7.5.2
Group F1: Quick Start Parameter
Code
Name
Setting range
Default
Attri.
F1.00
ASF parameter initialization
0: Inactive
1: Restore to ASF default settings
2: Deactivate ASF
0
Stop
F1.02
Control word: Pressure command source
0: Depend on the value of F1.04
1: Communication
2: Analog input
3: Learning pressure command
4: Select by digital input (F1.04 shows
status)
0
Stop
F1.04
Pressure command selection
0: Pressure command digital setting 0
1: Pressure command digital setting 1
0
Run
F1.05
Pressure command digital setting 0
5.0...1,000.0 bar
5.0
Run
F1.06
Pressure command digital setting 1
5.0...1,000.0 bar
5.0
Run
F1.08
Preferred swivel angle command source
0: Swivel angle command of F1.09
1: Communication
0
Stop
F1.09
Command value: Preferred swivel angle
0.00...100.00 %
70.00
Run
F1.15
Motor type
0: Others
1: MOT-FC_HOY
0
Stop
F1.16
Motor power level
0: No selection 1...21 (only change mo‐
tor parameter by switching from 0 to
1...21)
0
Stop
Tab. 7-27:
Parameter list of group F1
7.5.3
Group F2: Input and Output Parameter
Code
Name
Setting range
Default
Attri.
F2.00
Analog input AI1
0: No function assigned
1: Pressure command
2: Pressure feedback
3: Oil level warning / error
4: Oil temperature
0
Stop
F2.02
Extended analog input EAI
0
Stop
F2.01
Analog input AI2
0: No function assigned
1: Pressure command
2: Pressure feedback
2
Stop
F2.04
Pressure command corresponding to 10 V / 20
mA
0.1...1,000.0 bar
100.0
Stop
F2.05
Pressure command null offset in V or mA
0...5.0 V, mA
0.1
Stop
F2.06
Pressure feedback corresponding to 10 V or 20
mA
0.1...1,000.0 bar
100.0
Stop
F2.07
Pressure feedback null offset in V or mA
0.0...5.0 V,mA
0.1
Stop