Form CP-OPT-GMK (6-16), P/N 208831 R3, Page 2

Instructions

1. 

Turn off the gas supply at the shutoff valve upstream of the combination 

valve and turn off the electrical supply.

2. 

Remove the flue and combustion air damper with solenoid actuator as an 

assembly

 (See 

FIGURE 2

)

:

a. 

On the outside of the cabinet, remove the two upper control access panels, 

revealing the control compartment, the venter assembly and the flue duct 

assembly. Carefully remove the venter motor and wheel assembly from the 

venter housing. Remove the venter housing.  

(

Model RP series only 

- Disconnect the rubber tubing from the sensing probe on 

the venter housing. Leave other end attached to the pressure switch).  

Save all venter parts including hardware, will be reused.

b. 

Disconnect Wires (Refer to original damper actuator wiring shown on page 4):

• 

Disconnect and discard the black wire that connects the combustion damper 

actuator coil to Terminal C in the heater control compartment.

• 

Disconnect and discard the white wire that connects the combustion damper 

actuator coil to Terminal L2 in the heater control compartment.

• 

Disconnect the yellow wire at its connection on the combustion damper upper 

end-switch. (Leave the other end of the yellow wire connected to Terminal 87 in 

the heater control compartment. This yellow wire will be reused.)

• 

Disconnect the orange wire at its connection on the combustion damper lower 

end-switch. (Leave the other end of the orange wire connected to Terminal 84 

in the heater control compartment. This orange wire will be reused.)

• 

Disconnect and discard the black wire that connects the combustion damper 

lower end-switch to Terminal 88.

c. 

Remove the flue duct cover plate from the flue duct and damper assembly. 

Model SC Series only.

 - Disconnect the rubber tubing from the sensing probe 

on 

the flue duct cover plate.

d. 

Remove the flue duct, combustion air damper and solenoid actuator as an 

assembly. Remove the screws attaching the flue duct to the collection box 

and remove the assembly. See 

FIGURE 2

. Keep the restrictor plate and all 

hardware

. Discard the flue outlet duct gasket.

 

On Model SC Series heaters

 - Remove and keep the sensing probe that is 

attached to the side of the flue duct. 

Discard the remaining assembly illustrated 

in 

FIGURE 2

.

Read carefully as 

many parts must be 

re-installed.

Flue Duct

Keep solid 

cover plate 

removed from 

the front of 

Step 2c

Solenoid 

Actuator

Model Series SC

Remove & keep the sensing 

probe that was attached to 

the side of the flue duct

End Switches

Remove all screws around 

the flue duct to remove the 

assembly from the flue 

collection box

Assembly removed from a unit manufactured prior to 8/2001

End Switches

Solenoid 

Actuator

Remove all screws 

around the flue 

duct to remove the 

assembly from the 

flue collection box

Flue Duct

Keep solid 

cover plate 

removed from 

the front in 

Step 2c

Model Series SC

Remove & keep the sensing 

probe that was attached to 

the side of the duct flue

Assembly removed from a unit manufactured beginning 8/2001

FIGURE 2

Remove & discard the Flue Duct & Combustion Air Damper Assembly with Solenoid Actuator

• 

Models RP & SC - 

Keep the restrictor plate & all hardware. Discard the flue duct gasket.

• 

Models RP & SC - 

Keep the cover plate removed in Step 2c. Discard the cover plate gasket.

• 

Model SC - 

Remove & keep the sensing probe attached to the side of the flue duct.

Summary of Contents for SC Series

Page 1: ... Wired Flue Duct Combustion Air Damper Assembly with Gear Motor P N 207975 or P N 207976 three Replacement Gaskets Flue Outlet Duct Gasket P N 31900 Use when attaching the new flue duct assembly to the collection box NOTE Be sure to reuse the restrictor plate Venter Seal Gasket P N 44695 Use when re installing venter housing on side of flue duct Cover Plate Gasket P N 41996 Use when reattaching co...

Page 2: ...k wire that connects the combustion damper lower end switch to Terminal 88 c Remove the flue duct cover plate from the flue duct and damper assembly Model SC Series only Disconnect the rubber tubing from the sensing probe on the flue duct cover plate d Remove the flue duct combustion air damper and solenoid actuator as an assembly Remove the screws attaching the flue duct to the collection box and...

Page 3: ...of the new combustion damper upper end switch Connect the orange wire from the heater control compartment Terminal 84 to the common terminal of the new combustion air damper lower end switch Connect the purple wire from the normally open terminal of the new combustion air damper upper end switch to Terminal 88 in the heater control compartment Connect the black wire from the normally open terminal...

Page 4: ...illustrations subject to change without notice and without incurring obligations Nortek Global HVAC LLC 2016 All rights reserved All marks are the property of their respective organizations O Fallon MO I Printed in U S A 6 16 FORM CP OPT GMK 6 16 PN208831 R3 ...

Reviews: