3.2 MOUNTING HOLES

There  are  special  mounting  holes  in  the  back  flange  of  the  fan.  Using  them,
 it is possible to mount the device with e. g. mounting pins. In order to dampen 
possible  vibrations  of  the  structure,  it  is  recommended  to  use  anti-vibration 
mounts.  Necessary  assembly  elements,  suitable  for  this  type  of  installation, 
should be purchased independently.

4. INSTALLATION INSTRUCTIONS

4.1. CONNECTION OF THE DEIVCE TO THE ELECTRICAL SYSTEM 

all  works  concerning  electrical  installation  should  be  made  by  the  qualified 

personnel (who possess required authorizations to install electrical equipment), 
based on wiring schematic diagrams (see 7)

the electrical installation of the building shall have a residual current device

it is recommended to check the electric installation and controls before the first 

start

5. PRECAUTIONS & WARNINGS

The  precautions  mentioned  below  must  be  strictly  followed  during  operation 
of the device:
-  all  works  concerning  electrical  installation  (disassembly,  repair  etc.)  should 
be made by the

 

qualified staff, who possess the qualifications due to the domestic 

and local norms, regarding electrical installations
- before service or exchange of the device it is obligatory to cut off the current 
supply
- do not limit or cover the inlet and outlet of the device
- do not install, service the device with wet hands or barefoot
- the device should be kept out of reach of children and animals

after operating time of the device, please utilize it concerning the local norms 

and regulations

ź

i

t is recommended to clean the device periodically (at least twice a year)

:

 

air stators, fan casing and blades clean from dirt

-failure  to  comply  with  cleaning  obligations  may  have  a  negative  effect 
on technical parameters of the device

 

and lead to loss of warranty

i

f the device is not used for a longer time and lead to loss of warranty

 

disconnect 

the voltage supply

the  device  is  transported  with  the  closed  air  stators.  It  is  essential  to  open 

them in at least  for 30 % before first start

:

ź

 

opening  the  air  stators  of  the  diffuser  360°

 

must  be  done  by  two  hands 

in parallel

6. CONTROLS

Usage of automatic control dedicated to the devices of Reventon Group gives 
great possibilities of adjusting the efficiency of the unit in different, depending 
on needs, degree of its operation automation. We can offer the following:

5 control levels: 

80-105-135-170-230 V

Voltage/ Frequency: 

230 V AC / 50 – 60 Hz

Maximum current output (depending on model):

1.2 A, 3 A, 5 A, 7 A, 14 A

Protection: 

thermal switch

Weight(depending on model):

1.45 kg, 2.5 kg, 4.5 kg, 5.5 kg or 10.5 kg

Degree of protection: 

IP 54

Fan speed controller HC

designed to change the single-phase fan's speed voltage controlled in industrial
supply  and  heating  systems.  It  is  available  in  several  versions.  The  selection
of  the  appropriate  model  depends  on  the  number  of  the  devices
that  have  to  be  connected  to  the  to  one  regulator  –  the  total 

current

of  the  connected  devices  cannot  exceed  the  maximum  current  flow
of the regulator.

Manual thermostat HC

c

ontrols  operation  of  the  heater

 

destratification  fan.  It  switches  the  unit 

off  automatically

,   

when  the  set  temperature  is  reached

The  total

 

current

of  the  connected  devices  cannot  exceed  the  maximum  current  flow 
of the thermostat.

                                                                                          

Power supply/ Frequency

:

 230 V AC / 50 – 60 Hz

                                                                                      

   

Maximum current

3 A

                                                                                            

Operating temperature:

 0 - 40°C

                                                                                            

Temperature control range:

 10 - 30°C

                                                                                 

    

Control accuracy:

 <1°C

Degree of casing's protection:

 IP 30

allows to connect a receiver with higher current consumption than permissible 
current load of connected regulator.

                                                                                         

Power supply/ Frequency :

 230 V AC / 50 – 60 Hz

                                                                                            

Maximum rated current:

 16 A

                                                                                            

Input

:

 

NO/COM

  

                                                                                            

Input

:

 

SL Connection of a regulator

with the voltage relay 230 V

                                                                                            

Dimension

:

 47 x 47 x 20 mm

Relay Module RM-16A