WMZ-G1
© RESOL_10096
WMZ-G1.mon
us.ind
d
7
|
2.4 Operating control lamp
The device is equipped with a red/green operating control
lamp. The following operating states can be visualized:
•
green constant
normal operation;
•
green flashing
measured value outside alarm
limit
•
red flashing
defective sensor
•
not illumated
no voltage
3. Measured values
S1:
T1: 74.8 ° c
P1: 0.14 bar
P: 9 W
S2:
T2: 23.9 ° C
Q2: 5.55 l/min
Heat: 19944 Wh
In the submenu “Measured values”, different measurement
val ues are shown: the measured values depend on the sen-
sor type and can be the following:
Sensor 1: T1 (temperature in ° C or ° F)
p1 (pressure in bar)
Q2 (flow rate in l/min, m³/h or gallon/h)
P (in W) – values over 999,999 W cannot be
processed. In such a case, both the displayed
value and the VBus
®
data packet value remain
at 999,999 W.
Sensor 2: T2 (temperature in °C or ° F)
p2 (pressure in bar)
Q2 (flow rate in l/min, m³/h or gallon/h)
Heat (in Wh
, kWh, MWh, kJ, MJ or GJ.
)
Note:
“Power” and “Heat” are only indicated when
at least one of the sensors connected is a VFS
type sensor and the option “Heatmeter” in the
submenu “Adj. values” has previously been set
to “Yes”.
S1 measures the flow temperature, S2 the return
temperature.
If the flow temperature is lower than the return temperature,
heat quantity measurement is not carried out. In that case,
the power is displayed as 0.
Briefly press button 3 in order to get back to the main
menu.
2.3 Initial commissioning
•
Language:
Î
Select the menu item “Language“ with button 1 and
confirm with button 3
Î
Select the desired language with buttons 1 and 2
Î
In order to confirm the selection, briefly press button
3 and answer the security inquiry with “Yes“
Î
In order to change to the adjustment values menu,
select the menu item “back“ and confirm with button 3
The following languages are available: German (“Deutsch“),
English, Spanish (“Castellano“), French (“Français“), Italian
(“Italiano“). The factory setting is “English“.
Î
Establish the power supply
In the “Adjust. Values“ menu, carry out the adjustments
mentioned below. For further information on the adjustment
values, see chap. 5.
•
Date:
Î
Select the menu item “Date“ with button 1 and confirm
with button 3
Î
Adjust the year, the month and the day with buttons 1
and 2 and confirm each with button 3
Î
In order to confirm the adjustment, briefly press button
3 and answer the security inquiry with “Yes“
• Time:
Î
Select the menu item “Time“ with button 1 and confirm
with button 3
Î
Adjust the hours and the minutes with buttons 1 and 2
and confirm each with button 3
Î
In order to confirm the adjustment, briefly press button
3 and answer the security inquiry with “Yes“
Adj. values:
language
english
Date
01.01.2009
Time
00:00