E-STOP (9W 'D' plug)
The E-STOP connector is provided to allow connection of external emergency stop and reset switches into the SPA3-2. The machine
manufacturer or product installer must perform a risk assessment (refer to BS EN ISO13849-1:2015 (or current version) para. 5.2.2.) to
determine the requirements for emergency stopping and emergency switching off.
Pin number
Function
1
E-STOP A1
2
Not connected
3
0 V
4
E-STOP B1
5
E-STOP RESET A
6
E-STOP A2
7
E-STOP B2
8
Not connected
9
E-STOP RESET B
NOTE:
The emergency stop function of the SPA3-2 can be used as part of a Performance Level B system as per BS EN ISO13849-
1:2015 (or current version). To meet a higher performance level an external safety system must be fitted.