Offset adjustment VK4115VE/VK8115VE (see fig. 1 and fig. 2.) 

  Remove cap screw with a Torx T-40 screw driver or 5 mm 

hex key to expose offset adjustment screw. 

  Check gas supply pressure to the appliance using a 

pressure gauge connected to the inlet pressure tap. 

  Start fan and check air flow. 

  Energize both electric operators in order to have gas input 

to burner and ignite boiler. 

  Adjust CO2 % at the desired value at high output with 

throttle adjustment screw. Turn throttle adjustment screw 

clockwise to decrease CO2 %. 

  Operate boiler on low output. (Only modulating 

applications). 

  Adjust CO2 % at the desired value at low output with 

offset adjustment screw. Turn offset adjustment screw 

clockwise to increase CO2 %. 

  Replace cap screw and tighten pressure taps. 

 

Throttle adjustment ..VE types. 

The position of the throttle screw can be found on page 2. 

Apply a screwdriver to turn the screw. 

To decrease the flow, turn screw clockwise. 

To increase flow, turn screw counter-clockwise. 

 

WARNING 

Applied torque may not exceed 8 Ncm 

CHECKOUT 

  After any adjustment check pressure taps and gas 

connections with an approved leak detection fluid for gas 

leakage. 

  After any adjustment set appliance in operation and 

observe a complete cycle to ensure that all burner 

components function correctly. 

 

MAINTENANCE AND SERVICE 

Under normal circumstances no maintenance or service is 

required. 

WARNING 

Do not disassemble the gas control; it contains no 

replaceable components. 
Attempted disassembly or repair may damage the 

gas control 
Screws on the valve that have been sealed must 

never be removed. 

 

increase flow 

(pressure)

 

 

Throttle screw

 

 

decrease flow 

(pressure)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

www.resideo.com 

Ademco 1 GmbH 

Hardhofweg 40 

74821 Mosbach 

Phone: +49 1801 466 388 

[email protected] 

homecomfort.resideo.com

 

@2020 Resideo Technologies, Inc. 

All rights reserved. 

This product is manufactured by 

Resideo Technologies, Inc and its 

affiliates. 

Summary of Contents for VK41 Series

Page 1: ...V B E gas controls perform all the functions required to safely regulate gas flow to the main burner of domestic central heating equipment warm air furnaces back boilers and water heaters Models VK41 0 series line voltage gas control with pilot burner connection two automatic shut off valves and pilot burner connection for direct spark ignition DSI or hot surface ignition HSI applications VK41 5 s...

Page 2: ...e applicable Standard at end outlet M8 x 1 for 4 mm outer diameter tubing M5 x 0 8 3 37 6 mm full thread 94 8 68 3 Side outlet Pressure tab 9 24 34 Cap screw offset adjustment 24 Side outlet optional 84 5 Hole 2 6 mm to connect ignition control Inlet Fig 1 Dimensional drawing standard version Fig 2 Dimensional drawing Quick connect and Throttle versions Pilot outlet M8 x 1 6H for 4 mm tubing 29 Ai...

Page 3: ... indication on the housing is the maximum inlet pressure at which the gas control functions safely Maximum air pressure 8 mbar without outlet gas pressure before ignition 20 mbar with outlet gas pressure present after ignition Offset range 0 4 mbar 0 2 mbar with coils sidewards 0 24 mbar 0 36 mbar with coils on top Inlet End outlet Side outlet Body length mm Flanged Flanged 105 Flanged Flanged 105...

Page 4: ...d with min 6 mm full thread In case of side outlet the three holes for mounting the flange are provided with M5 thread with a minimum of 6 mm full thread Electrical data Coil indication Supply voltage 220 240 Vrac 220 V 50 60 Hz using rectifier 240 V 50 60 Hz using rectifier 110 Vrac 110 V 50 60 Hz using rectifier 24 Vrac 24 V 50 60 Hz using rectifier Electrical connection Molex 1 1 square pin hea...

Page 5: ...o far see table below Otherwise distortion and malfunction could result Pipe size inch Max length of pipe thread mm 3 8 14 1 2 18 6 Apply a moderate amount of good quality thread compound to the pipe or fitting only leaving the two end threads bare If permitted by local safety regulations PTFE tape may be used as an alternative Gas controls for flange connection Insert O ring in the groove of each...

Page 6: ...ling ring connection 1 Fig 10 Pipe dia 15 mm for flat sealing ring connection 23 4 0 15 Fig 11 Pipe end for O ring connection 1 Fig 12 Pipe dia 15 mm for flat sealing ring connection 1 Fig 13 Pipe dia 18 mm for flat sealing ring connection Pilot gas connection at outlet side if applicable Square off the end of tubing and remove burrs Slip compression fitting over 4 mm tubing Insert tubing into aut...

Page 7: ...control seems to operate normally but does not detect flame check for right polarity of power supply line neutral Checking flame current The minimum value should be in accordance with the specified value of the ignition control To check flame current connect a DC micro Ampèremeter between flame sensing wire and flame sensing rod If flame current is insufficient check that flame sensing rod is full...

Page 8: ...on page 2 Apply a screwdriver to turn the screw To decrease the flow turn screw clockwise To increase flow turn screw counter clockwise WARNING Applied torque may not exceed 8 Ncm CHECKOUT After any adjustment check pressure taps and gas connections with an approved leak detection fluid for gas leakage After any adjustment set appliance in operation and observe a complete cycle to ensure that all ...

Reviews: