background image

#

Remedy

Close door to the box.  Make sure door remains closed unless/until access to box is needed.

Verify at controller display the current superheat and valve position; go to 

Status →Superheat/EXV Current Pos.

  If superheat is 

consistently high and valve is consistently running at or close to 100%, the system could be low on refrigerant.  Verify if sight 
glass at condensing unit is clear.  Verify suction pressure with a set of gauges.  Recharge system as needed, verify if any leaks are 
present and fix as needed.

Verify at condensing unit if compressor is shutting down intermittently.  Troubleshoot condensing unit and verify if high head 
pressure, phase loss, etc.

Verify under the controller settings that the correct refrigerant is selected.  On the display, go to 

Settings →Equipment→Refrigerant

.  An incorrect refrigerant setting will cause incorrect superheat calculation and the system 

will not operate properly.

Verify if Suction Temp Thermistor alarm is active: on controller display go to 

Service →Current Alarms

.  Also verify Suction 

Temperature reading under 

Status→Sensors→Suc on Temp

; if it is reading "‐60 ⁰F", the sensor is not making good contact or is 

missing.  If Suction Temp sensor input is missing, the EXV will remain at a fixed position until sensor is replaced, and alarm 

"A100 Suction Temp Thermistor Failure"

 will be active.  If sensor is reading a value other than ‐60  ⁰F, verify that it is not an 

erratic value and that the reading reasonably corresponds to the conditions at the evaporator (for example, if sensor is reading 
150 ⁰F when the suction line at the evaporator is near freezing conditions).   Replace Suction Temp Thermistor (part no. 
08219637).

Verify if Suction Pressure alarm is active: on controller display go to 

Service →Current Alarms

.  Also verify Suction Pressure 

reading under 

Status→Sensors→Suc on Pressure

; if it is reading "‐14.7 PSIG", the sensor is malfunctioning or is disconnected.  

If the controller detects that the pressure input is missing, alarm 

"A106 Suction Pressure Sensor Failure"

 will be active and the 

controller will attempt to calculate approximate superheat by using Evap Temp 1 reading instead of Saturated Suction Temp and 
continue metering the EXV, but the calculated superheat will not be as accurate.   Replace Suction Pressure Transducer (part no. 
08219621).

Verify harness connection to the EXV and to the controller board is secure.  Set System Enable to NO, under 

Settings →System 

Enable

 in order to close the EXV and force a pumpdown.  Confirm that the EXV can be heard moving as it closes.  Confirm EXV 

position under 

Status→EXV→EXV Current Pos.

 is 0%.  Verify that compressor pumps down and shuts off after a couple of 

minutes; Suction Pressure reading under 

Status→Sensors→Suc on Pressure

 should decrease as the system pumps down.  If 

the compressor is still running and does not turn off, the EXV may be malfunctioning and allowing some refrigerant to pass 
through even after being commanded by the controller to close.   See 

Addendum A

 for more information on troubleshooting the 

EXV.  Replace EXV if necessary.

Make sure door to the freezer is kept closed unless/until access to freezer is needed.

Verify that when controller starts a defrost, the heaters are energized and operating properly.  A manual defrost can be started 
by going on the display to 

Service →Defrost Control→Start a Defrost

.  Verify at the controller board that the LED's for the 

defrost relays turn ON and their status is ON on the display (

Status→Outptus→Defrost Relay #1/#2

).  

If the unit is a Low 

Profile evaporator, make sure that Coil Type is set to "Single" 

(go to 

Settings→Equipment

 and scroll down to verify these 

parameters), and that Evap Temp 1 sensor is connected and having a valid reading.  If Evap Temp 1 sensor is disconnected, the 
controller will alarm (

"A101 Evaporator Temp Sensor Failure"

) and the Defrost Relays will not turn ON.  If Coil Type is 

mistakenly set to Dual, the controller will alarm (

"A102 Evap Temp 2 Thermistor Failure"

) and the missing Evap Temp 2 sensor 

will prevent Defrost Relay #2 from turning on; this would keep the bottom heater and drain pan heater from turning on during a 
defrost and will cause ice build up on the bottom part of the coil.  If both Defrost Relays are turning ON, verify with a meter that 
the heaters are drawing amps and are warming up; if they are not, verify the heater wiring with the wiring diagram at the 
evaporator.  If the heaters are wired properly but still not heating, they may need to be replaced.

