RH-D AND RH-W ELECTRIC DUCT HEATERS
RENEWAIRE.COM
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
1.800.627.4499
14
INSTALLATION
Remove two screws from bottom
of thermostat and lift cover off.
Install base plate on wall using provided
hardware or mount directly on standard 2 X 4
electrical junction box.
Pull low-voltage wiring through
opening in the back of the
thermostat and then attach
thermostat to base plate using
the provided two short screws.
Each thermostat is provided with a mounting base plate and all necessary mounting hardware.
• Mount the base plate on the wall using provided anchors and screws or mount it directly on a
standard 2 X 4 electrical junction box..
• Open the thermostat housing by removing two screws on the bottom of the thermostat and lift
the cover off.
• Pull low voltage wiring through the opening in the back of the thermostat and then mount the
thermostat on the base plate using the provided two short screws.
• Connect low voltage wiring as shown in illustration at right.
• Set the DIP switches to desired settings. See chart and illustration at right.
• Reinstall the front cover.
• Reconnect power to the heater, which will provide 24 VAC to the thermostat.
RISK OF ELECTRIC SHOCK OR EQUIPMENT DAMAGE
Whenever electrical wiring is connected, disconnected or changed, the power supply to the electric
heater and its controls must be disconnected. Lock and tag the disconnect switch or circuit breaker
to prevent accidental reconnection of electric power.
CAUTION CAUTION