4. INSTALLATION
Installation and wiring must be performed in accordance with the local
electric code and the following instructions by professional personnel.
For safety, please cut off the mains power switch before installation.
The battery breaker also needs to be cut off.
1.
Open the terminal block cover located on the rear panel of the
UPS
,
please refer to the appearance diagram.
2.
For 6K UPS, it is recommended to select the UL1015 10AWG
(
6mm2
)
wire or other insulated wire which complies with AWG
Standard for the UPS input and output wirings.
3.
For 10K UPS, it is recommended to select the UL1015 8AWG
(10mm2
)
wire or other insulated wire which complies with AWG
Standard for the UPS input and output wirings.
4.
To connect the load with the UPS, please turn off all the loads first,
then perform the connection and finally turn on the loads one by one.
5.
Connect the input and output wires to the corresponding input and
output terminals according to the following diagram
Note: you must make sure that the input and output wires and
the input and output terminals are connected tightly.
6.
After having completed the installation, make sure the wiring is
correct.
7.
If the UPS connect external batteries, make sure the battery polarity
and voltage are correct.
Note: Do not use the wall receptacle as the input power source for
the UPS, as its rated current is less than the UPS’s maximum input
current. Otherwise the receptacle may be burned and destroyed.