Tubing
4.0 INSTALLATION
4.4.2.5 Oil Level Adjustments for
Long Line Set Applications
Additional oil will need to be added if refrigerant is
added during installation. Below is the equation for
the oil level adjustment and the compressor name
plate oil charge for the different outdoor units.
Oil to be Added = [(Charge Adju OD
Unit Name Plate Refrigerant Charge (oz.)) ×
(0.022) – [(0.10) × (Compressor Name Plate Oil
Charge (oz.))]
Example:
An application requires 125ft of line set
with a liquid line diameter of 3/8”, Charge Adjust-
ment = 66 oz., Name Plate Charge = 212 oz.,
Name Plate Oil Charge = 40 oz., Oil to be Added =
((66 oz. + 212 oz.) × .022) – (.10 × 40 oz.) = 2 oz.
4.4.2.6 Capacity Losses
Long line lengths can result in a reduction in
capacity due to vapor line pressure drop and heat
gain or loss. Refer to Table 2 for capacity loss
multipliers for various vapor line diameters and
equipment line lengths. This table does not ac-
count for any capacity loss due to heat gain or loss
from the environment. It is extremely important
not to oversize the vapor line to minimize capacity
loss at the expense of proper oil return. If the table
shows an “NR” for a particular vapor line diameter
and length, or, if a vapor line diameter is not listed,
oil return will not be adequate.
2'0RGHO
&RPSUHVVRU
1DPHSODWH2LO
&KDUJHR]
3
=39(=(
3
=39(=(
3
3
=39&((
ƋƵŝǀĂůĞŶƚ>ĞŶŐƚŚĨŽƌ&ŝƚƚŝŶŐƐ͗Ĩƚŵ
>ŝŶĞ^ŝnjĞ
ŝŶŵŵ
ϵϬΣ^ŚŽƌƚ
ZĂĚŝƵƐ
ůďŽǁ
ϵϬΣ>ŽŶŐ
ZĂĚŝƵƐ
ůďŽǁ
ϰϱΣ
ůďŽǁ
^ŽůĞŶŽŝĚ
sĂůǀĞ
ŚĞĐŬ
sĂůǀĞ
^ŝŐŚƚ
'ůĂƐƐ
&ŝůƚĞƌ
ƌLJĞƌ
ϯͬϴϵ͘ϱϯ
ϭ͘ϯϬ͘ϰϬ
Ϭ͘ϴϬ͘Ϯϰ Ϭ͘ϯϬ͘Ϭϵ
ϲϭ͘ϴϯ
ϰϭ͘ϮϮ
Ϭ͘ϰϬ͘ϭϮ ϲϭ͘ϴϯ
ϭͬϮϭϮ͘ϳϭ
ϭ͘ϰϬ͘ϰϯ
Ϭ͘ϵϬ͘Ϯϳ Ϭ͘ϰϬ͘ϭϮ
ϵϮ͘ϳϰ
ϱϭ͘ϱϮ
Ϭ͘ϲϬ͘ϭϴ ϲϭ͘ϴϯ
ϱͬϴϭϱ͘ϴϴ
ϭ͘ϱϬ͘ϰϲ
ϭϬ͘ϯϬ
Ϭ͘ϱϬ͘ϭϱ
ϭϮϯ͘ϲϲ
ϲϭ͘ϴϯ
Ϭ͘ϴϬ͘Ϯϰ ϲϭ͘ϴϯ
ϯͬϰϭϵ͘Ϭϱ
ϭ͘ϵϬ͘ϱϴ
ϭ͘ϯϬ͘ϰϬ Ϭ͘ϲϬ͘ϭϴ
ϭϰϰ͘Ϯϳ
ϳϮ͘ϭϯ
Ϭ͘ϵϬ͘Ϯϳ ϲϭ͘ϴϯ
ϳͬϴϮϮ͘Ϯϯ
Ϯ͘ϯϬ͘ϳϬ
ϭ͘ϱϬ͘ϰϲ Ϭ͘ϳϬ͘Ϯϭ
ϭϱϰ͘ϱϳ
ϴϮ͘ϰϰ
ϭϬ͘ϯϬ
ϲϭ͘ϴϯ
ϭͲϭͬϴϮϴ͘ϱϴ Ϯ͘ϳϬ͘ϴϮ
ϭ͘ϴϬ͘ϱϱ Ϭ͘ϵϬ͘Ϯϳ
ϮϮϲ͘ϳϭ
ϭϮϯ͘ϲϲ
ϭ͘ϱϬ͘ϰϲ ϲϭ͘ϴϯ
Table 1
Refrigerant tubing is measured in terms of actual
length and equivalent length. Actual length is used
for refrigerant charge applications. Equivalent
length takes into account pressure losses from
tubing length, fittings, vertical separation, acces-
sories, and filter dryers. The table below references
different commonly used equivalent lengths.
4.4.3 Line Set Length and Fitting Losses