If the heaters are verified to be working properly, proceed to verify defrost cycle duration: on the controller display, go to 

Status →Defrost→Last Defr. Time

.  Also, force a defrost and wait for it to finish to take note of the duration.  Low Profile 

Evaporators typically need between 20 to 30 minutes defrost duration to clear the ice.  If the defrost cycle is too short, the 
Defrost Termination Temperature (

Def. Term. Temp

) and Runtime Until Defrost (

Def. Cmp. Run Time

)  can be adjusted as 

needed in 

Settings→Equipment

.  Also, the pulsing on Defrost Relay #1 (top heater) can be disabled by setting 

Defrost Pulse 

Override

 to YES if needed.  If the unit already has some ice built up in the coil, it may take several defrost cycles to clear the ice 

after the parameters mentioned above are adjusted.

Make sure door to the freezer is kept closed unless/until access to freezer is needed.

Verify that when controller starts a defrost, the heaters are energized and operating properly.  A manual defrost can be started 
by going on the display to 

Service →Defrost Control→Start a Defrost

.  Verify on the controller board that the LED's for the 

defrost relays turn ON and their status is ON on the display (

Status→Outptus→Defrost Relay #1/#2

). 

 

If the unit is a Center 

Mount evaporator, make sure that 

Coil Type

 is set to 

"Dual"

 and 

Defrost Pulse Override

 set to 

"YES"

 (go to 

Settings→Equipment

 

and scroll down to verify these parameters), and that Evap Temp 1 and Evap Temp 2 sensors are 

connected and having a valid reading.  If Evap Temp 1 sensor is disconnected, the controller will alarm (

"A101 Evaporator Temp 

Sensor Failure"

) and Defrost Relay #1 will not turn ON; if Evap Temp 2 sensor is disconnected, the controller wil alarm (

"A102 

Evap Temp 2 Thermistor Failure"

) and Defrost Relay #2 will not turn ON.  If the Defrost Relays are turning ON, verify with a 

meter that the heaters are drawing amps and are warming up; if they are not, verify the heater wiring with the wiring diagram 
at the evaporator.  If the heaters are wired properly but still not heating, they may need to be replaced.

On Center Mount evaporators (

Coil Type = Dual

), both Evap Temp 1 (white wires) and Evap Temp 2 (blue wires) are used for 

defrost termination.  During a defrost cycle, when Evap Temp 1 sensor reaches Defrost Termination Temp, the Defrost Relay #1 
will turn off.  Same for Evap Temp 2 with Defrost Relay #2; each side will terminate defrost independently.  Verify with the 
wiring diagram on the unit that Evap Temp 1 sensor is located on the coil whose heaters are wired to Defrost Relay #1.  Same 
goes for Evap Temp 2, it should be located on the coil whose heaters are wired to Defrost Relay #2.

On Center Mount evaporators (

Coil Type = Dual

), make sure that Defrost Pulse Override is set to YES so Defrost Relay #1 does 

not pulse during a defrost cycle (go to 

Settings →Equipment→Def. Pulse Overr.

 and make sure it is set to YES).

If the heaters are verified to be working properly, proceed to verify defrost cycle duration: on the controller display, go to 

Status →Defrost→Last Defr. Time

.  Also, force a defrost and wait for it to finish to take note of the duration.  Center Mount 

Evaporators typically need between 20 to 30 minutes defrost duration to clear the ice.  If the defrost cycle is too short, the 
Defrost Termination Temperature (

Def. Term. Temp

)and Runtime Until Defrost (

Def. Cmp. Run Time

)  can be adjusted as 

needed in 

Settings→Equipment

.  If the unit already has some ice built up in the coil, it may take several defrost cycles to clear 

the ice after the parameters mentioned above are adjusted.

Compressor could be shutting down 
intermittently.

Verify that the correct refrigerant is selected.

Door is open.

Suction Temp sensor disconnected (controller will 
alarm; red LED on controller will be blinking), or 
sensor could be malfunctioning/reading erratic 
value.

Suction Pressure transducer disconnected 
(controller will alarm; red LED on controller will be 
blinking), or transducer could be malfunctioning.

9

10

Suction line at compressor is icing up 
excessively.

System could be undercharged/leak present in the 
system.

12

Evaporator coil is icing up (Center Mount 
FREEZER, electric defrost).

Unit is cooling but Space Temp never 
reaches setpoint.

Verify that heaters are working when controller 
goes into defrost.

Verify duration of defrost cycle/runtime between 
defrosts.

Door is being left open.

11

Evaporator coil is icing up (Low Profile 
FREEZER, electric defrost)

Verify EXV is functioning properly, closing 
completely for pumpdown.

Verify Evap Temp 1 and Evap Temp 2 sensor 
locations.

Verify Defrost Pulse Override is set to YES.

Door is being left open.

Verify that heaters are working when controller 
goes into defrost.

Verify duration of defrost cycle/runtime between 
defrosts.

Problem

Possible Cause

Page 2 of 4

Summary of Contents for HTPG EcoNet Series

Page 1: ...Unit Coolers Troubleshooting Guide 3885 Crestwood Pkwy Ste 500 Duluth Georgia 30096 www htpg com Phone 800 288 9488 256 259 7400 Fax 256 259 7478 A member of the Rheem family of brands HTPG EN TG0821...

Page 2: ...via display under Status Outputs Aux Relay 1 Aux Relay 2 Relay operation for fan speed control is as follows Aux Relay 1 ON Full Speed Aux Relays 1 2 ON Half Speed Aux Relays 1 2 OFF Fans off If dama...

Page 3: ...g properly proceed to verify defrost cycle duration on the controller display go to Status Defrost Last Defr Time Also force a defrost and wait for it to finish to take note of the duration Low Profil...

Page 4: ...Settings System Enable and verify that all the controllers in the group are set to YES Verify software version at each controller on the display by navigating to Service So ware Version Every control...

Page 5: ...ment Network Instance Make sure that communication wires from E1 and E2 terminals at the Command Center mounting bracket are securely connected at the E1 and E2 terminals respectively on the first con...

Page 6: ...art of initial startup of the controller 4 If the valve does not make any noise a Verify connection to the valve is secure and that the 4 pins on the valve are not bent b Verify that the wiring harnes...

Page 7: ...6 With the meter test leads touching pins 1 and 3 when the controller signals that the output to the valve reached the desired position between 35 and 65 visible via Status EXV the meter should read a...

Page 8: ...L MNOL J PI QJ L S NT UV L MI W X YV Y PI QJ L Z L MN NT _ I L aL X I b L c d e g h i j k lV YQL T Nm n L o MI W X YV Y p L T I J S L YoL T I V T L qV T X p I J J rstu v rstu w rstu x y z u y u z e y...

Page 9: ...6 5 0 8 6 6 4 8 9 0 70 2 5 6 6 8 8 9 76 8 6 5 0 8 6 8 9 5 6 5 6 6 5 6 6 8 6 5 6 8 9 MN 8 8 9 5 0 8 8 6 I O O 0 8 6 8 9 P Q R 5 8 6 N4 85 0 5 6 S70 8 2 T 6 8 9 5 5 9 6 4 2 58 5 0 8 0 0 9 8 6 5 P 5 0 8...

Reviews: