Reznor XBWS11 Installation Instructions Manual Download Page 13

PAGE 13

Mist Elimi na tor Fil ter in In take Hood (5HP)

Ex ter nal Static Pres sure (in wa ter)

0

0.25

0.5

0.75

1

1.25

1.5

CFM

4600

815

900

975

1045

1085

1125

1175

5000

880

940

1015

1060

1135

1175

1215

5400

915

975

1045

1125

1150

1195

1250

5800

975

1045

1085

1175

1250

1260

N/A

6200

1000

1075

1165

1200

N/A

N/A

N/A

Ba ro met ric Hood, 2" Pleated Fil ters (5HP)

Ex ter nal Static Pres sure (in wa ter)

0

0.25

0.5

0.75

1

1.25

1.5

CFM

4600

825

915

1000

1025

1100

1140

1170

5000

890

975

1025

1100

1140

1170

1240

5400

925

1000

1085

1140

1170

1240

1280

5800

975

1025

1140

1170

1240

N/A

N/A

6200

1025

1120

1170

N/A

N/A

N/A

N/A

SUP PLY

Blower RPM for XBWS62 w/AQ21

EXHAUST

Notes:
1. Drive losses included in the above tables.
2. Performance can vary depending on ambient conditions.
3. Blower RPMs are for reference only.

RPM Range

Low

820- 1000

Stan dard  Unit

Me dium

1000- 1200

Op tional  Kit

High

1175- 1375

Op tional  Kit

SUP PLY

Blower RPM for XBWS46 w/AQ21

EXHAUST

Notes:
1. Drive losses included in the above tables.
2. Performance can vary depending on ambient conditions.
3. Blower RPMs are for reference only.

RPM Range

Low

780- 1020

Stan dard  Unit

Me dium

1000- 1315

Op tional  Kit

High

1315- 1700

Op tional  Kit

Mist Elimi na tor Fil ter in In take Hood (5HP)

Ex ter nal Static Pres sure (in wa ter)

0

0.25

0.5

0.75

1

1.25

1.5

CFM

3000

900

1030

1100

1165

1240

1285

1350

3400

975

1085

1175

1240

1290

1350

1400

3800

1070

1175

1240

1290

1350

1400

1465

4200

1165

1240

1320

1350

1430

1465

1515

4600

1240

1320

1375

1430

1500

1515

1580

Ba ro met ric Hood, 2" Pleated Fil ters (5HP)

Ex ter nal Static Pres sure (in wa ter)

0

0.25

0.5

0.75

1

1.25

1.5

CFM

3000

955

1100

1160

1245

1280

1360

1425

3400

1055

1185

1245

1300

1375

1425

1480

3800

1160

1300

1360

1400

1425

1530

1585

4200

1245

1375

1450

1480

1500

1585

1650

4600

1360

1450

1500

1585

1600

1650

1700

Summary of Contents for XBWS11

Page 1: ...el mode is accomplished by two blowers providing continuous exhaust of stale indoor air and replacement by equal amount of outdoor air Energy recovery is achieved by slowly rotating the energy recovery wheel within the cassette frame work In winter the ERV adsorbs heat and moisture from the exhaust air stream during one half of a complete rotation and gives them back to the cold drier intake air s...

Page 2: ...ons 8 Refer to the unit nameplate for minimum circuit ampacity MCA and maximum overcurrent protection size fuse 9 Electrical data is listed on unit rating plate and motor name plates 10 Connect line voltage power supply to ERV fuse block in control box of unit from disconnect switch See wiring diagram 11 Ground unit with a suitable ground connection either through unit supply wiring or an earth gr...

Page 3: ...it is constantly rotating when in the air stream the ERV is always being cleaned by air first in one direction then the other Because it is always dry dust or other particles impinging on the surface during one half cycle are readily removed during the next half cycle During the heating season when outdoor air temperatures are below 15o F it is recommended to use the optional low ambient kit field...

Page 4: ... adjusted to tension the belt If using a belt tension checker adjust the span to the appropriate setting and check the belt defection force The belt deflection force should be between 5 8 lbs or the lowest tension at which the belt will not slip under peak load conditions 5 Disconnect main power to unit before making adjustment to economizer and or ERV unit 6 Replace ERV control access cover 7 Set...

Page 5: ...factory at the low static setting Pulley kits are available for the medium and high static settings To install a pulley kit 1 Check content of pulley kit if pulley kit contains A An adjustable sheave and a fixed pitch pulley then remove belt and both motor and blower pulley B An adjustable sheave then remove the motor pulley C A fixed pitch pulley then remove the blower pulley 2 Replace pulley s w...

Page 6: ...2 A B C D E F G H I J J 4 K EXHAUST RETURN FRESH AIR SUPPLY EXHAUST RETURN DUCT FIELD SUPPLIED FRESH AIR SUPPLY DUCT FIELD SUPPLIED EXHAUST HOOD FRESH AIR HOOD ERV Data Dimensional Data Size CFM Range Duct Size G x J ERV Roof Curb A B C D E F G H I J K 11 300 1100 17 00 x 11 38 44 75 32 13 33 50 11 00 43 00 39 00 17 50 30 25 26 25 11 88 2 50 20 1200 2000 21 88 x 14 00 54 36 37 25 37 50 17 50 52 75...

Page 7: ... J50 Jack Control Box Wheel J51 Jack Control Box Exhaust Air J56 Jack Control Box Damper J148 Jack Fresh Air Motor Harness J150 Jack Wheel Motor Harness J151 Jack Exhaust Air Motor Harness J160 Jack Damper Motor Harness K94 Relay On Off Optional K163 Contactor Exhaust Air Motor K164 Contactor Fresh Air Motor P33 Plug Cycle Control Optional P34 Plug Cycle Control Harness Optional P40 Plug Wheel Cyc...

Page 8: ...ove jumper to install field optional low ambient switch 2 Selective voltage terminals for proper unit voltage 3 Optional low ambient switch 4 Optional motorized intake damper 5 Optional Stop Start and Jog Control 6 For energy management systems connect 24v to G and common 24v to C ...

Page 9: ... Control Box Damper J148 Jack Fresh Air Motor Harness J150 Jack Wheel Motor Harness J151 Jack Exhaust Air Motor Harness J152 Jack Transformer High Voltage J160 Jack Damper Motor Harness K94 Relay On Off Optional K163 Contactor Exhaust Air Motor K164 Contactor Fresh Air Motor P33 Plug Cycle Control Optional P34 Plug Cycle Control Harness Optional P40 Plug Wheel Cycle Optional P48 Plug Fresh Air Mot...

Page 10: ...ield optional low ambient switch 2 Step down transformer assembly for 460 575 volt units 3 Selective voltage terminals for proper unit voltage 4 Optional low ambient switch 5 Optional motorized intake damper 6 Optional Stop Start and Jog Control 7 For energy management systems connect 24v to G and common 24v to C ...

Page 11: ...r reference only RPM Range Low 1000 1300 Standard Unit Medium 1300 1700 Optional Kit High 1700 2080 Optional Kit SUPPLY Blower RPM for XBWS11 w AQ21 EXHAUST Notes 1 Drive losses included in the above tables 2 Performance can vary depending on ambient conditions 3 Blower RPMs are for reference only RPM Range Low 1000 1300 Standard Unit Medium 1300 1700 Optional Kit High 1750 2200 Optional Kit Barom...

Page 12: ...UST RPM Range Low 750 975 Standard Unit Medium 1008 1314 Optional Kit High 1311 1708 Optional Kit Mist Eliminator Filter in Intake Hood 3HP External Static Pressure in water 0 0 25 0 5 0 75 1 1 25 1 5 CFM 1200 N A 790 960 1110 1210 1315 1380 1600 750 900 1005 1145 1230 1365 1410 2000 900 1005 1105 1210 1275 1400 1450 2400 1005 1125 1210 1275 1365 1450 1500 2800 1125 1230 1315 1380 1450 1535 1600 B...

Page 13: ...RPM Range Low 820 1000 Standard Unit Medium 1000 1200 Optional Kit High 1175 1375 Optional Kit SUPPLY Blower RPM for XBWS46 w AQ21 EXHAUST Notes 1 Drive losses included in the above tables 2 Performance can vary depending on ambient conditions 3 Blower RPMs are for reference only RPM Range Low 780 1020 Standard Unit Medium 1000 1315 Optional Kit High 1315 1700 Optional Kit Mist Eliminator Filter i...

Page 14: ...695 1901 www RezSpec com 2004 Thomas Betts Corp All rights reserved Printed in U S A Reznor is registered in at least the United States All other marks are the property of their respective organizations Notes ...