The analog output terminals can be set with parameter ‘FM1 channel mode’
[E1.11] to select output signals 0 − 10 V, 0 − 20 mA or 2 − 10 V, or 4 − 20
mA.
Either voltage signals or current signals are output via analog output termi‐
nals is determined with JP3 and JP4 on the control board:
●
If JP3 is set to 1 − 2, FM1 outputs voltage signals; if JP3 is set to be 2 −
3, FM1 outputs current signals.
●
If JP4 is set to 1 −2, FM2 outputs voltage signals; if JP4 is set to be 3 −
4, FM2 outputs current signals.
●
Analog outputs are set with parameter ‘FM1 analog outputs’ [E1.10], as
fig. 7-47 "Meanings of analog outputs" on page 123
.
[E1.10]
Outputs
[E1.11]=0
[E1.11]=1
0
Output
frequency/
rotation speed
0 to maximum
output frequency,
corresponding
0 − 10 V / 0 − 20 mA
0 to maximum
output frequency,
corresponding
2 − 10 V / 4 − 20 mA
1
Reference
frequency/
rotation speed
0 to maximum
reference frequency,
corresponding
0 − 10 V / 0 − 20 mA
0 to maximum
reference frequency,
corresponding
2 − 10 V / 4 − 20 mA
2
Output current
0 to 2 times of rated cur‐
rent,
corresponding
0 − 10 V / 0 − 20 mA
0 to 2 times of rated cur‐
rent,
corresponding
2 − 10 V / 4 − 20 mA
3
Torque current
0 to 200 % of rated torque
current, corresponding
0 − 10 V / 0 − 20 mA
0 to 200 % of rated torque
current, corresponding
2 − 10V / 4 − 20 mA
4
Output voltage
0 to 1.2 times of rated volt‐
age, corresponding
0 − 10 V / 0 − 20 mA
0 to 1.2 times of rated volt‐
age, corresponding
2 − 10 V / 4 − 20 mA
Fig.7-47:
Meanings of analog outputs
●
Parameter ‘FM1 gain setting’ [E1.12] is used to set the gain of FM1.
E1.13
FM2 analog outputs
Factory Default 1
Setting range
0 − 4
Minimum unit
1
E1.14
FM2 channel mode
Factory Default 0
Setting range
0, 1
Minimum unit
1
E1.15
FM2 gain setting
Factory Default 1.00
Setting range
0 − 10.00
Minimum unit
0.01
The description is the same as that of parameters [E1.10] − [E1.12].
E1.16
Pulse outputs
Factory Default 0
Setting range
0, 1, 2
Minimum unit
1
DOK-RCON02-FV*********IB01-EN-P
Rexroth Frequency Converter Fv
Bosch Rexroth AG
123/219
Parameter Settings
Summary of Contents for Fv Series
Page 20: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 18 219...
Page 30: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 28 219...
Page 34: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 32 219...
Page 52: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 50 219...
Page 58: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 56 219...
Page 144: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 142 219...
Page 164: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 162 219...
Page 180: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 178 219...
Page 214: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 212 219...
Page 216: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 214 219...
Page 220: ...Bosch Rexroth AG DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv 218 219...
Page 221: ...Notes DOK RCON02 FV IB01 EN P Rexroth Frequency Converter Fv Bosch Rexroth AG 219 219...