Charging voltage is
too high
1. Check if the
connection between
battery and inverter is
well.
2. Make sure battery
condition is ok.
3. Then, restart the
inverter.
4. If error message
remains, please contact
your installer.
22
Overload fault
1. Remove exessive
loads. Be sure that total
connected loads are less
than maximum power
consumption this
inverter can support.
2. Then, restart the
inverter.
23
Battery
disconnected
1. Check if battery cable
is connected firmly.
2. If error message
remains, please contact
your installer.
24
Inverter current is
too high for a long
time
1. Remove exessive
loads.
2. Then, restart the
inverter.
25
Short circuited on
inverter output
1. Turn off the inverter.
2. Disconnect AC circuit
breaker first. Then,
disconnect DC circuit
breaker and then
disconnect the loads.
3. Please check if load
circuit is ok. After
removing the error, turn
on the PV DC breaker
and battery breaker.
4. Turn on the inverter.
5. If error message
remains, please contact
your installer.
26
Fan fault
1. Please check if fans
are runing ok.
2. If fans are runing ok,
please shut down
inverter first and then,
restart it.
3. If fans are stop runing
or error message
remains after restart the
inverter, please contact
your installer.
27
OP Current Sensor
fault
1. Shut down the
inverter completely.
2. Restart the inverter to
see if it’s ok.
3. If error message still
remains, please contact
your installer.
28
Charger failure
1. Shut down the
inverter completely.
2. Restart the inverter to
see if it’s ok.
3. If error message still
remains, please contact
your installer.
29
Version mismatch
between controller
board and power
board
1. Shut down the
inverter completely.
2. Restart the inverter to
see if it’s ok.
3. If error message still
remains, please contact
your installer.
30
Reverse connection
of input and output
wires
1. Shut down the
inverter completely.
2. Check if grid wires are
connected to AC output
terminals.
3. If mis-connected,
re-connect it correctly.
And turn on the inverter
again.
4. If error message still
remains, please contact
your installer.
31
43
44