![Rheem ECONET RP2024BJVCA Installation Instructions Manual Download Page 35](http://html1.mh-extra.com/html/rheem/econet-rp2024bjvca/econet-rp2024bjvca_installation-instructions-manual_1451480035.webp)
35
Components
7.5 EcoNet
™
Variable Speed Outdoor Control (VSODC) (cont.)
7.5.2 TEST and SW2 Buttons
TEST and SW2 buttons are used to enter the
following menus and modes:
• Test mode
• Forced Defrost
• Fault Code Recall Menu
• Compressor Speed Menu
• Superheat Menu
7.5.3 Memory Card
• The memory card stores all unit information.
• The unit information is called model data.
• The model data is all the information needed for
proper unit operation of that specific model.
7.5.4 Factory Superheat Setting
The VSODC is pre-programmed with the optimum
superheat setting of 6º for each outdoor unit.
7.0 COMPONENTS & CONTROLS
7.5.5 Superheat Offset DIP Switch Settings
(DIP Switch Bank on the Right)
Although the factory programmed superheat
setting is considered to be the most efficient
setting for each unit, installation conditions can
effect the measurement of superheat on the
VSODC. For this reason the following dip switch
settings have been provided to enable flexibility for
various installation conditions.
Outdoor Unit
Superheat
(°F)
Dipswitch Settings
1
2
(-‐)P1724
6
Off
Off
(-‐)P1736
6
Off
Off
(-‐)P1748
6
Off
Off
(-‐)P1760
8
Off
Off
Superheat
Offset Selection
Profile
Off Set from
Programmed
Setting (°F)
A
0
B
-‐4
C
-‐2
D
+2
7.5.6 Defrost Termination Temperature DIP Switches
(DIP Switch Bank on the Left)
Off
On
Off
On
Off
Off
On
On
60
º
F [15.6
º
C]
50
º
F [10
º
C]
40
º
F [4.4
º
C]
70
º
F [21.1
º
C]