E1 and E2 terminals respectively on the first con...

Page 6: ...art of initial startup of the controller 4 If the valve does not make any noise a Verify connection to the valve is secure and that the 4 pins on the valve are not bent b Verify that the wiring harnes...

Page 7: ...6 With the meter test leads touching pins 1 and 3 when the controller signals that the output to the valve reached the desired position between 35 and 65 visible via Status EXV the meter should read a...

Page 8: ...L MNOL J PI QJ L S NT UV L MI W X YV Y PI QJ L Z L MN NT _ I L aL X I b L c d e g h i j k lV YQL T Nm n L o MI W X YV Y p L T I J S L YoL T I V T L qV T X p I J J rstu v rstu w rstu x y z u y u z e y...

Page 9: ...6 5 0 8 6 6 4 8 9 0 70 2 5 6 6 8 8 9 76 8 6 5 0 8 6 8 9 5 6 5 6 6 5 6 6 8 6 5 6 8 9 MN 8 8 9 5 0 8 8 6 I O O 0 8 6 8 9 P Q R 5 8 6 N4 85 0 5 6 S70 8 2 T 6 8 9 5 5 9 6 4 2 58 5 0 8 0 0 9 8 6 5 P 5 0 8...

Reviews: