7.2.1.3 • CO
2
control
In this menu you can set the threshold of the CO
2
-registration of the sensor controller. Default
the value will always be set on 1000 ppm (parts per million). Once the CO
2
-concentration,
of the room where the controller is situated, exceeds this value, the Endura Twist will adjust
the ventilation level gradually. The higher the transgression, the higher the ventilation level.
If you raise the threshold to a higher value, the extra ventilation will be delayed. To ensure a
good air quality, we advise not to raise the threshold.
- If CO
2 room
< CO
2 threshold
– hysteresis/2
➔
L1
- If CO
2 threshold
– hysteresis/2 ≤ CO
2 room
≤ CO
2 threshold
+ hysteresis/2
➔
L2
- If CO
2 room
> CO
2 threshold
+ hysteresis/2
➔
L3
Choose ‘CO
2
Control’ in the system menu and confirm with
■
.