Rheem HC-TST402DFMS Series Installation/Configuration Manual Download Page 7

These numbers are approximate and represent operation with a typical system. Actual temperature differentials
and run times may vary widely based on your building and equipment, as well as outdoor temperature conditions.

COMPRESSOR OFF DELAY

Installer table, step 11 is available if the
fossil fuel kit alternative option (PUMP
OFF) is selected.

This item allows a selection of 0 to 99
seconds, which is the time that the compres-
sor will continue to run after the point that
the auxiliary heat is energized.  Running the
compressor after the Auxiliary has started
prevents cool air from creating drafts prior to
the heat exchanger reaching normal tempera-
tures. The factory default value is 0 seconds.
Consult with your equipment’s manufacturer
before increasing this time.

BALANCE POINT TEMPERATURE

Installer table step 12, bPT, is available only
if the fossil fuel kit option is selected and the
outdoor temperature sensor is used (see the
user menu in the owner manual).

This item allows a selection of 5 to 50° F,
which is the outdoor temperature below
which the thermostat will not energize heat
pump compressor stages. It will use
Auxiliary heat stages (only) until the outdoor
temperature raises 3°  above the selected
temperature and then allow compressor
stages to operate. The factory default value
of 35° F is typical for most systems.

BALANCE POINT

Installer table step 13, bP, is available only if
the fossil fuel kit option is selected and the
outdoor temperature sensor is not used. The
Balance Point influences when second stage
comes on. The factory default creates
approximately 1° F between stages. Increas-
ing the setting decreases the separation
between stages. Decreasing the value
increases stage separation. This adjustment
allows a small change in the operation of
your heat pump system versus your auxiliary
system relative to the thermostat adjustment.

PROGRAMMABLE BLOWER
BALANCE POINT

Installer table step 14, bbP, is available only
when configured for Heat Pump systems,
and wired as shown in Fig. 3.

If the system is running a high percentage of
the time due to cold weather conditions, the
output vent air temperature may be cooler
than normal thus creating a drafty room
condition. This feature will reduce the draft
by lowering the blower speed with the DHM
terminal. The lower speed will make the air
temperature slightly warmer and more
comfortable.

Example: If you want the blower to go to a
lower speed when the system is running
greater than 50% of the time,then reduce the
Blower Balance Point to 50%.

To turn this feature OFF, press 

 to 99

then press once more to display OFF.

COMPRESSOR LOCKOUT.

(Installer table step 15). This thermostat is
capable of helping to protect the system
against premature compressor failure by
“locking out” the compressor for at least five
minutes after each cycle. When the thermo-
stat is in compressor lockout, the word
COOL will flash on the display. With heat
pump systems, the word HEAT will flash if
the lockout occurs during a heat cycle.
During this period, the compressor will not
be energized.

Lockout Bypass Option

FOR QUALIFIED SERVICE TECH-
NICIANS’ USE ONLY.
HOMEOWNERS SHOULD NOT USE
THIS FEATURE DUE TO POSSIBIL-
ITY OF EQUIPMENT OR PROP-
ERTY DAMAGE, OR PERSONAL
INJURY.

COMPRESSOR SHORT TERM CYCLE
PROTECTION

If this thermostat has been configured to
provide short-cycle protection, during
the 5-minute lockout period the thermo-
stat will lock out the compressor to allow
head pressure to stabilize. To override
this feature for one cycle while testing

thermostat operation,  press SET 

TIME

and SET 

DAY

 buttons at the same time.

If the system has short-cycle protection, this
item should not need to be enabled. How-
ever, if your system does not have short-
cycle protection,
 turn COMP LOCK ON.
This will protect the compressor from short-
cycling and potential premature compressor
failure.

Note that COMP LOCK OFF permanently
disables compressor lockout. If you need to
temporarily disable compressor lockout,
please see Lockout Bypass Option.

DISABLING AUTOMATIC
CHANGEOVER MODE.

(Installer table step 16). This thermostat, as
configured at the factory, provides automatic
changeover, which allows the thermostat to
switch between heating and cooling to
maintain temperature. In this configuration,
when you press the SYSTEM button, the
thermostat will go through HEAT-OFF-
COOL-AUTO modes (HEAT-EMER-OFF-
COOL-AUTO for heat pumps). Select
HEAT(-EMER)-OFF-COOL to disable the
automatic changeover feature.

HEATING

COOLING

Anticipation Value

Cycle Length  Differential Temperature

Cycle Length Differential Temperature

Shorter

0.4–0.6 F (0.2–0.3 C)

N/A

1–8

N/A

Longer Shorter

9–20

0.6–1.0 F (0.3–0.6 C)

0.6–1.0 F (0.3–0.6 C)

Hydronic Longer

21–40

1.0–1.6 F (0.6–0.9 C)

1.0–1.6 F (0.6–0.9 C)

(Continued)

Pump
Stage

Fossil
Auxiliary
Stage

Decreasing
Indoor
temperature

Higher number
Lower number

Stage separation
1˚F at setting 05

7

Summary of Contents for HC-TST402DFMS Series

Page 1: ...orrect wiring will damage thermostat and could cause personal injury and or property damage Do not use on circuits exceeding specified voltage Higher voltage will damage thermostat and could cause sho...

Page 2: ...from the old thermostat one at a time DO NOT let the wires fall back into the wall Install the new thermostat using the follow ing procedures ATTACH BASE TO WALL Remove packing material from the ther...

Page 3: ...r wiring see CONFIGURATION section for proper thermostat configuration THERMOSTAT TERMINALS Upper L SA SB SC OT Malfunction Light Remote Sense A Remote Sense B Remote Sense C Outdoor Sensor THERMOSTAT...

Page 4: ...OMPRESSOR SYSTEM ONLY If you have a single stage compressor system see the diagram below A relay customer provided should be installed as shown in Fig 5 to switch the fan speed to the next lower speed...

Page 5: ...6 step 6 is for heat pump only These items allow the cycle times in heating cooling and auxiliary heat pump systems only to be increased or decreased The factory set values can be adjusted higher for...

Page 6: ...T COOL and AUTO with SYSTEM button EMER appears in sequence after HEAT if HEAT PUMP is selected Program RUN TIME FWD Heat Pump ONLY TIME FWD TIME FWD TIME FWD TIME FWD TIME FWD TIME FWD TIME FWD 6 SET...

Page 7: ...e slightly warmer and more comfortable Example If you want the blower to go to a lower speed when the system is running greater than 50 of the time then reduce the Blower Balance Point to 50 To turn t...

Page 8: ...service interval SERVICE REMINDER 8 1 Step Press Button s Displayed Press or to select COMMENTS Factory Default PAD TIME OFF Hrs or REM PAD TIME No of Hrs ON or OFF Set Humidifier Maintenance Reminde...

Page 9: ...temperature to call for heat 3 LED indicatior will glow red indicat ing the thermostat is calling for heat 4 Lower the termperature a few degrees below room temperature and the red LED and the heat sh...

Page 10: ...re securely attached 3 Cooling system requires service or Same procedure as diagnostic for No Heat thermostat requires replacement condition except press the SYSTEM button until COOL is displayed and...

Page 11: ...e it will provide precise temperature control on a properly sized system Any time your program is running and you would like to override it for a specific amount of time press or until the temperature...

Page 12: ...357 367 H O M E O H O M E O H O M E O H O M E O H O M E OWNER HELP LINE WNER HELP LINE WNER HELP LINE WNER HELP LINE WNER HELP LINE 1 800 284 2925 1 800 284 2925 1 800 284 2925 1 800 284 2925 1 800 28...

Reviews: