Microprocessor Control Board
–
Random start timer prevents multiple units from
simultaneous start-ups after power outage.
–
Fan purge — fan remains on for 60 seconds after
heat/cool call is satisfied
–
Anti-short-cycle compressor protection prevents
compressor from rapid cycling
–
Freeze protection — prevents evaporator coil
freeze up, improving compressor reliability
–
Low ambient lockout prevents compressor
operation in outdoor temperatures less than 40°F
(4.4°C) Heating, 25°F Cooling.
–
Test operation — all timers are temporarily
suppressed to allow ease of testing or
troubleshooting
–
Control board LED provides self-diagnostic
troubleshooting codes. See Sequence of
Operation, page 15.
•
Field-Installed Accessories:
–
Remote wall thermostat (digital 1-stage or
2-stage available).
GENERAL PRODUCT INFORMATION
Product Description
• RQTH single package vertical heat pump (SPVHP).
• R-410A refrigerant.
• Custom outdoor louver required for performance.
• Insulated top-discharge indoor compartment.
• Vertical discharge allows ducting to top of room(s).
• Models can be applied in non-ducted return air
applications.
• RQTH models are limited-range heat pumps. Heat pump
operation will cease at approximately 40°F (4.4°C)
outdoor temperature. Cooling opertion will cease at
approximately 25°F.
Standard Controls And Components:
• Ability to utilize one stage cooling or two stage
heating thermostat for emergency heat.
•
Disposable return air filter.
APPLICATION LIMITATIONS
• Contact manufacturer if units will be operated in
temperatures outside ranges listed below.
Table 2 Ambient Air Limitations
OUTDOOR
[Ambient air temperature °F (°C)]
COOLING
HEATING
Minimum
Maximum
Maximum
Dry bulb
Dry bulb
Dry bulb
67 (19)
115 (46)
70 (24)
INDOOR
[Ambient air temperature °F (°C)]
COOLING
HEATING
Minimum
Maximum
Min.
Max.
Dry
bulb
Wet
bulb
Dry
bulb
Wet
bulb
Dry bulb
67 (19) 57 (14) 90 (32) 72 (22) 50 (10) 80 (27)
8
Made in USA
PN 240010236 REV. D [12/15/2018]