and then use MODE button to  go  to  the next positions:

Controlling

Settings  - 

press  SET  button  for  6  seconds  to  enter  the  edition  mode 

ź

Clock  –  while  in  the  clock  setting  mode,  press  SET  button  and  use  UP 

and  DOWN  arrows  to    set    the    hour.  Then  press  again  MODE  button 
to set the minutes in a similar way. To confirm the  set time press SET button.

ź

  Day  –  while  in  the  day  of  the  week  mode,  press  SET  button  and  use  UP 

and  DOWN  arrows  to    set  the  correct  one.  To  confirm  the  set 

day

  press  SET 

button.

If the period is active, press MODE button to move to the end time of the period 
(using UP and DOWN arrows and MODE button to   go   from hour to minute

or vice versa). To confirm the set start time of the period press SET button. Repeat 
the  above  steps  until  the  start  times  for  all  required  periods  are  set. 
Then press SET key again to save the set schedule.

If the period is active, press MODE button to move to the start time of the period 
(using UP and DOWN arrows and MODE button to   go   from hour to minute 

ź

 Weekly timer on – while in the weekly switch settings mode, press SET button 

and then by   pressing SET key select correct day of the week and period 1 or 2 
(two periods per day can be programmed). After selecting the day, press POWER 
ON / OFF button to activate / deactivate the start time of the period for the day. 

ź

 Weekly timer off – while in the weekly switch settings mode, press SET button 

and then by   pressing SET key select correct day of the week and period 1 or 2 
(two periods per day can be programmed). After selecting the day, press POWER 
ON / OFF button to activate / deactivate the end time of the period for the day. 

or vice versa). To confirm the set end time of the period press SET button. Repeat 
the above steps until the end times for all required periods are set. Then press 
SET key again to save the set schedule.

Error code – 

press SET buton to display the error code.

to value

 1 (see point 6.3).

to set the required supply air temperature from the range 10 

-

  25°C.

to previous settings when the humidity level falls below the permissible value.

in  the  humidity  sensor  mode,  use  UP  /  DOWN  arrows  to  set  the  maximum 
permissible relative humidity (within the range of  45 - 90%), after which the unit 
starts  to  work  automatically  at  the  highest  speed.  The  device  will  return 

ATTENTION!  If  humidity  sensor  is  connected,  remember  to  change 

Setting  humidity  sensor  (available  only  if  humidity  sensor  is  connected)  –

 

the switching circuit 3  to  ON  position (see point 6.6).

Setting supply air temperature (available only if electric heater is connected 
in  the  supply  air  side)  – 

in  the  TA  mode,  use  UP  /  DOWN  arrows 

ATTENTION!  If  heater  is  connected,  remember  to  change  parameter  no.  1 

ź

 If OA 

temperature

 is > -15°C, but FR 

temperature

 is < -1°C, preheater 

turns

 

ATTENTION! In the ON mode standard RA temperature sensor is deactivated 
because  its  function  is    taken  over  by  the  humidity  sensor.  For  this  reason 

ź

If  OA 

temperature

  is  <  -15°C  the  preaheater  turns  on  for  50  minutes 

Switching circuit 1 – 

allows you to change the defrosting mode. It is set to OFF 

by  deafult,  i.  e.  defrosting  by  using  return  air.  Changing  the  position  to  ON

and the fans turn off for 10 minutes (after this time they turn on again)

Switching  circuit  3  –

  in  the  OFF  mode,  the  unit  works  according  to  the  CO

2

 

sensor (if connected) and   in   the ON mode it reacts on the CO

2

 sensor signal 

The  dial  switch  is  located  on  the  controller  (see  wiring  diagram  in  point  7)

on for 10 minutes

6.6 DIAL SWITCH 

 and allows the controller to  adapt to the user's requirements. It consists of four 
two-state switching circuit, which correspond  to:

ź

 If the preheater is turned on and OA temperature is > 25 °C, the preheater turns 

off for 5 minutes; if such situation repeats 3 times in a row, the preheater turns off

Switching circuit 2 – 

allows to inactivate the bypass function (both automatic 

and manual bypass using dedicated circuit) - to do this, switch the system from 
OFF (default) to ON position.

  is  a  signal  for  the  controller,  a  preheater  on    the    outside  air  side  has  been 
connected and the possible defrosting process will be carried out using it:

ź

 If the preheater is turned on and FR temperature is still < -1°C, the fans turn 

and / or the relative humidity (if connected).

if the circuit 3 is in ON position without a  humidity sensor connected, an error 
code E3 will be displayed.

Switching circuit 4 –

in the OFF mode value of baud rate is 4800, while in the ON 

mode it is 9600

off for 50 minutes

Code

E1

E2

E3

E4

E5

E6

E7

E8

Error

fresh air temperature sensor (OA) error

EEPROM memory error

return air temperature sensor (RA) error

exhaust air temperature sensor (FR) error

communication error

supply air temperature sensor (SA) error

exhaust fan error

supply fan error

Summary of Contents for INSPIRO

Page 1: ...Technical documentation Energy Recovery Unit INSPIRO MODELS INSPIRO 150 INSPIRO 250 INSPIRO 350 INSPIRO 500 INSPIRO 650 INSPIRO 800 INSPIRO 1000 INSPIRO 1300 EN...

Page 2: ...3 ASSEMBLY 3 2 DUCTING 4 1 CONNECTION OF THE DEVICE TO THE ELECTRICAL SYSTEM 5 PRECAUTIONS WARNINGS 6 CONTROLS 6 2 COMMISSIONING 6 3 CONTROLLER S PARAMETER 6 5 INTELLIGENT CONTROL PANEL PREMIUM 6 4 I...

Page 3: ...INSPIRO500 1975 INSPIRO650 1976 INSPIRO800 1977 INSPIRO 150 INSPIRO 250 INSPIRO 350 INSPIRO 500 INSPIRO 650 INSPIRO 800 150 70 80 220 240 50 38 X2 25 31 5 A 250 73 81 220 240 50 85 X2 27 34 5 A 350 7...

Page 4: ...INSPIRO 350 INSPIRO 500 INSPIRO 650 INSPIRO 800 INSPIRO 1000 INSPIRO 1300...

Page 5: ...ou can check on the panel an error code data memory the controller remembers the settings in a case of power supplybreak freecooling thefunctionenablesdirectsupplyofcoldoutsideairbyactivating bypassat...

Page 6: ...ameter Auto restart Electrical heater Automatic bypass temperature X Automatic bypass temperature Y Defrosting interval Defrosting entering temperature Defrosting duration time Permissible CO2 concent...

Page 7: ...timer off to determine endsoftheseperiods andLEFTbuttonstoselectday The numbers 1 and 2 indicate the end of the first and second schedule period Weekly timer on press WEEKLY TIMER ON button all days...

Page 8: ...ENTION If humidity sensor is connected remember to change Setting humidity sensor available only if humidity sensor is connected theswitchingcircuit3 to ON position seepoint6 6 Setting supply air temp...

Page 9: ...areavailableonlyiftheyareconnected ischanged Itispossibletoset10differentspeedsforeachfan UP DOWN use the arrows to adjust the fan speed Depending on the mode the speed of the supply air fan in OA or...

Page 10: ...7 CONNECTION SCHEME...

Page 11: ...Warranty does not cover the parts of the device subject to normal maintenanceandthefollowingcases fromleavingthesupplier swarehouse of the warranty card with stamp of installation company document co...