EON Field Replacement Kit 

EON Control for Replacing ECM 2.3 or EON motor Control 

 
 
10.

 

Place the two 2.76-inch bolts into the holes at the base of 

the new EON control and tighten down to a torque 
measurement of 15-19 inch pounds.  

 
11.

 

Reattach the 5-pin power cable and 16-pin signal cable into 

the unit connector.  

 

Installing connectors 

incorrectly may result in failure of control module. Rotate 
the motor assembly to insure plug is in correct location to 
match original location. 

 
12.

 

Discard the shorter set of bolts. 

 

Replacing an EON control:                           

 
13.

 

Two sets of bolts are included in the kit. When                 

replacing the EON, use the 2.45-inch bolts (shorter set). The 
longer bolts and adapter ring are not used 
         

14.

 

Attach the 3-pin connector from motor to corresponding 

connector on the new EON control (see Figure 2a). 

 
15.

 

Align motor endshield to top of new EON control. Align 

notch in motor endshield with tab on connector (see Figure 
6). 
 

          

 

 

                 Figure 6:

 Motor endshield on control 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

16.

 

Place control onto the existing motor. (see Figure 7). 

  

         

   

 

                    Figure 7:

 Motor and control mated 

 
 

17.

 

Place two 2.45-inch bolts into the holes at the base of the 

new EON control and tighten down to a torque 
measurement of 15-19 inch pounds.  

 
18.

 

Reattach the 5-pin power cable and 16-pin signal cable into 

the unit connector.  

 

Installing connectors 

incorrectly may result in failure of control module. 

 
19.    Discard the longest set of bolts and adapter ring.  
  
 
 

Reviews: