resideo SmartValve SV9410 Installation Instructions Manual Download Page 9

SV9410/SV9420; SV9510/SV9520; SV9610/SV9620 SMARTVALVE™ SYSTEM CONTROLS

9

69-1058—05

Fig. 10. SV9410/SV9420; SV9510/SV9520; 

SV9610/SV9620 typical wiring connections 

direct to the system thermostat.

STARTUP AND CHECKOUT

Ignition System Control Switch 
Settings

Ignition system control switch settings are as follows:

OFF prevents main gas flow through the ignition 

system control.

ON permits gas to flow through the control body. At 

the appropriate time in the appliance operation, main 

gas can flow to the main burner.

NOTE:

Controls are shipped with the ignition system 

control switch in the ON position. If the 

appliance is operated with the ignition system 

control switch in the OFF position, the system 

will respond as if the air proving switch is stuck 

in the no airflow position.

Turn on Main Burner

Follow the instructions provided by the appliance 

manufacturer or turn up the thermostat to call for heat.

Perform Gas Leak Test

WARNING

Fire or Explosion Hazard.

Can cause property damage, severe injury or 

death.

Check for gas leaks with soap and water solution 

any time work is done on a gas system.

CAUTION

Equipment Damage Hazard.

Liquid can damage the SmartValve™ Control.

Do not spray soap and water solution on the 

SmartValve™ housing. Do not use an excessive 

amount of soap and water solution to perform the 

gas leak test. These can damage the control.

Gas Leak Test

1.

Paint pipe connections upstream of the ignition 

system control with rich soap and water solution. 

Bubbles indicate a gas leak.

2.

If a leak is detected, tighten the pipe connections.

3.

Stand clear of the main burner while lighting to 

prevent injury caused from hidden leaks that could 

cause flashback in the appliance vestibule. Light 

the main burner.

4.

With the main burner in operation, paint the pipe 

joints (including adapters) and the control inlet and 

outlet with rich soap and water solution.

5.

If another leak is detected, tighten the adapter 

screws, joints, and pipe connections.

6.

Replace the part if a leak cannot be stopped.

Check and Adjust Gas Input and 
Burner Ignition

CAUTION

Equipment Damage Hazard.

Exceeding input ratings can damage the controls.

Do not exceed input rating stamped on appliance 

nameplate, or manufacturer’s recommended 

burner orifice pressure for size orifice(s) used. 

Make certain primary air supply to main burner is 

properly adjusted for complete combustion. 

Follow instructions of appliance manufacturer.

Checking Gas Input by Clocking Gas Meter:

Make certain there is no gas flow through the meter other 

than to the appliance being checked. Other appliances 

must remain off with the pilots extinguished (or that 

consumption must be deducted from the meter reading). 

Convert flow rate to Btuh as described in form 70-2602, 

Gas Controls Handbook, and compare to Btuh input 

rating on appliance nameplate.

Checking Gas Input with Manometer:

Make sure the ignition system control is in the OFF 

position before removing outlet pressure tap plug to 

connect manometer (pressure gauge). Also move the 

ignition system control switch to the OFF position when 

C1

C2

C3

LOAD

COMMON

THERMOSTAT

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD 
PROTECTION AS REQUIRED.

CONNECT 120V (HOT) LEAD AS SHOWN.

APPLIANCE CHASSIS MUST HAVE RELIABLE CONNECTION TO
 EARTH GROUND.

DATA AND R LINES MUST BE CONNECTED TO W ON THERMOSTAT 
FOR PROPER SYSTEM OPERATION.

THERMOSTAT MUST HAVE ZERO OFF-STATE CURRENT DRAW. 
MECHANICAL SWITCH THERMOSTATS RECOMMENDED.  TRIAC
SWITCH THERMOSTATS OR POWER-STEALING THERMOSTATS 
ARE NOT RECOMMENDED.

IN THIS APPLICATION, POSTPURGE FUNCTION IS NOT AVAILABLE
AND THE LED FUNCTIONS ONLY DURING A CALL FOR HEAT.

1

4

5

6

6

3

2

2

5

4

1

M12173D

AIR

PROVING

SWITCH

NEUTRAL

HOT

L2

L1
(HOT) 

TO
120 VAC, 60 HZ 
POWER SUPPLY

ROLL-OUT

SWITCH

LIMIT

SWITCH

COMBUSTION
AIR BLOWER

R

W

R

C

AIR

DATA

40 VA
TRANSFORMER

L1

L2

SV9410/SV9420;
SV9510/SV9520;
SV9610/SV9620

HOT 
SURFACE 
IGNITER

FLAME ROD

3

AUXILIARY
LIMIT SWITCH
(OPTIONAL)

1

1
2

5
6

7
8

1

2

2

3

3

3

4

4

4

Summary of Contents for SmartValve SV9410

Page 1: ...g furnaces rooftop furnaces boilers unit heaters infrared heaters water heaters and commercial cooking appliances The specific application of the SmartValve System is the responsibility of the appliance manufacturer See Table 2 for temperature ranges and regulator types Line voltage polarity sensing models monitor the line voltage input connection to assure line voltage polarity is correct If line...

Page 2: ...atural Gas to LP 393691 Conversion Kit LP to Natural Gas 394588 Conversion Kit Two Stage N Q suffix Conversion Kits Natural Gas to LP 396021Conversion Kit LP to Natural Gas 396025 Conversion Kit WARNING Fire or Explosion Hazard Can cause property damage severe injury or death Do NOT attempt to convert step opening models SV9510P SV9520P SV9610P SV9620P Always change the main burner orifices when c...

Page 3: ...he control can wear out more quickly Perform a monthly checkout Water or Steam Cleaning If a control gets wet replace it If the appliance is likely to be cleaned with water or steam protect cover the control and wiring from water or steam flow Mount the control high enough above the bottom of the cabinet so it does not get wet during normal cleaning procedures High Humidity or Dripping Water Dripp...

Page 4: ... contamination of ignition system control CAUTION Equipment Damage Hazard Improper wiring can damage equipment Never apply a jumper across or short the thermostat 24V hot or 24V common terminal in the SV9410 SV9420 SV9510 SV9520 SV9610 SV9620 wiring harness This can burn out the heat anticipator in the thermostat or damage the system transformer Follow the appliance manufacturer instructions if av...

Page 5: ... the seals until ready to connect the piping Install Piping to Control All piping must comply with local codes and ordinances or with the National Fuel Gas Code ANSI Z223 1 NFPA No 54 whichever applies Tubing installation must comply with approved standards and practices 1 Use new properly reamed pipe free from chips If tubing is used make sure the ends are square deburred and clean All tubing ben...

Page 6: ...he appliance manufacturer instructions All wiring must comply with applicable electrical codes and ordinances WARNING Electrical Shock Hazard Can cause severe injury death or property damage Disconnect power supply before making wiring connections to prevent electrical shock or equipment damage 1 Check the power supply rating on the ignition system control and make sure it matches the available su...

Page 7: ...d be less than ten volts Fig 6 Testing for ground commonality Fig 7 SV9410 SV9420 SV9510 SV9520 SV9610 SV9620 typical wiring connections in fan assisted warm air furnace with ST9160 Fan Board M17570 MULTIMETER LESS THAN 10V APPLIANCE CHASSIS L1 L2 120 VAC C1 C2 C3 CONT EAC HEAT HUM M2 MOTOR PARKING TERMINALS M1 L1 NEUTRALS 24 VAC R W C COM XFMR COOL LOAD COMMON POWER SUPPLY PROVIDE DISCONNECT MEAN...

Page 8: ...BOARD APPLIANCE CHASSIS MUST HAVE RELIABLE CONNECTION TO EARTH GROUND 1 2 3 2 3 AUXILIARY LIMIT SWITCH OPTIONAL 1 1 5 6 7 8 1 2 2 2 1 3 5 4 6 2 3 3 3 4 4 4 P1 L1 L2 M12397C DATA R 24V THERMOSTAT C R8285D CONTROL CENTER POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED CONNECT THE 120V HOT LEAD AS SHOWN DATA AND R LINES MUST BE CONNECTED TO AQUASTAT CONTROL FOR PROPER SYSTEM...

Page 9: ...f another leak is detected tighten the adapter screws joints and pipe connections 6 Replace the part if a leak cannot be stopped Check and Adjust Gas Input and Burner Ignition CAUTION Equipment Damage Hazard Exceeding input ratings can damage the controls Do not exceed input rating stamped on appliance nameplate or manufacturer s recommended burner orifice pressure for size orifice s used Make cer...

Page 10: ...eplace the ignition system control Otherwise take the necessary steps to provide proper gas pressure to the control NOTE If the burner firing rate is above the capacity at 1 in wc pressure drop of the control see Table 3 for capacities it may not be possible to deliver the desired outlet pressure This is an application issue not a control failure Take whatever steps are required to correct the sit...

Page 11: ... Hazard Can cause severe injury death or property damage Do not disassemble the ignition system control it contains no replaceable components Attempted disassembly or repair can damage the ignition system control CAUTION Equipment Damage Hazard Improper wiring can damage the equipment 1 Do not apply a jumper across or short the thermostat 24V hot or 24V common terminal in the SV9410 SV9420 SV9510 ...

Page 12: ...nnot reach your gas supplier call the fire department 2 The ignition system control must be replaced in event of any physical damage tampering bent terminals missing or broken parts stripped threads or evidence of exposure to heat IMPORTANT Follow the operating instructions provided by the manufacturer of your heating appliance The information below describes a typical ignition system control appl...

Page 13: ...R PROVING SWITCH PROVED CLOSED WITHIN 30 SECONDS COMBUSTION AIR BLOWER OFF MAIN VALVE CLOSES COMBUSTION AIR BLOWER OFF AFTER POST PURGE 1 HOUR AUTO LOCKOUT RESET DELAY MAIN VALVE CLOSES COMBUSTION AIR BLOWER OFF AFTER POST PURGE CIRCULATING AIR FAN OFF AFTER DELAY WAIT FOR NEXT CALL FOR HEAT FAILED TRIALS FOR IGNITION LESS THAN FOUR DURING THIS IGNITION SEQUENCE NO NO YES YES YES NO NO MAIN VALVE ...

Page 14: ... If control system includes ST9160 Electronic Fan Timer the heat speed circulating air fan will be energized until the limit string resets 1 Open manual reset or auto reset burner rollout switch 2 Open high temperature or auxiliary limit switch 3 Limit and rollout switch wiring in good condition and securely connected 5 Flashes Flame signal sensed out of proper sequence Combustion air blower is en...

Page 15: ...s 5 on this call for heat last failure was Limit Circuit Opened During Run 1 Open high temperature or auxiliary limit switch 2 Open manual reset or auto reset burner rollout switch in the limit circuit 3 Limit and rollout switch wiring in good condition and securely connected 4 Circulating air fan wiring and operation 5 Obstructions in appliance or duct work that prevent proper circulation through...

Page 16: ... ignition trial A total of four ignition trials will be attempted before the system goes to lockout 1 Line voltage to L1 terminal of ST9160 or Terminal Board must be 120 volts with reference to appliance chassis 2 Appliance must be reliably connected to earth ground 3 Combustion air blower moving main burner flame away from flame sense rod 4 Inlet gas pressure too low for proper flame sensing 5 Fl...

Reviews: