9
3. Connect the furnace to the supply
air plenum.
4. Secure the four angle brackets
shipped with the unit to the return air
opening. See Figure 5. Connect the
return air ducting to the return air
opening at the top of the unit. Make
the connection air tight to prevent
entraining combustion gases from
an adjacent fuel-burning appliance.
5.
Be sure to have adequate space
for the unit filter.
NOTE:
DO NOT take return air from
bathrooms, kitchens, furnace rooms,
garages, utility or laundry rooms, or
cold areas.
FIGURE 5
HORIZONTAL RETURN AIR DUCT
FIGURE 6
AIR FROM HEATED SPACE
THIS FURNACE AND ANY OTHER
FUEL-BURNING APPLIANCE MUST
BE PROVIDED WITH ENOUGH
FRESH AIR FOR PROPER
COMBUSTION AND VENTILATION
OF THE FLUE GASES. MOST
HOMES WILL REQUIRE THAT
OUTSIDE AIR BE SUPPLIED INTO
THE FURNACE AREA. FAILURE TO
DO SO CAN CAUSE DEATH FROM
CARBON MONOXIDE POISONING.
Adequate facilities for providing air for
combustion and ventilation must be
provided in accordance with section
5.3, Air for Combustion and Ventilation,
of the National Fuel Gas Code, ANSI,
Z223.1 latest edition or CAN/CGA
B149.1 and .2 or, applicable provisions
for the local building codes, and not
obstructed so as to prevent the flow of
air to the furnace.
IMPORTANT:
Air for combustion and
ventilation must not come from a
corrosive atmosphere. Any failure due
to corrosive elements in the
atmosphere is excluded from warranty
coverage.
The following types of installation may
require OUTDOOR AIR for
combustion, due to chemical
exposures:
• Commercial buildings
• Buildings with indoor pools
• Furnaces installed in laundry rooms
• Furnaces in hobby or craft rooms
• Furnaces installed near chemical
storage areas.
Exposure to the following substances
in the combustion air supply may also
require OUTDOOR AIR for
combustion:
• Permanent wave solutions
• Chlorinated waxes and cleaners
• Chlorine-based swimming pool
chemicals
• Water softening chemicals
COMBUSTION AND VENTILATION AIR
WARNING
!
FOUR ANGLE BRACKETS ARE SHIPPED WITH EACH
UNIT THAT CAN BE INSTALLED HORIZONTALLY. THESE
BRACKETS MAY BE USED TO SECURE THE RETURN
AIR DUCT TO A HORIZONTAL UNIT.
• De-icing salts or chemicals
• Carbon tetrachloride
• Halogen type refrigerants
• Cleaning solvents (such as
perchloroethylene)
• Printing inks, paint removers,
varnishes, etc.
• Hydrochloric acid
• Cements and glues
• Antistatic fabric softeners for clothes
dryers
• Masonry acid washing materials
Summary of Contents for 1x2000
Page 20: ...20 FIGURE 16 UTEC NO 1095 100 CONTROL BOARD TWINNING CONNECTION SINGLE STAGE OPERATION I685 ...
Page 21: ...21 FIGURE 17 UTEC NO 1095 100 CONTROL BOARD TWINNING CONNECTION TWO STAGE OPERATION I684 ...
Page 29: ...29 FIGURE 25 FILTER RETAINING RODS SIDE RETURN FIGURE 26 DOWNFLOW FILTER INSTALLATION ...
Page 31: ... FIGURE 27 INTEGRATED FURNACE CONTROL IFC TROUBLESHOOTING GUIDE FOR UTEC 1095 101 31 ...
Page 32: ...32 ...
Page 33: ... FIGURE 28 UTEC 1095 101 INTEGRATED FURNACE CONTROL 33 ...
Page 34: ...34 ...
Page 35: ...35 ...
Page 36: ...36 CM 599 Rheem Manufacturing Company Air Conditioning Division Fort Smith Arkansas ...