OPERATING INSTRUCTIONS 

General 

The  Model BX-LP is a low power loop detector for solar or low power installations.  To minimize power 
consumption the detector’s 

DET

  (Detect)  LED  will only light  during the three minutes immediately following 

initial power-up or detector reset.  After the three minutes the 

DET

 (Detect) LED is will not light, but the detector 

continues to function normally. 

Please verify source voltage before applying power.

  The model designation indicates the input power required 

and output configuration for the detector as follows: 

Model BX-LP-xx

 

 

Blank = 12 VDC with Relay Outputs 

 

24

 = 24 VDC with Relay Outputs 

 

SS

 = 12 VDC / 24 VDC with Solid State Outputs 

The input voltage range, and current consumption  figures for the various versions of the detector are listed in the 
table below. 

 

Relay Outputs

 

Solid State Outputs 

Model 

BX-LP 

BX-LP-24 

BX-LP-SS 

Input Voltage 

10 to 14 VDC 

20 to 28 VDC 

10 to 28 VDC 

Current 

Consumption* 

3.3 to 7.0 mA in No Detect State  

35 to 40 mA in Detect State 

(Output A Presence / Output B Pulse) 

60 to 65 mA in Detect State 

(Output A Presence / Output B Presence) 

3.3 to 7.0 mA** 

 

NOTES: 

*  Current consumption is a function of the sensitivity.  See the table in the "Front Panel Rotary 
Switch (Sensitivity)" section for actual current draw at each of the sensitivity settings. 

**  Add 6.0 mA for each lit (DET and/or Fail) LED. 

II

 

Indicators and Controls 

Detect / Fail LEDs 

The detector has two red LED indicators that are used to provide an indication of the detector’s output state 
and/or loop failure conditions.  The 

DET

  (Detect)  LED is only activated during the three minutes immediately 

following initial power-up or detector reset.  The table below lists the various indications and their meanings. 

Status 

DET (Detect) LED

 

FAIL (Loop Fail) LED 

Off 

Output(s) Off 

Loop OK 

On 

Output(s) On 

N/A 

Flash 

4 Flashes per Second 

(50% duty cycle) 

Two second timing delay activated 

1 Hz (50% duty cycle) 

Loop Failure 

One flash every five seconds 

Prior Loop Failure 

NOTE: 

The 

DET

  (Detect) LED will only turn on or flash during the three minutes 

immediately following initial power-up or reset of the detector.  After the three 
minutes immediately following initial power-up or detector reset, the Detect 
LED is deactivated, but the detector continues to function normally.  The 

FAIL

 

(Loop Fail) LED provides the indications shown above at all times. 

MODEL BX-LP SERIES 