ii 

Front Panel Rotary Switch (Sensitivity) 

The eight-position rotary switch selects one of eight (8) sensitivity levels as shown in the table below.  0 is 
lowest and 7 is highest, with normal (factory default) being 3.  Use the lowest sensitivity setting that will 
consistently detect the smallest vehicle that must be detected.  Do not use a sensitivity level higher than necessary. 

Position 

3 * 

-

L/L 

1.28% 

0.64% 

0.32% 

0.16% * 

0.08% 

0.04% 

0.02% 

0.01% 

Current 

Draw 

3.3 mA 

3.5 mA 

3.8 mA 

4.6 mA * 

5.0 mA 

5.1 mA 

5.2mA 

7.0 mA 

*  Factory default setting.

 

iii 

Front Panel DIP Switches 

Switch 

ON 

OFF

 

Factory Default

 

Frequency 

(See table in Frequency section) 

OFF 

OFF 

Limited Presence 

True Presence

TM 

OFF 

Sensitivity Boost 

No Boost 

OFF 

Two Second Delay 

No Delay 

OFF 

Fail-Safe Output A 

Fail-Secure Output A 

OFF 

Exit Pulse Output B 

Entry Pulse Output B 

OFF 

Presence Mode Output B 

Pulse Mode Output B 

OFF 

Frequency  (DIP Switches 1 and 2) 

In situations where loop geometry forces loops to be located in close proximity to one another, it may be necessary 
to select different frequencies for each loop to avoid loop interference, commonly known as crosstalk.  DIP 
switches 1 and 2 can be used to configure the detector to operate at one of four frequencies corresponding to 

Low

Medium / Low

Medium / High

, and 

High

 as shown in the table below. 

NOTE:

  After changing any frequency DIP switch setting(s), the detector must be reset by momentarily changing 

one of the other DIP switch positions. 

Switch 

Frequency 

Low (0)  Medium / Low (1) *  Medium / High (2)  High (3) 

ON 

OFF * 

ON 

OFF 

ON 

ON * 

OFF 

OFF 

*  Factory default setting. 

Presence Hold Time  (DIP Switch 3) 

Output A always functions as a presence output.  DIP switch 3 can be used to select one of two presence hold 
times; Limited Presence or True Presence

TM

.  Both modes provide a detect  output when a vehicle is present 

in the loop detection zone.  True Presence

TM

  is selected when DIP switch 3 is 

OFF

.  If DIP switch 3 is 

ON

Limited Presence is selected.  Limited Presence will typically hold the detect output for one to three hours.  True 
Presence

TM

  will hold the detect output  as long as the vehicle is present in the loop detection zone provided that 

power is not interrupted, and  the detector is not reset.  TruePresence

TM

  time applies only for normal size 

automobiles and trucks and for normal size loops (approximately 12 ft

2

 to 120 ft

2

).  The factory default setting is 

OFF

 (True Presence

TM

 Mode). 

Sensitivity Boost  (DIP Switch 4) 

DIP switch 4 can be turned 

ON

  to increase sensitivity during the detect period without changing the sensitivity 

during the no detect period.  The boost feature has the effect of temporarily increasing the sensitivity setting by up 
to two levels.  When a vehicle enters the loop detection zone, the detector automatically boosts the sensitivity level.  
As soon as no vehicle is detected, the detector immediately returns to the original sensitivity level.  This feature is 
particularly useful in preventing dropouts during the passage of high  bed vehicles.  The factory default setting is 

OFF

 (no Sensitivity Boost). 

Output Delay  (DIP Switch 5) 

A two second delay of Outputs A and B can be activated by setting DIP switch 5 to the 

ON

 position.  Output delay 

is the time the detector outputs are delayed after a vehicle first enters the loop detection zone.  If the two second 
Output Delay feature is activated, the outputs will only be turned on after two seconds have passed with a vehicle 
continuously present in the loop detection zone.  If the vehicle leaves the loop detection zone during the two 
second delay interval, detection is aborted and the next vehicle to enter the loop detection zone will initiate a new 
full two second delay interval.  The detector provides an indication that a vehicle is being detected but that the 
outputs are being delayed, by flashing the front panel 

DET

 (Detect) LED at a four Hz rate with a 50% duty cycle.  

The factory default setting is 

OFF

 (no Output Delay). 

Fail-Safe / Fail-Secure  (DIP Switch 6) 

When DIP switch 6 is in the 

ON

 position, the detector will operate in Fail-Safe mode when a loop fault condition 

exists.  If a loop fault condition occurs while Fail-Safe mode is selected, Output A will activate (Relay A Normally 
Open contacts closed, Relay A Normally Closed contacts open or Solid State Output A sourced to ground).  When 
DIP switch 6 is in the 

OFF

  position, the detector will operate in Fail-Secure mode when a loop fault condition 

exists.  If a loop fault condition occurs while Fail-Secure mode is selected, Output A will not activate (Relay A 
Normally Open contacts open, Relay A Normally Closed contacts closed or Solid State Output A not sourced to 