12
8
.
Bypass range setting
(Under AC mode, this menu is displayed before turning the UPS on)
A. To protect the load, the function
of bypass auto-transfer is
activated only when the AC main
voltage is within the setting
range of LO(low) and HI(high).
Once AC main voltage exceeds the
Setting range, the bypass output
will be closed automatically to
protect the load.
In this screen, press Enter-key
to enter the following steps
for LO/HI voltage setting.
B. The cursor (
→
) will pop up to
indicate the item newly selected.
Press Enter-key
to get the item of
LO or HI range the user wants to
adjust.
Use Up
or Down-key
to adjust
the voltage (changing 1V by every
press). LO (low rang) :176V+/-20V,
HI(high range):253V+/- 20V).
C. Once the value is confirmed, press
Enter-key
again to save the data.