Resol WMZ-G1 Mounting, Connection, Operation Download Page 4

WMZ-G1

© RESOL_10096 

WMZ-G1.mon

us.ind

d

|

 

4

 

Î

Unscrew the cross-head screw of the cover (1.) and 
re move the cover from the housing. 

 

Î

Unscrew the two lateral srews of the transparent shield 
(2.) and remove the shield.

 

Î

Pull out the board which is to be replaced carefully (3.). 
Replace with new board.

 

Î

Place the shield back on the housing and attach with 
the two screws. 

 

Î

Put the cover on the housing and attach with the cross-
head screw.

VBus

®

 board

When the WMZ-G1 is connected to a control-
ler, the VBus

®

 master board has to be replaced 

with the VBus

®

 slave board!

When  several WMZ-G1  modules  are  cascaded 
and connected to a datalogger or PC (see p. 14), 
only  the VBus

®

  master  boards  of  the WMZ-G1 

modules with the subaddress 1 or higher have to 
be replaced with the VBus

®

 slave boards!

Replacing the VBus

®

 board

WARNING!

Electric shock!
Opening the housing will expose 
live parts!

 

Î

Switch off power supply and dis-
connect the device from mains 
before opening the housing!

ATTENTION! ESD damage!

Electrostatic discharge can lead to da-
mage to electronic components!

 

Î

Take care to discharge properly 
before touching the inside of the 
device!

1.

2.

3.

The VBus

®

 master board is marked with a “B”, 

the VBus

®

 slave board with a “J” in the upper 

right corner of the populated side of the board.

Summary of Contents for WMZ-G1

Page 1: ...OL WMZ G1 Mounting Connection Operation Manual 48005460 48005460 Thank you for buying this RESOL product Please read this manual carefully to get the best performance from this unit Please keep this m...

Page 2: ...scription of symbols 2 Disposal 2 Information about the product 2 Technical data and overview of functions 3 VBus board 4 1 Installation 5 1 1 Mounting 5 1 2 Connections 5 1 3 Data communication Bus 5...

Page 3: ...the number and type of sensors connected the unit is capable to show tempera ture values flow rates and relative or differential pressures or a combina tion of them Heat quantity measurement is possib...

Page 4: ...theVBus slave board When several WMZ G1 modules are cascaded and connected to a datalogger or PC see p 14 only the VBus master boards of the WMZ G1 modules with the subaddress 1 or higher have to be...

Page 5: ...equipped with 1 relay to which a load can be connected Relay 1 R1 conductor R1 N neutral line N 12 13 14 grounding The sensors S1 S2 are connected to the following ter minals T 1 2 temperature signal...

Page 6: ...hed Briefly press button 3 in the relevant menu line for modification of adjustment values change value appears on the display adjust the requested value by pressing buttons 1 and 2 Briefly press butt...

Page 7: ...eturn temperature heat quantity measurement is not carried out In that case the power is displayed as 0 Briefly press button 3 in order to get back to the main menu 2 3 Initial commissioning Language...

Page 8: ...sensor 1 in l min m h gallon h Max maximum flow rate at sensor 1 in l min m h gallon h Acc accumulated volume since commissioning last reset in l m or gallons Display of balance values Sensor 2 Tempe...

Page 9: ...6 bar 0 2 5 bar 0 4 bar 0 6 bar 0 10 bar 0 16 bar 0 25 bar 0 40 bar DPS Range Custom Min 0 00 15 99 bar Max 0 00 16 00 bar 0 0 6 bar 0 1 bar 0 1 6 bar 0 2 5 bar 0 4 bar 0 6 bar 0 10 bar 0 16 bar Adju...

Page 10: ...epends on the sensor type Therefore the following parameters and adjust ment values depend on the sensor type flow rate forVFS pressure for RPS differential pressure for DPS Adjust the parameters refe...

Page 11: ...has to be adjusted Adjustment range 0 99 9 bar Heat quantity measurement Heat quantity measurement is carried out by means of the difference between the flow and the return temperature as well as the...

Page 12: ...hange the factory setting if the WMZ G1 is connected to a RESOL controller with VBus output terminal corresponds to the bus mode Passive Select bus mode Active if the WMZ is not connected to a control...

Page 13: ...rm Reports Sensor 1 Min d p alarm The differential pressure at sensor 1 has fallen below the adjusted minimum value Signal failure at sensor 1 signal 1 temperature Signal failure at sensor 1 signal 2...

Page 14: ...Min d p alarm Signal failure at sensor 2 signal 1 temperature Signal failure at sensor 2 signal 2 this can be flow rate relative pressure or differential pressure depending on the sensor type The adju...

Page 15: ...board subaddress 1 15 bus mode Cascaded The connection sequence at theVBus is arbitrary Cascade with controller controller No adjustments have to be made WMZ G1 module must not be registered WMZ G1 0...

Page 16: ...requires the approval of RESOL Elektronische Regelungen GmbH This especially applies for copies translations micro films and the storage into electronic systems Editor RESOL Elektronische Regelungen G...

Reviews: