HKM2

|

2.5 Heating circuit rapid warm-up

A rapid warm-up of the heating circuit can only be activated 
if the remote control is set to position “rapid warm-up 
process”. 
Rapid warm-up means that the mixer is fully started up 
and the heating circuit pump is switched on. There is no 
regulation  of  the  flow  temperature.  The  heating  circuit 
rapid warm-up should only be activated if the maximum 
flow temperature exceeds the current store temperature. 
The heating circuit will be switched off if the maxiumum 
flow temperature is reached.

2.1 Weather-compensated heating circuit:

The flow set temperaure for the heating circuit results 
from the outdoor temperature and the chosen heating 
curves. This flow set temperature can also be changed with 
a remote control and the parameters “day correction/night 
correction”. The control adjusts the current heating circuit 
flow temperature to the determined flow set temperature 
by opening/closing the heat circuit mixer.

2.2 Timer (daily programme): 

  

 

The timer determines whether the day correction or the 
night correction is used for changing the flow set tempe-
rature. If one of the time frames of the timer is “active”, 
the night correction is used. If none of the time frames is 
active, the flow set value is changed due to the day cor-
rection. A time frame is “active” when the current time is 
between the switch-on and the switch-off time.

2.3 Remote control:

The remote control allows manual adjustment of the hea-
ting curve (+/-15 K). Moreover, the heating circuit can be 
switched off or a rapid warm-up process can be started 
with the remote control. The remote control is option al 
and it is not included in the full kit.

2.4 Heating circuit shutdown:

The heating circuit can be switched off manually if 
• the remote control is set to “Heatlp. off” 

The heating circuit is shut down automatically if 
  the adjusted maximum flow temperature is reached
  the  outdoor  temperature  is  higher  than  the  adjusted 

summer temperature. 

  the flow set temperature sensor is faulty.
•  or  the  heating  circuit  at  the  controller  is  deactivated 

(permanently off)

Heating circuit shutdown means that the heat circuit pump 
is switched off and the mixer is shut down. 

2. 

Function overview

All settings for the HKM2 have to be adjusted with 
the corresponding menu of the connected control-
ler! Please read the manual for the controller in 
order to use all functions of the HKM2.

Summary of Contents for HKM2

Page 1: ...uit module HKM2 Operation Mounting Electrical Connection 48001390 48001390 manual Thank you for buying this RESOL product Please read this manual carefully to get the best performance from this unit P...

Page 2: ...omestic water priority 11 3 1 14 Timer 11 3 1 15 HKM expert 12 3 1 16 Manual operation 13 3 1 17 Operating control lamp flashing codes 13 4 Commissioning 13 5 Tips for fault localisation 13 5 1 Troubl...

Page 3: ...eating circuit module for a weather compensated heating circuit incl outdoor temperature sensor FAP13 and flow temperature sensor FRP21 Can fuse T4A Attachment opening Sensor terminals Net terminals L...

Page 4: ...outputs Operating control lamp Manual control switch Technical data Housing plastic plug in Protection type IP20 EN 60529 Size 208 x 141 x 65 mm Ambient temperature 0 40 C Inputs 4 sensor inputs Pt100...

Page 5: ...cables WARNING Switch off power supply before opening the housing 1 1 Wall mounting 1 Installation The HKM2 is designed for wall mounting Please pay at tention to the fact that the back of the wall ho...

Page 6: ...angeover contact terminals 1 2 The connection of the load must be effected at the terminals 17 to 28 with correct polarity Rx N see terminal scheme fig 2 The protective conductors are to be connected...

Page 7: ...anging the flow set tempe rature If one of the time frames of the timer is active the night correction is used If none of the time frames is active the flow set value is changed due to the day cor rec...

Page 8: ...ng circuit during domes tic hot water after heating For this purpose the option domestic hot water priority has to be activated and the after heating has to be effected by the boiler charge con trol 2...

Page 9: ...ion ofVBus Adjustment channel HKM2 MM Manual Mode State of the relays only if manual control switch is set to I 0 R1 on R3 on 1 R1 on R2 on 2 R1 on PG ProGramme Hardware version Display channel HKM2 V...

Page 10: ...justment of the value is to be exclusively effected at the external remote control RESOL RTA11 M which has to be activated from the DeltaSol M Version 1 10 on in the heat circuits expert menu The valu...

Page 11: ...he deviation of the current flow temperature from the flow set temperature The mixer is activated for four seconds in each case factory setting The pause is calcu lated from the deviation from the set...

Page 12: ...the maximum flow temperature is reached Only the mixer will be shut down In this menu the weather compensated after heating can be activated Select adjustment therm function refers to S1 or boiler fun...

Page 13: ...nts 1 Power supply If the operating control lamp is off please check the power supply of the controller The HKM2 is protected by a can fuseT4A which is accessible and can be replaced by opening the co...

Page 14: ...ating heats very slowly Adjusted value for mixer runtime is too low In spite of heating pauses it is constantly too warm Please check the adjusted heating curve decrease it if necessary Flow maximum t...

Page 15: ...work by cleaning the contact area and by applying heat con ductive paste between sensor and pipe In order to protect the sensor cable against external temperature influences we recommend insulating th...

Page 16: ...gen GmbH This especially applies for copies translations microfilms and the storage into electronic systems Editor RESOL Elektronische Regelungen GmbH Important notice We took a lot of care with the t...

Reviews: