Rheem HC-TST402DFMS Series Installation/Configuration Manual Download Page 4

RESET SWITCH

See the Troubleshooting section at the end
of this document for more information about
the function of this switch.

E2/P SWITCH (DHM) TERMINAL
FUNCTION

The E2/P switch is located on the back of
the thermostat body (see fig. 2). This switch
controls how the DHM terminal will be
energized.

1. In the P position (up) the DHM terminal
will be energized on a call for dehumidifica-
tion.

2. In the E2 position (down) the DHM terminal
will always be energized except on a call for
dehumidification. The switch must be in the E2
position on some electronically controlled
variable speed blower systems.

Figure 2. Switch locations on back of thermostat body

CONFIGURATION

1

2

P

E2

S18

S19

1

Reset switch

E2/P switch

2

SWITCHES

HM

R

I

R

Humidifier

System

120 VAC

24 VAC

NEUTRAL

HOT

120 VAC

NEUTRAL

HOT

TRANSFORMER

Typical Wiring for 120V Humidifier System

HM

R

I

Humidifier

System

120 VAC

24 VAC

NEUTRAL

HOT

TRANSFORMER

Typical Wiring for 24V Humidifier System

Figure 4. Typical Wiring for 120V Humidifier System

Figure 5. Typical Wiring for 24V Humidifier System

Figure 3. Typical Wiring for Dehumidifier System

DEHUMIDIFICATION WIRING WITHOUT AN ELECTRONICALLY CONTROLLED VARIABLE SPEED BLOWER SYSTEM

FOR SINGLE STAGE COMPRESSOR SYSTEM ONLY

If you have a single stage compressor system see the diagram below.

 

A relay (customer provided) should be installed as shown in Fig. 5 to

switch the fan speed to the next lower speed on a call for dehumidification from the thermostat. The reduction in air flow allows the coil to remove
more humidity from the air. The relay should be rated for blower motor load. Since this configuration reduces the air flow in cooling, the anti-
freeze-up control (White-Rodgers CAFC) or equivalent is recommended. The CAFC prevents the air conditioning coil from freezing due to low
air flow, dirty filters, low refrigerant pressure, etc. The CAFC snaps onto the suction line close to the evaporator coil as possible and breaks
the compressor circuit when the suction line drops below 38

°

F and re-make the circuit at 46

°

F.

NOTE: If you have a two stage compressor, the thermostat software will lengthen cycle times for the first stage of cool. The longer cycles will
improve dehumidification while cooling, allowing the DHM terminal not to be used on a two stage compressor system.

24 V

A

C

Hea

t F

an Speed

Cool F

an Speed

LOW

DHM

C

R

G

HI

GH

MED. HI

GH

N.O.

N.C.

3-4 speed
Blower
Motor

COMMON

Y1

Furnace
Control
Module

Customer supplied relay
rated for blower motor load

E2

P

120 VAC

NEUTRAL

TRANSFORMER

HOT

Selecting P - DHM Energized on call for

Dehumidification

Selecting E2 - DHM Deenergized on call for

Dehumidification

4

Summary of Contents for HC-TST402DFMS Series

Page 1: ...orrect wiring will damage thermostat and could cause personal injury and or property damage Do not use on circuits exceeding specified voltage Higher voltage will damage thermostat and could cause sho...

Page 2: ...from the old thermostat one at a time DO NOT let the wires fall back into the wall Install the new thermostat using the follow ing procedures ATTACH BASE TO WALL Remove packing material from the ther...

Page 3: ...r wiring see CONFIGURATION section for proper thermostat configuration THERMOSTAT TERMINALS Upper L SA SB SC OT Malfunction Light Remote Sense A Remote Sense B Remote Sense C Outdoor Sensor THERMOSTAT...

Page 4: ...OMPRESSOR SYSTEM ONLY If you have a single stage compressor system see the diagram below A relay customer provided should be installed as shown in Fig 5 to switch the fan speed to the next lower speed...

Page 5: ...6 step 6 is for heat pump only These items allow the cycle times in heating cooling and auxiliary heat pump systems only to be increased or decreased The factory set values can be adjusted higher for...

Page 6: ...T COOL and AUTO with SYSTEM button EMER appears in sequence after HEAT if HEAT PUMP is selected Program RUN TIME FWD Heat Pump ONLY TIME FWD TIME FWD TIME FWD TIME FWD TIME FWD TIME FWD TIME FWD 6 SET...

Page 7: ...e slightly warmer and more comfortable Example If you want the blower to go to a lower speed when the system is running greater than 50 of the time then reduce the Blower Balance Point to 50 To turn t...

Page 8: ...service interval SERVICE REMINDER 8 1 Step Press Button s Displayed Press or to select COMMENTS Factory Default PAD TIME OFF Hrs or REM PAD TIME No of Hrs ON or OFF Set Humidifier Maintenance Reminde...

Page 9: ...temperature to call for heat 3 LED indicatior will glow red indicat ing the thermostat is calling for heat 4 Lower the termperature a few degrees below room temperature and the red LED and the heat sh...

Page 10: ...re securely attached 3 Cooling system requires service or Same procedure as diagnostic for No Heat thermostat requires replacement condition except press the SYSTEM button until COOL is displayed and...

Page 11: ...e it will provide precise temperature control on a properly sized system Any time your program is running and you would like to override it for a specific amount of time press or until the temperature...

Page 12: ...357 367 H O M E O H O M E O H O M E O H O M E O H O M E OWNER HELP LINE WNER HELP LINE WNER HELP LINE WNER HELP LINE WNER HELP LINE 1 800 284 2925 1 800 284 2925 1 800 284 2925 1 800 284 2925 1 800 28...

Reviews: