Tanks cool down at night.

Does the collector 
circuit pump run during 
the night?

no

yes

Check controller.

At  night,  the  collector 
temperature  is  higher 
than  the  outdoor  tem-
perature.

no

yes

Check  the  non-return 
valve in flow and return 
pipe with regard to the 
functional efficiency.

Sufficient tank insulation?

yes

no

Increase insulation.

Insulation close enough 
to the tank?

yes

no

Replace insulation or in-
crease it.

Are the tank connections 
insulated?

yes

no

Insulate the connections.

Warm water flows 
upwards?

no

yes

Change connection and 
let the water flow side-
wards or through a siphon 
(bow  downwards);  less 
tank losses now?

Does warm water circu-
lation run for a very long 
time?

no

yes

Use the circulation pump         
with timer and switch-off 
thermostat (energy effi-
cient circulation)

The solar circuit pump does not run although the collector 
is significantly warmer than the tank.

Does the operating con-
trol lamp flash?

yes

no

Does the pump start up 
in manual operation?

yes

No current; check fuses 
/ replace them and check 
power supply.

The adjusted temperature 
difference for starting the 
pump is to high; choose a 
value which makes more 
sense.

no

Is the pump current re-
leased by the controller?

yes

Is the pump stuck?

Turn the pump shaft using 
a screwdriver; now pas-
sable?

Pump is defective - re-
place it

Are the controller fuses 
o.k.?

Controller might be de- 
fective - replace it.

no

yes

no

no

yes

Replace the fuses.

Circulation  pump  and 
blocking valve should be 
switched off for one night; 
less tank losses?

yes

no

Check whether the pumps 
of the after-heating cir-
cuit runs at night, check 
non-return valve; problem 
solved?

no

no

yes

o.k.

Check  the  non-return 
valve in warm water cir-
culation – o.k.?

yes

no

Further pumps which are 
connected to the solar 
tank must also be che- 
cked.

The gravity circu lation in 
the circulation line is too 
strong; insert a stronger 
valve in the non-return 
valve or an electric 2-port 
valve behind the circula-
tion pump; in pump ope-
ration, the 2-port valve 
is open, other wise it is 
closed, conect pump and 
2-port valve in parallel; 
activate circulation again!

Clean or replace

a

a

b

b

Summary of Contents for DeltaSol AL

Page 1: ...L product Please read this manual carefully to get the best performance from this unit Please keep this manual carefully RESOL DeltaSol AL Mounting Connection Operation Troubleshooting Examples Manual...

Page 2: ...contents Advice 2 1 Overview 3 2 Installation 4 2 1 Mounting 4 2 2 Electrical connection 5 2 3 Data communication Bus 5 2 4 Terminal allocation 6 3 Operation 6 3 1 Buttons for adjustment 6 3 2 System...

Page 3: ...tem states background illumination and operating control lamp Operation 3 push buttons at the front of the housing and 1 slide switch Functions Differential temperature controller for standard solar t...

Page 4: ...ver Mark the upper fastening point on the wall Drill and fasten the enclosed wall plug and screw leaving the head protruding Hang the housing from the upper fastening point and mark the lower fastenin...

Page 5: ...erminal 12 conductor R1 R normally closed contact 13 conductor R1 A normally open contact 14 neutral conductor N Depending on the product version power supply cable and sensor cables are already conne...

Page 6: ...ards through the display menu or to increase the adjustment values Button 2 is similarly used for scrolling forward and reducing values In order to access the adjustment mode scroll down in the displa...

Page 7: ...e indication is set to F and Ra the units are not displayed 3 2 1 Channel display Channel display 3 2 2 Tool bar The additional symbols in the tool bar indicate the current system state Tool bar 3 2 S...

Page 8: ...ing OK red green flashing initialization phase manual operation red flashing Sensor defective sensor symbol is flashing quickly 3 4 Flashing codes 3 4 2 LED flashing codes 3 4 1 System Screen flashing...

Page 9: ...mperature TST tank temperature TST tank temperature display range 40 260 C 40 500 F Display sensor 3 Shows the current temperature of the additional sensor without control function S3 temperature sens...

Page 10: ...n are used for determining the heat quantity delivered It is shown in kWh in the channel kWh and in MWh in the channel MWh The overall heat quantity results from the sum of both values The accumulated...

Page 11: ...Ra Collector temperature limitation for emergency shutdown of the collector If the adjusted collector emergency shutdown temperature EM is exceeded the controller switches off the solar pump in order...

Page 12: ...cuit will be deactivated Option recooling If the adjusted maximum tank temperature S MX is reached the controller keeps the solar pump running in order to prevent the collector from being overheated T...

Page 13: ...In this adjustment channel the menu language can be chosen dE German En English It Italian Fr French LANG language selection adjustment range dE En It Fr factory setting En Temperature units In this...

Page 14: ...resistance values corresponding to different temperatures are listed yes Check the supply line and reconnect it If a malfunction occurs an error code will be indicated on the display by means of symb...

Page 15: ...Heat exchanger blocked yes no Clean it Heat exchanger too small yes Replace with correctly sized one no Plausibility control of the tube collector function Change Ton and Toff correspondingly Switch o...

Page 16: ...Does the pump start up in manual operation yes No current check fuses replace them and check power supply The adjusted temperature difference for starting the pump is to high choose a value which make...

Page 17: ...the data issued by the controller collector and tank temperature as well as heat quantity produced in the solar system The use of high efficient LEDs and antireflective filter glass assures a high opt...

Page 18: ...DeltaSol AL 18 RESOL 10341 deltasol_al monus indd Notes...

Page 19: ...DeltaSol AL 19 RESOL 10341 deltasol_al monus indd Notes...

Page 20: ...f RESOL Elektronische Regelungen GmbH This especially applies for copies translations micro films and the storage into electronic systems Editor RESOL Elektronische Regelungen GmbH Important notice Th...

Reviews: