11

1.800.627.4499

HE-Series Indoor

ERV

2.4 E-BOX

Every HE4XINV is equipped with what is known as an “E-Box.” High-voltage supply wiring 
and low-voltage control wiring is all terminated here. When VFDs are installed in the unit, the 
VFD keypads are installed here. If optional integrated programmable controls are installed, an 
additional 24 VAC transformer is installed here to power both the controller and its dedicated 
sensors.

FIGURE 2.4.0 E-BOX WITH MOTOR STARTERS

NOTE: Every ERV 
has an attached 
electrical connec-
tion box, known as 

the E-Box. It is attached to 
the outside of the ERV and 
all electrical connections 
are made there. There is 
a high-voltage side and 
a low-voltage side. See 
Figure 2.4.0.

COMPONENTS

2.5 FILTERS

All HE4XINV units come equipped with eight each MERV 8 20" X 20" X 2" thick pleated paper 
filters. MERV 13 filters can be ordered as an accessory and are shipped loose.

2.6 FACTORY INSTALLED OPTIONS

All HE4XINV units can be ordered with factory installed options.  See Unit Configuration Code on 
page 8. 
Options will have supplemental manuals shipped with the unit. 
For Isolation Dampers, see 

Isolation Dampers Supplemental Manual

For Commercial Controls, see 

Commercial Controls Supplemental Manual

For Filter Alarm, see 

Filter Alarm Supplemental Manual

For Economizer/Bypass, see 

Bypass Economizer Supplemental Manual

For Isolation Dampers, see 

Isolation Dampers Supplemental Manual

For Variable Frequency Drive, see 

VFD Supplemental Manual

3.0 SHIPPING/RECEIVING/HANDLING

HE4XINV units are palletized at the factory and then shipped by common carrier. Upon receipt 
by the installer, the shipment should be inspected for shipping damage, prior to unloading. Any 
discovered shipping damage should be immediately reported to the RenewAire sales rep and the 
damage must be recorded on the Bill Of Lading, prior to signing for acceptance of the shipment. 
The unit can be handled with a fork lift or a crane. Prior to moving the unit, verify that all 
latches and securing bolts on the cabinet doors are tightly fastened. 

www.renewaire.com     (800) 627- 4499 

[email protected]

GROUND BUS

DISCONNECT SWITCH

POWER SUPPLY WIRING 

CONNECTED HERE ON TOP 

OF DISCONNECT SWITCH

OPTIONAL UNIT FUSING

www.renewaire.com     (800) 627- 4499 

[email protected]

24 VAC STEP-DOWN TRANSFORMER 

(WITH BUILT-IN CIRCUIT BREAKER)

LOW-VOLTAGE TERMINAL STRIP 

(ALL CONTROL WIRING IS CONNECTED HERE)

Summary of Contents for HE4XINV

Page 1: ...HE4XINV HE SERIES ERV Installation Operation and Maintenance Manual HE 3XINV Shown...

Page 2: ...breaker to prevent accidental reconnection of electric power RISK OF CONTACT WITH HIGH SPEED MOVING PARTS Disconnect all local and remote power supplies verify with a voltmeter that electric power is...

Page 3: ...seasonal maintenance and include start up maintenance tasks as described in this manual NOTICE UNIT INFORMATION Record information as shown below In the unlikely event that factory assistance is ever...

Page 4: ...5 13 4 6 7 5 3 32 6 15 1 11 9 45 20 15 14 5 13 4 6 7 5 3 35 9 16 6 13 1 45 20 15 AIRFLOW PERFORMANCE Motor HP Blower RPM Sheave Adj Turns Open External Static Pressure in w g 0 00 0 25 0 50 0 75 1 00...

Page 5: ...8 Overall 34 1 8 Minimum Service Area 45 5 8 Minimum Service Area TOP VIEW Door Swing Model HE4XINV Drawing Type Unit Dimension Version MAY18 ABBREVIATIONS EA Exhaust Air to outside OA Outside Air int...

Page 6: ...tage Control System 17 5 3 3 How to Reset the 24 VAC Circuit Breaker 17 5 3 4 Limits of Power Output 17 5 4 ELECTRIC WIRING SCHEMATIC 18 5 5 EXTERNAL LOW VOLTAGE CONTROL WIRING CONNECTIONS 20 5 5 1 Si...

Page 7: ...igure 6 4 0 HE4XINV Pressure Port Locations 24 Figure 6 4 1 Initial Pressure Drop of MERV 8 Filters Supplied with this unit 25 Figure 6 4 2 Initial Pressure Drop of MERV 13 Filters Available as an Acc...

Page 8: ...Face damper also acts as Isolation damper in EA or RA Airstream Restrictions 1 Voltage Codes 1 only available with Phase Code 1 Single Phase 2 Voltage Codes 4 8 only available with Phase Code 3 Three...

Page 9: ...cted HE4XIN see the HE4XINH manual For information on the outdoor version of this product see the HE4XRT manual These ERVs are commonly installed as part of an air handling system that provides heatin...

Page 10: ...ulation on the inside Units are available in either single wall or double wall construction Doors are hinged and are fitted with stainless steel machine screws through the faces to prevent accidental...

Page 11: ...r Isolation Dampers see Isolation Dampers Supplemental Manual For Commercial Controls see Commercial Controls Supplemental Manual For Filter Alarm see Filter Alarm Supplemental Manual For Economizer B...

Page 12: ...W x70 H 1 332 lbs 3 1 2 Shipping Dimensions and Weight SHIPPING RECEIVING 3 2 1 HE4XINV Hoisting Weights and COG 9 12 06 MF SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE RenewAire LLC Scale 1 24 Do...

Page 13: ...ductwork SHIPPING RECEIVING 3 4 HANDLING AND STORAGE Units that must be stored prior to installation should be left on their pallets and protected from weather and physical damage Units must be place...

Page 14: ...4 Power In C L 2 5 8 Control In 5 Fr 2 7 8 Holes for Wiring in Bottom of E Box RA FA Disconnect Switch E Box C L 8 Wiring 25 5 8 Wiring 1 5 8 Typ 37 7 8 Typ 10 1 4 Typ 46 5 8 Typ RA Inlet 42 X 14 Duc...

Page 15: ...esh air inlet on the outside of the building should be at least 10 apart to avoid cross contamination The exhaust outlet should not dump air into an enclosed space or any other structure The inlets an...

Page 16: ...verify with a voltmeter that electric power is off and wear protective equipment per NFPA 70E before working within electric control enclosure Failure to comply can cause serious injury or death Custo...

Page 17: ...ected to an excessive load or a short circuit the circuit breaker will trip to prevent the failure of the transformer When it trips the circuit breaker s button pops up Shut off the primary side power...

Page 18: ...tactor Overload 24 VAC A1 A2 95 96 1L1 3L2 5L3 2T1 4T2 6T3 Exhaust Contactor Overload 24 VAC A1 A2 95 96 1L1 3L2 5L3 2T1 4T2 6T3 Supply M Supply Fan Exhaust Fan GND L3 L2 L1 Input Power 115 VAC 1 Phas...

Page 19: ...or Overload 24 VAC A1 A2 95 96 1L1 3L2 5L3 2T1 4T2 6T3 Exhaust Contactor Overload 24 VAC A1 A2 95 96 1L1 3L2 5L3 2T1 4T2 6T3 Supply M Supply Fan M Exhaust Fan GND L3 L2 L1 Transformer COM 24V F1 Input...

Page 20: ...e OA FA blower u Install a jumper provided between terminals 4 and 5 to operate the ERV s isolation relay for the RA EA blower u Supply only 24 VAC not VDC from a Class II power source UNIT INTERNAL C...

Page 21: ...A SWITCH OR NON POWERED CONTROL USING UNIT S 24VAC POWER SUPPLY 1 2 3 4 5 Unit s 24VAC Power Supply C Isolation Relay Coil Exhaust Air Image B from Filename Control Connections HE2XRT and larger JUL14...

Page 22: ...rom a structure and bring in fresh air from outside while transferring heating or cooling energy from the exhaust air to the fresh air The HE4XINV is a very simple device and will accomplish this purp...

Page 23: ...is a conflict between the specification sources consult the HVAC design engineer A frequent requirement is for the airstreams to be perfectly balanced between Fresh Air supply and Exhaust Air dischar...

Page 24: ...e high pressure side of your measuring device to the Outside Air OA port and the low pressure side to the Fresh Air FA port u To read SCFM of Room Air RA install the high pressure side of your measuri...

Page 25: ...0 1 0 2 0 3 0 4 500 1000 1500 2000 2500 3000 3500 4000 Clean filter Pressure Drop in w g Unit Airflow CFM Initial Pressure Drop of MERV 13 Filters available option FIGURE 6 4 2 INITIAL PRESSURE DROP O...

Page 26: ...adjustable sheaves must be re set in the field to attain optimum performance of the ERV This adjustment is to be done after all ductwork is connected Adjustable sheaves are held in position on the dr...

Page 27: ...enthalpic core media and damage the cores For units that have filter air pressure differential sensors a dirty filter alarm will occur on the connected alarm or control device Filter cleanliness and r...

Page 28: ...asing Larger horsepower motors come equipped with grease fittings Before greasing any motor consult the motor manufacturer s web site to determine the correct maintenance and greasing schedule FIGURE...

Page 29: ...ld be reinstalled so that the foam gasketing is toward the back of the ERV and the core label is facing toward the front To access enthalpic cores for cleaning remove the air filters To clean enthalpi...

Page 30: ...800 627 4499 30 HE Series Indoor ERV MAINTENANCE 7 7 MAINTENANCE RECORDS MAINTENANCE LOG ENTER DATES OF SERVICE OA FILTER CHANGE RA FILTER CHANGE INSPECTION CLEANING CLEAN CORE CLEAN BLOWERS INITIALS...

Page 31: ...d assistance from the factory for a specific issue make sure that you have the information called for in the Unit Records page in the Owner Information section of this manual The person you speak with...

Page 32: ...st claims due to long term reliability derived from innovative design practices expert workmanship and Quick Response Manufacturing QRM As the pioneer of static plate core technology in North America...

Reviews: