12.2.5
ModBus Communication Example
One slave address is 01H. The frequency setting of the frequency converter
has been set to “external computer frequency setting” and the source of run‐
ning commands is “external computer control”. It is required for the motor
connected to the frequency converter to run with 50 Hz (forward rotation).
The operation can be achieved with function 0x10 of the ModBus protocol.
The messages of the requests from the master and responses from the slave
fig. 12-20 "Example of ModBus communication" on page 189
.
Example 1: Start 01# converter for forward rotation at frequency of 50.00Hz (represented by 5000 internally)
Slave ad‐
dress
Function code Start ad‐
dress
Number of ad‐
dress
Bytes of data Data content
CRC code
Request
0x01
0x10
0x4000
0x0002
0x04
0x0001,
0x1388
0xFA9E
Response
0x01
0x10
0x4000
0x0002
N/A
N/A
0x0854
Example 2: Read the output voltage of 01# converter and set frequency
Slave ad‐
dress
Function code Start ad‐
dress
Number of ad‐
dress
Bytes of data Data content
CRC code
Request
0x01
0x03
0x5001
0x0002
N/A
N/A
0xCB84
Response
0x01
0x03
N/A
N/A
0x04
0x1388,
0x1388
0xCB73
Example 3: Stop 01# converter according to the stop mode set with the function code
Slave ad‐
dress
Function code Start ad‐
dress
Number of ad‐
dress
Bytes of data Data content
CRC code
Request
0x01
0x06
0x4000
N/A
N/A
0x0008
0xCC9D
Response
0x01
0x06
0x4000
N/A
N/A
0x0008
0xCC9D
Fig.12-20:
Example of ModBus communication
12.2.6
Special Notes
1. The external computer can not wirte to function codes [b0.03], [b0.08],
[b0.09] and [S2.10].
2. [b0.00] and [b0.02] do not support multiple write including single write in
multiple write; parameters of motor name plate and motor can not be
written at the same time; Terminals X1 ─ X8 can not be rewritten if they
are not 0.
3. If the communication protocol is changed, baud rate, data frame and lo‐
cal address will be restore to factory default.
4. The read response of uer password and factory password is '0000' in
case of external computer reading.
5. External computer can not set, modify or cancel user password; external
computer can only write 0 in case of no password or write correct pass‐
word in case of with password; if a password is active, the external com‐
puter only has the access to modify the parameters after input of the
correct password; After the external has the access to modify the pa‐
rameters, if the previous password is input again, the modification ac‐
cess is disabled.
6. The access to control registers and state registers is not limited by user
password.
DOK-RCON02-FV*********IB01-EN-P
Rexroth Frequency Converter Fv
Bosch Rexroth AG
189/219
Communication Protocols
Summary of Contents for Fv Series
Page 20: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 18 219...
Page 30: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 28 219...
Page 34: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 32 219...
Page 52: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 50 219...
Page 58: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 56 219...
Page 144: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 142 219...
Page 164: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 162 219...
Page 180: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 178 219...
Page 214: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 212 219...
Page 216: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 214 219...
Page 220: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 218 219...
Page 221: ...Notes DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv Bosch Rexroth AG 219 219...