Accessory
Remote control RTA11-M
The remote control RTA11-M serves for the adjustment of the heating curve of the
controller. An increase of the heating curve causes also an increase of the flow set tem-
perature, a lowering stands for a decrease of the flow set temperature. Furthermore, the
remote control comprises the function “Heating circuit off” and “Rapid warm-up”.
Information concerning orders
Item number
RTA11-M remote control
136 000 20
For the RESOL module HKM2 and the corresponding con-
troller precision temperature sensors in Pt1000 version
(FKP and FRP) are used
FK: 1,5 m weather- and temperature resistant silicone cable
for temperatures between -50 °C ... +180 °C, mostly used
for collectors.
Sensor types
Immersion sleeve: Available in different lengths (im-
mersion depth)
FK...60: 60 mm immersion depth, brass sleeve, chromed
FK...150: 150 mm immersion depth, copper sleeve, chro-
med
Cylindrical clip-on sensors: for optional tube diameter,
completed with strain relief
FK...21 or FR...21
Ensure good thermal contact of the sensor with the pipe
work by cleaning the contact area and by applying heat con-
ductive paste between sensor and pipe. In order to protect
the sensor cable against external temperature influences,
we recommend insulating the pipe.
Flatscrew sensors: For installation on flat surfaces
FK...9 oder FR...9
Ensure good thermal contact of the sensor with the pipe
work by cleaning the contact area and by applying heat con-
ductive paste between sensor and pipe. In order to protect
the sensor cable against external temperature influences,
we recommend insulating the pipe.
FR: 2.5 m PVC cable for temperatures between
-10 °C ... +80 °C, mostly used for stores.
Make sure that all electrical works are carried out according
to the relevant local and national regulations. The sensor
cables carry low voltages and they must not run together
in a cable conduit with cables carrying higher voltages than
50 V. The sensor cables can be extended up to 100 m,
but the cross-section area of the extended cable must be
1.5 mm² (or 0.75 mm² up to a cable length of 50 m); For lon-
ger cables and for a use in cable conduits, twisted two-wire
cables should be used. The sensors must not be in direct
contact with water, please always use immersion sleeves.
Note:
Push the sensor entirely into the sleeve and
tighten the screw slightly.