Stores are cooled during the night.

Does collector circuit 
pump run during the  
night?

no

yes

Check the controller 
functions

Collector temperature is 
higher at night than am-
bient temperature?

no

yes

Check operation of non 
return valves.

Is trore insulation suffi-
cient?

yes

no

Intensify the insulation.

Is store insulation close 
enough to the store?

yes

no

Replace  or  intesify  the 
insulation.

Are the store connceti-
ons insulated?

yes

no

Insulate connections.

Warm water outflow 
upwards?

no

yes

Change connection and 
let the water flow side-
wards or through a siphon 
(bow  downwards);  less 
store losses now?

The solar circuit pump does not work although the coll-
ector is obviously warmer than the store.

Does the control LED 
flash?

yes

no

Does the pump start up 
in manual operation?

yes

There is no current; check 
fuses / replace them and 
check power supply.

The adjusted tempe rature 
difference for starting the 
pump is too high; choose 
a value which makes more 
sense.

no

Is the current of the 
pump released by the 
controller?

Free  the  pump  using  a 
screwdriver; in operation 
now?

Is the pump defective - 
replace it.

 Are the fuses of the 
controller  o.k.?

Controller seems to be 
defective - replace it.

no

no

no

yes

Replace the fuses.

no

yes

o.k.

Control the return flow 
preventer in warm water 
circulation- o.k.

no

Cleaning or replacement.

yes

 Is the pump stuck?

yes

Summary of Contents for DeltaSol AX

Page 1: ...e Thank you for buying a RESOL product Please read this manual carefully in order to put this controller to the best possible use RESOL DeltaSol AX Mounting Connection Operation Application examples m...

Page 2: ...to avoid danger and damage to people and property Instructions Attention should be paid to the statutory provisions for prevention of industrial accidents to the statutory provisions for environmenta...

Page 3: ...e system is effected by a standard relay changeover contact to which several motors or electrical valves can be connected The controller switches ON if the adjusted temperature difference is exceeded...

Page 4: ...t relay RC 9 neutral contact relay N ground clamp collective terminal strip ac power supply to the clamps 10 neutral conductor N 11 conductor L ground clamp collective terminal strip The guides of the...

Page 5: ...and temperature sensor S2 with the adjusted temperature difference T at the potentiometer C The controller switches over the relay as soon as the temperature reaches the adjusted nominal value the ope...

Page 6: ...flue gas condensation within the boiler By maintaining a minimum temperature limitation in the heat generator a flue gas condensation on the boiler walls is avoided If the minimum temperature is unde...

Page 7: ...r supply available please check the fuses The controller is protected by a fine fuse T4A which can be replaced after having removed the housing and the cover A spare fuse is enclosed on the backside o...

Page 8: ...he temperature difference T between store sensor S1 and heating circuit return sensor S2 exceeds the tempera ture difference adjusted at the controller the 3 way valve is switched over The return temp...

Page 9: ...pump RO is switched on when simultaneously the given minimum temperature is reached or exceeded The temperature difference is reduced Store charge 1 S1 S2 2 3 4 7 RO RC N N L 8 9 10 11 S1 R0 S2 ON OFF...

Page 10: ...nrtol replacement Decalificatiom no Heat exchanger blocked yes no Cleaning Heat exchanger too small yes New calculation of the dimension Change Ton and Toff accordingly Switch on temperature differenc...

Page 11: ...through a siphon bow downwards less store losses now The solar circuit pump does not work although the coll ector is obviously warmer than the store Does the control LED flash yes no Does the pump st...

Page 12: ...e design and the specifications can be changed without advance notice The illustrations can differ from the production model RESOL Elektronische Regelungen GmbH Heiskampstra e 10 D 45527 Hattingen Tel...

Reviews: