12
Powering Appliances
CHARGE
FAULT
ENT
DOWN
UP
SET
AC/INV
CHARGING
LI
INPUT
100%
25%
CHARGE
FAULT
ENT
DOWN
UP
SET
AC/INV
CHARGING
LI
INPUT
BYPASS
100%
25%
4.1.4
Powered by Batteries
Powered by Bypass AC
The Solar Inverter Charger
AC/INV Indicator lights up
yellow when the appliances
are powered by bypass AC.
The Solar Inverter Charger
AC/INV Indicator flashes
yellow when the appliances
are powered by the batteries.
z
Please close the Viewing Window and tighten the captive screws after completing the steps
above.
z
When the 20A AC Outlet is used to power appliances, the continuous loads shall not exceed 16A,
and the noncontinuous loads shall not exceed 20A.
z
When the 30A AC Outlet is used to power appliances, the continuous loads shall not exceed 24A,
and the noncontinuous loads shall not exceed 30A.
z
If the appliances are powered by bypass AC from a 20A outlet, the continuous loads shall not
exceed 16A, and the noncontinuous loads shall not exceed 20A, no matter which AC outlet on
LYCAN is used.
z
If the appliances are powered by bypass AC from a 15A outlet, the continuous loads shall not
exceed 12A, and the noncontinuous loads shall not exceed 15A, no matter which AC outlet on
LYCAN is used.
Temporary Power Supply
Off-Grid Living
Emergency Backup