NOTICE: This guide recommends minimum branch circuit sizing and wire size based on National Electric Code. 

Refer to wiring diagrams in this manual for field wiring connections.

Branch Circuit Sizing and Wire Size Guide

CAUTION: The presence 

of water in the piping 

and water heater does 

not provide sufficient 

conduction for a ground. 

Non-metallic piping, 

dielectric unions, flexible 

connectors etc. can cause 

the water heater to be 

electrically isolated.

Electrical Connections

A separate branch circuit with copper 

conductors, overcurrent protective device 

and suitable disconnecting means must be 

provided by a qualified electrician. 
All wiring must conform to local codes or 

latest edition of National Electrical Code 

ANSI/NFPA 70.
The water heater is completely wired to 

the junction box inside jacket at the top 

front of the water heater. An opening for 

1/2

 or 3/4

 electrical fitting is provided 

for field wiring connections.
The voltage requirements and wattage 

load for the water heater are specified  

on the rating plate on the front of the 

water heater. 

The branch circuit wiring should include either:

   

Metallic conduit or metallic sheathed 

cable approved for use as a 

grounding conductor and installed 

with fittings approved for the 

purpose.

   Non-metallic sheathed cable, metallic 

conduit or metallic sheathed cable 

not approved for use as a ground 

conductor shall include a separate 

conductor for grounding. It should be 

attached to the ground terminals of 

the water heater and the electrical 

distribution box.

Water heater junction box.

WARNING

WARNING

Junction  

box cover

Wire connections

Ground screw

Conduit 

connector

Single Phase

Wiring

Total Water 

Heater Wattage

Recommended Over Current Protection 

(fuse or circuit breaker amperage rating)

Copper Wire Size AWG Based 

on N.E.C Table 310-16 (75

o

C)

208V

240V

208V

240V

3,000

20

20

12

12

4,000

25

25

10

10

4,500

30

25

10

10

5,000

30

30

10

10

5,500

35

30

8

10

!

Summary of Contents for AP16697

Page 1: ...you do not understand these instructions or any terms within it seek professional advice Any questions regarding the operation maintenance service or warranty of this water heater should be directed t...

Page 2: ...nswers to common problems in the Before You Call For Service section If you review our chart of Troubleshooting Tips first you may not need to call for service at all READ THIS MANUAL Your safety and...

Page 3: ...control operation section of this manual DANGER Hotter water increases the potential for Hot Water SCALDS D A N G E R HOT Water temperature over 125 F can cause severe burns instantly or death from sc...

Page 4: ...with generic earthquake bracing instructions can be obtained from Office of the State Architect 400 P Street Sacramento CA 95814 or you may call 916 324 5315 or ask a water heater dealer However appl...

Page 5: ...nderneath the water heater is strong enough to sufficiently support the weight of the water heater once it is filled with water CAUTION The water heater should not be located in an area where leakage...

Page 6: ...nsion tank in the cold water line between the water heater and the check valve refer to the illustration below The expansion tank is designed with an air cushion built in that compresses as the system...

Page 7: ...t pitch downward from the valve to allow complete drainage by gravity of the relief valve and discharge line The end of the discharge line should not be threaded or concealed and should be protected f...

Page 8: ...n opening for 1 2 or 3 4 electrical fitting is provided for field wiring connections The voltage requirements and wattage load for the water heater are specified on the rating plate on the front of th...

Page 9: ...manufacturer into onto or in conjunction with the water heater The use of unauthorized energy saving devices may shorten the life of the water heater and may endanger life and property The manufacture...

Page 10: ...and cold water inlet openings NOTICE Do not apply heat to the HOT or COLD water connections If sweat connections are used sweat tubing to adapter before fitting adapter to the water connections on hea...

Page 11: ...Air purged from water heater and piping Water connections tight and free of leaks Temperature and Pressure Relief Valve properly installed and discharge line run to open drain Discharge line protected...

Page 12: ...smoke or use an open flame near the faucet at the time it is open Safety Controls The water heater is equipped with a temperature sensor and temperature limiting control ECO that is located above the...

Page 13: ...heater s thermostat s The lower the temperature setting the greater the savings in energy and operating costs To comply with safety regulations the electronic control is factory programmed at 120 F or...

Page 14: ...the On O button for 3 seconds to turn the water heater On Reduce Water Temperature Press DOWN arrow until desired temperature is shown on display Increase Water Temperature Press UP arrow until desire...

Page 15: ...d press any button and release to brighten the display before performing desired action Press and hold the VACATION button for 3 seconds to place the water heater in vacation mode This mode will reduc...

Page 16: ...The MODE menu is used to change the water heater from PERFORMANCE mode to ENERGY SAVER mode Use DOWN arrow to change the mode The CONFIGURE menu is used to change additional settings for the water hea...

Page 17: ...ion Display mode is used to change the temperature displayed from Fahrenheit to Celsius Press the UP and DOWN arrow at the same time to change Beep mode is use to turn all the audible alarms on and o...

Page 18: ...erature reading for that sensor History menu lists the 10 most recent error codes Use the DOWN arrow to scroll the codes ERROR DISPLAY ERROR SYMBOL History menu lists the 10 most recent error codes Pr...

Page 19: ...r element or associated wiring and connections Please call for service A106 Upper element error Electronic control has detected an error with the upper element or associated wiring and connections Ple...

Page 20: ...andle on the temperature pressure relief valve located near the top of the water heater to make certain the valve operates freely Allow several gallons to flush through the discharge line to an open d...

Page 21: ...on NOTICE Refer to the Hydrogen Gas Caution in the Operating Instructions Anode Rod This water heater is equipped with an anode rod designed to prolong the life of the glass lined tank The anode rod i...

Page 22: ...Not enough or no hot water Water usage may have exceeded the capacity of the water heater Wait for the water heater to recover after an abnormal demand A fuse is blown or a circuit breaker tripped Re...

Page 23: ...ing thermostat s heating elements or other operating controls Refer repairs to qualified service personnel TURN OFF POW ER BEFO RE SERV ICING Some models may have been supplied with External heat trap...

Page 24: ...ronic control and insulation Rotate the crossbar up and down until it breaks away from the remainder of the cavity insert See illustration to the left Discard the crossbar It cannot and need not be re...

Page 25: ...25 Wiring Diagram This water heater is wired as indicated in the schematic below Use only a 2 wire power feed with ground connection for this water heater...

Page 26: ...26 Notes...

Page 27: ...27 Notes...

Page 28: ...act the Manufacturer s National Service Department at the following address 1241 Carwood Court Montgomery Alabama 36117 Phone 1 866 279 4566 When contacting the manufacturer the following information...

Reviews: