VENT DAMPER
NORMAL OPERATION SUMMARY
For safe, efficient operation, the vent damper and all
flue product carrying areas of the appliance must be
checked annually, with particular attention given to dete-
rioration from corrosion or other sources. Check vent
damper operation as follows:
1. When the furnace or heater is off, check that the vent
damper position indicator points to the closed posi-
tion, Fig. 4.
2. Turn the thermostat or controller up to call for heat
and check that the vent damper indicator points to
the open position, Fig. 4.
3. Turn the thermostat or controller down again and
check that the vent damper position indicator re-
turns to the closed position.
DAMPER OPEN DAMPER CLOSED
FIG.4-VENT DAMPER POSITION INDICATOR
SHOWING OPEN & CLOSED POSITIONS.
MOUNTING
On vertical vents, the vent damper may be mounted with the actuator in any position. On horizontal vents, do
not mount the actuator either directly above or directly below the vent pipe; mount the vent damper actuator to the
side of the vent.
The vent damper is set up for a continuous pilot system. If the vent damper is installed on an intermittent Pilot
or Direct Spark Ignition equipped system, the energy savings of the vent damper can be improved by plugging the
hole in the vent damper blade using the knockout plug, Part No 105612R, provided in the parts envelope.
DO NOT plug the hole if installing the vent damper on a continuous pilot system as this will create a hazardous
condition.
THE VENT DAMPER MUST BE INSPECTED AT LEAST
ONCE A YEAR BY A TRAINED, EXPERIENCED SER-
VICE TECHNICIAN.. THE NAME OF THE PERSON
WHO ORIGINALLY INSTALLED YOUR VENT DAMPER
IS SHOWN ON THE INSTALLATION LABEL. DAMPER
MUST BE IN OPEN POSITION WHEN HEATER MAIN
BURNERS ARE OPERATING.
INSTALLING THE VENT DAMPER IN HORIZONTAL &
VERTICAL VENTS.
D80B GENERAL WIRING DIAGRAM
INSTALL THE VENT DAMPER TO SERVICE ONLY THE SINGLE APPLIANCE FOR WHICH IT IS INTENDED. IF
IMPROPERLY INSTALLED, A HAZARDOUS CONDITION, SUCH AS AN EXPLOSION OR CARBON MONOXIDE
POISONING, COULD RESULT.
17
Damper position
indicator
Summary of Contents for 136-1826
Page 5: ...5...
Page 39: ...WIRING DIAGRAM KEY 39...
Page 40: ...WIRING DIAGRAMS WIRING DIAGRAM MODELS 136 264 WITH ENERGY PUMP SAVING CONTROL Fig 2288e 40...
Page 41: ...WIRING DIAGRAM MODELS 331 399 Fig 1930e WIRING DIAGRAM MODELS 512 627 Fig 1924e 41...
Page 42: ...WIRINGDIAGRAMMODELS512 726 WIRING DIAGRAM MODELS 726 825 Fig 2194e Fig 2297e 42...
Page 43: ...WIRING DIAGRAM MODEL 825 1826 Fig 1967e WIRING DIAGRAM MODELS 962 1826 43...
Page 44: ...MODEL136GBONLY REPLACEMENT PARTS LISTS 44...
Page 45: ...MODEL136GBONLY 45...
Page 46: ...MODELS 181 264 331 399 GB 46...
Page 47: ...47...
Page 48: ...MODELS 181 264 331 399 GB 48...
Page 49: ...49 MODELS 181 264 331 339 GB...
Page 50: ...MODELS 512 627 726 825 GB 50...
Page 51: ...MODELS 512 627 726 825 GB 51...
Page 52: ...MODELS 512 627 726 825 GB 52...
Page 53: ...MODELS926 1826GB 53...
Page 54: ...MODELS926 1826GB 54...