6
Reverso Pumps, Inc. www.reversopumps.com | [email protected] | Ph: (954) 522-0882
Technical Specifications
Flow Rate
Approximately 210 GPH (795 LPH).
Actual flow rate may vary due to conditions of installation.
Operating Temperature
40 - 104°F (4-40°C)
Amp. Draw
3A@110V, 1.2A@220V
Circuit Breaker
10A@110V, 10A@220V
Service Space
4” on top and bottom, to facilitate changing filter elements and
draining water and particulate from the bowl
Pump
Brass Gear stainless shaft- double lip seal
Maximum Suction Hose
32.8 ft / 10m with foot valve above liquid level
Maximum Delivery Hose
164 ft / 50m
Maximum Level Difference
Between pump and suction: from 5 - 9.8 ft maximum / 1.5 to 3 m maximum.
Between pump and highest point of delivery: 23 ft / 7m maximum
Timer
Digital
PLC
Inlet
1/2”
Male
JIC
Outlet
1/2” Male JIC
Max Fluid Viscosity
29 CST
Filter Torque Values
Bowl Retainer Ring
8 Nm (70 in-lbs)
Lid
8
Nm
(70
in-lbs)
Plug
15
Nm
(130
in-lbs)
Bleed
Screw
4
Nm
(35
in-lbs)
• The system has been developed to be used with diesel fuel only, DO NOT USE WITH GASOLINE.
• The system is designed to meet environmental standards for safe operation (NOT for use with fluids that have a
flash point below 100°F (38°C), e. g.: Gasoline, alcohol,...)
Warning