© RESOL 09005 HMK2.monen.ind
d
HKM2
7
|
2.5 Heating circuit rapid warm-up
A rapid warm-up of the heating circuit can only be activated
if the remote control is set to position “rapid warm-up
process”.
Rapid warm-up means that the mixer is fully started up
and the heating circuit pump is switched on. There is no
regulation of the flow temperature. The heating circuit
rapid warm-up should only be activated if the maximum
flow temperature exceeds the current store temperature.
The heating circuit will be switched off if the maxiumum
flow temperature is reached.
2.1 Weather-compensated heating circuit:
The flow set temperaure for the heating circuit results
from the outdoor temperature and the chosen heating
curves. This flow set temperature can also be changed with
a remote control and the parameters “day correction/night
correction”. The control adjusts the current heating circuit
flow temperature to the determined flow set temperature
by opening/closing the heat circuit mixer.
2.2 Timer (daily programme):
The timer determines whether the day correction or the
night correction is used for changing the flow set tempe-
rature. If one of the time frames of the timer is “active”,
the night correction is used. If none of the time frames is
active, the flow set value is changed due to the day cor-
rection. A time frame is “active” when the current time is
between the switch-on and the switch-off time.
2.3 Remote control:
The remote control allows manual adjustment of the hea-
ting curve (+/-15 K). Moreover, the heating circuit can be
switched off or a rapid warm-up process can be started
with the remote control. The remote control is option al
and it is not included in the full kit.
2.4 Heating circuit shutdown:
The heating circuit can be switched off manually if
• the remote control is set to “Heatlp. off”
The heating circuit is shut down automatically if
• the adjusted maximum flow temperature is reached
• the outdoor temperature is higher than the adjusted
summer temperature.
• the flow set temperature sensor is faulty.
• or the heating circuit at the controller is deactivated
(permanently off)
Heating circuit shutdown means that the heat circuit pump
is switched off and the mixer is shut down.
2.
Function overview
All settings for the HKM2 have to be adjusted with
the corresponding menu of the connected control-
ler! Please read the manual for the controller in
order to use all functions of the HKM2.