Resol DeltaSol C/3 Mounting, Connection, Operation, Troubleshooting, Examples Download Page 18

D e lt a S o l

®

 

C/3

© RESOL 11150 deltasol_c/3.monen.ind

d

|

 

18

Stores cool down at night.

Does the collector 
circuit pump run in the 
night?

no

yes

Check controller.

At  night,  the  collector 
temperature  is  higher 
than  the  outdoor  tem-
perature.

no

yes

Check  the  non-return 
valve in flow and return 
pipe with regard to the 
functional efficiency.

Sufficient store insula-
tion?

yes

no

Increase insulation.

Insulation close enough 
to the store?

yes

no

Replace insulation or in-
crease it.

Are the store connec-
tions insulated?

yes

no

Insulate the connections.

Warm water flow up-
wards?

no

yes

Change connection and 
let the water flow side-
wards or through a siphon 
(bow  downwards);  less 
store losses now?

Does warm water circu-
lation run for a very long 
time?

no

yes

Use the circulation pump         
with timer and switch-off 
thermostat (energy effici-
ent circulation)

The solar circuit pump does not run although the collector 
is significantly warmer than the store.

Does the control LED 
flash?

yes

no

Does the pump start up 
in manual operation?

yes

No current; check fuses 
/ replace them and check 
power supply.

The adjusted temperature 
difference for starting the 
pump is to high; choose a 
value which makes more 
sense.

no

Is the pump current re-
leased by the controller?

yes

Is the pump stuck?

Turn the pump shaft using 
a screwdriver; now pas-
sable?

Pump is defective - re-
place it

Are the controller fuses 
o.k.?

Controller might be de- 
fective - replace it.

no

yes

no

no

yes

Replace the fuses.

Circulation  pump  and 
blocking valve should be 
switched-off for 1 night; 
less store losses?

yes

no

Check whether the pumps 
of the after-heating cir-
cuit runs at night, check 
non-return valve; problem 
solved?

no

no

yes

o.k.

Check  the  non-return 
valve in warm water cir-
culation- o.k.

yes

no

Further pumps which are 
connected  to  the  solar 
store must also be che- 
cked.

The gravity circu lation in 
the circulation line is too 
strong; insert a stronger 
valve in non-return valve 
or an electric 2-port val-
ve behind the circulation 
pump; in pump operation, 
the 2-port valve is open, 
other wise it is closed, co-
nect  pump  and  2-port 
valve in parallel; activate 
circulation again!

Clean or replace

a

a

b

b

Summary of Contents for DeltaSol C/3

Page 1: ...com Thank you for buying this RESOL product Please read this manual carefully to get the best performance from this unit RESOL D e lt a S o l C 3 Mounting Connection Operation Troubleshooting Examples...

Page 2: ...ppropriate usage This product is to be used in simple solar thermal systems in com pliance with the technical data specified in these instructions see p 3 Improper use excludes all liability claims In...

Page 3: ...ng plastic PC ABS and PMMA Protection type IP 20 DIN 40050 Ambient temp 0 40 C Dimensions 172 x 110 x 46 mm Mounting wall mounting mounting into patch panels is possible Display system monitor for sys...

Page 4: ...controller must additionally be supplied from a double pole switch with contact gap of at least 3 mm Please pay atten tion to separate routing of sensor cables and mains cables 1 Unscrew the cross hea...

Page 5: ...neutral conductor N 20 phase L 12 ground clamp The controller is equipped with the RESOL VBus for data transfer with and energy supply to external modules The connection is carried out at the two term...

Page 6: ...adjustment mode scroll down in the display menu and press the forward button 1 for approx 2 seconds after you have reached the last display item If an adjustment value is shown on the display the icon...

Page 7: ...n the toolbar indicate the actual system status toolbar 2 2 System Monitoring display Monitoring Display Symbol normal flashing relay 1 active relay 2 active store maximum limitation active maximum st...

Page 8: ...sensor collector with collector sensor pump store with heat exchanger afterheating with burner symbol temperature sensor 2 3 Flashing codes Pump symbols are flashing during the initialisation phase S...

Page 9: ...the automatic mode with typical settings The pre programmed system scheme is Arr 1 2 select adjustment channel Arr change to the mode see 2 1 select the arrangement via the Arr index number save the a...

Page 10: ...urs relay 2 11 kWh Heat quantity kWh 12 MWh Heat quantity MWh 12 time clock time 11 Arr 1 2 Arrangement DT O x x Switch on temperature difference 12 DT F x x Switch off temperature difference 12 S MX...

Page 11: ...Only if the temperature sensors are connected dis played will S3 and S4 be displayed Display of the current temperature at the sensor TRF temperature return The operating hours counter accumulates the...

Page 12: ...glycol 2 ethylene glycol 3 Tyfocor LS G LS The flow rate as well as the reference sensors S1 flow and S4 return are used for calculating the heat quantity sup plied It is shown in kWh in the channel...

Page 13: ...ler will switch off the solar pump R1 in order to protect the system against overheating collector emergency shutdown The factoring setting is 140 C but it can be changed within the adjustment range o...

Page 14: ...S MX is reached the controller keeps the solar pump running in order to prevent the collector from being overheated The store temperature may increase but only up to 95 C emergency shutdown of the sto...

Page 15: ...ed out 4 1 17 Operating mode HND HND1 HND2 Operating mode OFF relay off flashing AUTO relay in automatic operation ON relay on flashing HAND HND1 HND2 Operating mode Adjustment range OFF AUTO ON Facto...

Page 16: ...VBus 9 10 T2A 100 240V 50 60 Hz IP 20 Temp Sensor Pt1000 The symbol and the are shown Sensor fault An error code instead of a temperature is shown on the sensor display channel 88 8 888 8 Cable is br...

Page 17: ...it no Heat exchanger blocked yes no Clean it Heat exchanger too small yes Repalce with correctly sized one no Plausibility control of the tube collector function Change Ton and Toff correspondingly S...

Page 18: ...o Does the pump start up in manual operation yes No current check fuses replace them and check power supply The adjusted temperature difference for starting the pump is to high choose a value which ma...

Page 19: ...he overvoltage protection RESOL SP1 Sensos Our product range includes high precision platin tempe rature sensors flatscrew sensors outdoor temperature sensors indoor temperature sensors cylindrical cl...

Page 20: ...he Regelungen GmbH This especially applies for copies translations micro films and the storage into electronic systems Editor RESOL Elektronische Regelungen GmbH Important notice We took a lot of care...

Reviews: