EN
EN1H-1375GE23 R1020 - Translation of original
19
Resideo Technologies
Danger
Filling wrong gas in expansion vessel
Danger of poisoning!
Only fill the pressure pad with nitrogen.
Caution
Precharge pressure too high
Danger of damaging the tank!
Observe the values as stated by the manufacturer of the tank
(refer to type label or the tank manual).
The precharge pressure for the pressure vessel should be set to a value that
is lower than the programmed switch-on pressure.
This setting can be made with a valve under the cover hoodon the top of the
tank.
Example: Precharge pressure 10% below the switch-on pressure
Precharge pressure of the membrane pressure vessel p = 0.9 x p
E
p
E
= switch-on pressure of the compact booster unit
Recommendation
These are average values. Experiments conducted on tanks have shown
that the best storage volumes were achieved for pressures >3bar with a
factor of 0.9 and pressures of <3bar with a factor of 0.8.
Example:
p
E
= 5 bar: Precharge pressure 5 x 0.9 = 4.5 bar
p
E
= 2 bar: Precharge pressure 2 x 0.8 = 1.6 bar
8.3.2
Cleaning the dirt trap
1.
Remove the lid
2.
Take out the sieve
-
blow out if necessary
3.
Insert sieve
4.
Replace lid
-
use new seal if necessary
8.3.3
Checklist for maintenance work
9.
Troubleshooting
During the warranty period consult the manufacturer before performing
maintenance work on the system (only work that is required for start-up
and maintenance).
Our customer service department is at your service. Failure to comply
will lead to loss of any liablity claims.
9.1
Possible malfunctions / Errors
Possible malfunctions / Errors
A
The pump shuts off after brief manual operation. Water shortage is in-
dicated by red light.
B
The compact booster unit does not start.
C
The pump is running but doesn´t pump water.
D
The compact booster unit doesn`t pump enough.
E
The pump pressure is too low.
F
Pump pressure is too high.
G
The floating ring seal leaks.
H
Overheating of the motor/pump.
I
The motor protection switch is activated. The yellow light is on.
J
The pump does not shut off.
K
The pump operates too often (more than 30 times per hour).
L
Green and yellow lights are both on and the pump is running.
M
Yellow and red lights are on
N
Overflow of the dewatering connection
Work steps
Interval
Setting the precharge pressure for the membrane pressure
vessel
yearly
Cleaning the dirt trap
yearly