V404, V504, V524, V804, AND VS824 AUTOMATIC VALVE OPERATORS

95-6999-08

2

GENERAL INSTALLATION 
CONSIDERATIONS

When Installing This Product...

1.

Read these instructions carefully. Failure to follow 

them could damage the product or cause a hazard-

ous condition.

2.

Check the ratings given in the instructions and on 

the product to make sure the product is suitable for 

your application.

3.

Installer must be a trained, experienced service 

technician.

4.

After installation is complete, check out product 

operation as provided in these instructions.

WARNING

Remember that liquefied petroleum (LP) gas is 

heavier than air and will not vent upward 

naturally. Do not light pilot or operate electric 

switches, lights, or appliances until you are sure 

work area is free of gas. Failure to follow these 

instructions may result in an explosion. 

CAUTION

1. Disconnect power supply before beginning 

wiring to prevent electrical shock or equipment 

damage. 

2. Turn gas cock to OFF position.

3. On systems with a 24 V valve operator, NEVER 

apply a jumper across (or short) the valve coil 

terminals, even temporarily. This may burn out 

the heat anticipator in the thermostat. 

4. NEVER connect a millivoltage operator to 

voltage age greater than the operator's rating, 

as this may destroy the control. 

IMPORTANT

In a millivoltage system, the entire system is 

powered by the millivoltage generated by the 

Powerpile generator. It is important to clean and 

scrape all wires before connecting. Solder and 

tape all necessary splices using rosin flux to· 

prevent corrosion.Tighten terminal screws 

firmly. Total control circuit wiring must not 

exceed 30 ft [9 m] of 2-wire, 18 gauge cable or 

50 ft [15 m] of 2-wire, 16 gauge cable.

V524A --

--

3.5

0.87

Limited

Mechanical 

temperature-sensitive 

bulb

C580, C581, V520, V521, 

V530, V531 

V524B 

--

--

11.0

2.7

For LP gas

V404 

Order separate pressure regulator. 

Line voltage 

C580, C581, V400, V401, 

V444, V445, VR400, 

VR401 

V804 

Order separate pressure regulator. 

24 V

C580, C581, VB00, V801, 

V844, V845, VRB00, 

VR801, VR8440, VR8450; 

V814 Operator on V810, 

VR81 0 and V811. 

VS824 

Order separate pressure regulator. 

Powerpile 750 mV 

CS580, CS581, VS820, 

VSB21,VS880,VS897 

Table 2. Replacement Bulb and Bellows Assembly for V504/V524.

Order No.

Description

Temperature Range

F

C

394268-1 

Remote Bulb and Bellows 

50 to 90

10 to 32

394268-2 

Remote Bulb and Bellows 

35 to 75

2to 24

394268-3 

Remote Bulb, Bellows and Remote Dial (self-index) 

50 to 90

10 to 32

394268-4 

Remote Bulb, Bellows and Remote Dial (concealed) 

50 to 90

10 to 32

394268-6 

Remote Bulb, Bellows and Remote Dial (self-index or concealed) 

50 to 90

10 to 32

Table 1. Automatic Valve Operator Application.  (Continued)

Operator 

Model 

Number

Pressure Regulator Setting

Control

Add-on or Replacement 

Operator on:

Min. Rate

Full Rate

Adjustment

in. wc

kPa

in. wc

kPa

Summary of Contents for V404

Page 1: ...ng the valve V504 provides modulating control V524 provides on off control The V504 V524 replacement operator package includes Operator Operator Gasket 394018 Red Knob and Setscrew 394138 Red Knob and Setscrew 394075 Black Knob and Setscrew 388589BF Mounting Screws for Standard Capacity Valves The bulb and bellows assembly must be ordered separately see Table 2 Longer screws are required to mount ...

Page 2: ...ivoltage system the entire system is powered by the millivoltage generated by the Powerpile generator It is important to clean and scrape all wires before connecting Solder and tape all necessary splices using rosin flux to prevent corrosion Tighten terminal screws firmly Total control circuit wiring must not exceed 30 ft 9 m of 2 wire 18 gauge cable or 50 ft 15 m of 2 wire 16 gauge cable V524A 3 ...

Page 3: ...regulator gasket 3 Remove old operator from valve body Discard old operator and gasket REMOVING ADAPTER CASTING FROM MANUAL VALVE 1 Remove pressure regulator or blank cover plate Save regulator or cover plate for reassembly to operator Save gasket for blank cover plate discard pressure regulator gasket 2 Remove adapter casting from valve body See Figs 1 and 2 Discard casting and gasket INSTALLING ...

Page 4: ...s hole See Fig 4 5 If control has pressure regulator choose the cor rect new pressure regulator gasket see Fig 3 Press gasket into circle on operator casting align ing tab with recess in casting See Fig 4 Position regulator over gasket and fasten with two screws used originally For V5307 put the longer screw provided with the regulator in the outside corner hole Tighten screws evenly and securely ...

Page 5: ...splices using rosin flux to prevent corrosion Tighten terminal screws firmly Total control circuit wiring must not exceed 30 ft 9 m of 2 wire 18 gauge cable or 50 ft 15 m of 2 wire 16 gauge cable 1 Install millivoltage thermostat limit controller if required and Powerpile generator according to manufacturer s installation instructions 2 After Powerpile generator is installed route gener ator lead ...

Page 6: ... 32 UNC 2 3 8 in long screws obtain locally for high capacity valves 10 If the bulb and bellows assembly is new follow the instructions provided with the assembly to install the bulb and the remote dial assembly if used Fig 9 Form capillary smoothly and without crimping to fit in hole in operator Fig 10 Mounting the V504 and V524 operator on a standard capacity valve Cabinet mounted dial shown Fig...

Page 7: ... place 6 If using 394138 Dial insert 1 4 in rod obtain locally into end of dial Align hole in end with hole in dial sleeve Fasten with cotter pin 7 Turn dial to desired setting making sure the cali bration knob is turning with the dial If not repeat steps 2 5 Fig 12 Calibrating V504 V524 with dial on operator V504 V524 WITH DIAL MOUNTED ON CABINET 1 Light pilot as described under Pilot Lighting Pr...

Page 8: ...naturally Do not light pilot or operate electric switches lights or appliances until you are sure work area is free of gas Failure to follow these instructions may result in an explosion 2 Turn the Lite Rite knob to PILOT depress it com pletely and light the pilot burner while holding it down Hold the knob down about one minute If the pilot goes out when the knob is released repeat steps 1 and 2 3...

Reviews: