6. Trouble Shooting 

Use the table below to solve minor problems. 

Problem 

LCD/LED/Buzzer 

Explanation / Possible cause 

What to do 

When power fails, 
the backup time is 
shorten. 

Battery low alarm 
issue quickly. 

Battery voltage is too low. 

Charge  the  unit  at  least  8 
hours. 

Battery  capacity  is  not  full  even 
after charge the unit for at least 8 
hours. 

Check  the  date  code  of  the 
battery.  If  the  batteries  are 
too old, replace the batteries. 

Mains exist but the 
unit works in 
battery mode. 

Input voltage is 
displayed as 0 on the 
LCD and green LED is 
flashing. 

Input protector is tripped 

Check if AC breaker is tripped 
and  AC  wiring  is  connected 
well. 

Green LED is flashing. 

Insufficient quality of AC power. 
(Shore or Generator) 

1. Check if AC wires are too 
thin and/or too long. 
2. Check if generator (if 
applied) is working well or if 
input voltage range setting is 
correct. (Narrow

Æ

Wide) 

No LED display on 
the front panel 
when the utility 
power is normal. 

No LED display. 

Battery is not connected well. 

Check the external battery 
cable and terminal. Make sure 
all the battery connections to 
the unit are all correct. 

Battery defect.   

Replace the batteries. 

Buzzer beeps 
continuously and 
red LED is on. 

Fault code 00 

Output short circuited.   

Check if wiring is connected 
well and remove abnormal 
load.   

Fault code 01 

Overload error. The inverter is 
overload 110% and time is up. 

Reduce the connected load by 
switching off some 
equipment. 

Fault code 03 

Output voltage too high 

Return to repair center. 

Fault code 05 

Fan fault 

Replace the fan. 

Fault code 06 

Internal temperature of inverter 
component is over 100°C. 

Check whether the air flow of 
the unit is blocked or whether 
the ambient temperature is 
too high. 

Fault code 08 

Battery is over-charged.   

Return to repair center. 

The battery voltage is too high. 

Check if spec and quantity of 
batteries are meet 
requirements. 

If there is any abnormal situations occur, which doesn't list above, please call the service people immediately 
for professional examine. 

 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for Jaguar 1.2K

Page 1: ...USER MANUAL J A G U A R B AT T E RY B O X 1 2kVA 900W 2 4kVA 1600W s a l e s p o w e r p r o v i d e r c o z a w w w p o w e r p r o v i d e r c o z a ...

Page 2: ...Table of Contents 1 Introduction 1 2 Important Safety Warning SAVE THESE INSTRUCTIONS 1 3 Product Overview 3 4 Installation 3 5 Operation 5 6 Trouble Shooting 10 7 Specifications 11 ...

Page 3: ... cover or obstruct the cooling fan CAUTION Do not operate the inverter if it has received a sharp blow been dropped or otherwise damaged in any way If the inverter is damaged called for an RMA Return Material Authorization WARNING There are no user replaceable parts inside of the inverter Do not attempt to service the unit yourself WARNING It s very important for system safety and efficient operat...

Page 4: ...ke or allow a spark or flame in vicinity of a battery CAUTION If a remote or automatic generator start system is used disable the automatic starting circuit or disconnect the generator to prevent accident during servicing ...

Page 5: ...automatically charge the internal battery even though the unit is off Connect to Battery Pack 1 2k Model Follow below steps to connect battery pack Step 1 Take out top case by removing screws as shown below chart 1 Power switch 2 Status indicator 3 Charging indicator 4 Fault indicator 5 Function buttons Please see the Operation section for the details 6 LCD display 7 AC input 8 AC output receptacl...

Page 6: ...t to connect battery pack Step 3 Insert battery pack inside of cabinet Assemble top case to original position 2 4k Model Follow below steps to connect battery pack Step 1 Take out top case by removing screws as shown below chart ...

Page 7: ...e power switch again the unit will be turned off LED Indicators Function Keys Audible Alarms There are three indicators in the front panel of the unit LED Indicator Messages Green Solid On Output is available in bypass mode Flashing Output is powered by battery in inverter mode Green Solid On Battery is not charging Flashing Battery is charging Red Solid On Fault mode Flashing battery low or overl...

Page 8: ...mation Indicates the Battery level by 0 24 25 49 50 74 and 75 100 in battery mode charging status in line mode In AC mode it will present battery charging status Status Battery voltage LCD Display Constant Current mode Constant Voltage mode 11Vdc pcs 4 bars will flash in turns 11Vdc 11 5Vdc pcs Bottom bar will be on and the other three bars will flash in turns 11 5Vdc 12 5Vdc pcs Bottom two bars w...

Page 9: ...mode Escape 01 AC input voltage range Wide default If selected acceptable AC input voltage range will be within 90 280VAC Narrow If selected acceptable AC input voltage range will be within 170 280VAC 02 Battery type AGM Default Flooded User defined 03 Max AC charging current 20A default 10A 04 Bulk charging C V voltage voltage 12V model default setting 14 1V 24V model default setting 28 2V If sel...

Page 10: ...ill be fixed to setting value no matter what percentage of load is connected Display Setting The LCD display information will be switched in turns by pressing SCROLL key The selectable information is switched as below order input voltage battery voltage output voltage load percentage load in Watt and main CPU Version Selectable information LCD display Selectable information LCD display Input volta...

Page 11: ...e Mode The unit will provide output power from the mains It will also charge the battery at line mode Charging by utility Battery Mode The unit will provide output power from battery Power from battery only Fault Reference Code Fault Code Fault Event Icon on Fault Code Fault Event Icon on 00 Output short circuit 05 Fan locked 01 Over load time out 06 Over temperature 03 Output voltage too high 08 ...

Page 12: ...on the front panel when the utility power is normal No LED display Battery is not connected well Check the external battery cable and terminal Make sure all the battery connections to the unit are all correct Battery defect Replace the batteries Buzzer beeps continuously and red LED is on Fault code 00 Output short circuited Check if wiring is connected well and remove abnormal load Fault code 01 ...

Page 13: ... 10A 13A Maximum Output Fault Current 6 9A 13 6A Transfer Time 20 ms typical Waveform Simulated Sine Wave BATTERY Battery Type and Numbers 12 V 100Ah x 1 12 V 100Ah x 2 Maximum Battery Discharging Current 76A 76A Floating Charge Voltage 13 7 VDC 0 5 VDC 27 4 VDC 1 VDC Maximum AC Charging Current 10 A or 20 A 10 A or 20 A PHYSICAL Dimension DxWxH mm 393 250 459 345 400 450 Net Weight kgs 40 5 75 8 ...

Page 14: ......

Reviews: